Air System Sizing Summary for Q_first system

Project Name: Untitled 01/21/2024


Prepared by: hmm 11:58

Air System Information


Air System Name: Q_first system Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 136,0 sqm
Location: Casablanca, Morocco

Sizing Calculation Information


Calculation Months: Jan to Dec Calculation method: Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: 53,0 kW Load occurs at: Aug 1400
Total coil load: 53,0 kW OA DB / WB: 34,9/25,0
Sensible coil load: 37,9 kW Entering DB / WB: 26,3/19,8
Coil airflow: 2791 L/s Leaving DB / WB: 15,0/14,4
Sensible heat ratio: 0,715 Coil ADP: 13,7 C
Area per unit load: 2,6 sqm/kW Bypass Factor: 0,100
Load per unit area: 389,7 W/sqm Resulting RH: 56 %
Design supply temp: 15,0 C

Central Heating Coil Sizing Data


Max coil load: 19,9 kW Load occurs at: Des Htg
Coil airflow: 2791 L/s Ent DB / Lvg DB: 16,3/22,2
Load per unit area: 146,1 W/sqm

Supply Fan Sizing Data


Actual max airflow: 2791 L/s Fan motor BHP: 1,25 BHP
Standard airflow: 2770 L/s Fan motor kW: 0,93 kW
Actual max airflow per unit area: 20,52 L/(s-sqm) Fan static: 180,00 Pa

Outdoor Ventilation Air Data


Design airflow: 330 L/s Airflow per person: 4,72 L/s/person
Airflow per unit floor area: 2,43 L/(s-sqm)

Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Q_Restaurant 33,4 2791 Aug 1300 16,1 136,0 20,52

Block Load 4.15 Page 1 of 9


System Design Load Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

DESIGN COOLING DESIGN HEATING


Aug 1400 Design Heating Day
OA DB / WB 34,9 C / 25 C OA DB / WB 5 C / 1,4 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 48 sqm 1693 - 48 sqm - -
Wall Transmission 39 sqm 8186 - 39 sqm 777 -
Roof Transmission 136 sqm 3510 - 136 sqm 4894 -
Window Transmission 48 sqm 1433 - 48 sqm 2083 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 94 sqm 732 - 94 sqm 1447 -
Overhead Lighting 3750 W 3750 - 0W 0 -
Electric Equipment 1230 W 1230 - 0W 0 -
People 70 4956 6846 0 0 0
Infiltration - 1723 1965 - 5468 2
Miscellaneous - 3078 1320 - 0 0
Safety Factor 10% / 5% 10336 1728 10% 5005 1
>>Total Zone Loads - 33321 10638 - 16136 2
Thermostat and Pulldown Adjustment - -165 0 - -388 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 330 L/s 3823 4454 330 L/s 5058 0
Supply Fan Load 2791 L/s 930 - 2791 L/s -930 -
>> Total System Loads - 37909 15092 - 19876 2
Central Cooling Coil - 37909 15096 - 0 0
Central Heating Coil - 0 - - 19876 -
>> Total Coil Loads - 37909 15096 - 19876 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 9


Zone Design Load Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

Q_Restaurant DESIGN COOLING DESIGN HEATING


Aug 1300 Design Heating Day
OA DB / WB 34,5 C / 24,9 C OA DB / WB 5 C / 1,4 C
Thermostat Setpoint 25,0 C Thermostat Setpoint 18,0 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 48 sqm 1748 - 48 sqm - -
Wall Transmission 39 sqm 8546 - 39 sqm 777 -
Roof Transmission 136 sqm 3384 - 136 sqm 4894 -
Window Transmission 48 sqm 1381 - 48 sqm 2083 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 94 sqm 679 - 94 sqm 1447 -
Overhead Lighting 3750 W 3750 - 0W 0 -
Electric Equipment 1230 W 1230 - 0W 0 -
People 70 4956 6846 0 0 0
Infiltration - 1654 1901 - 5468 2
Miscellaneous - 3078 1320 - 0 0
Safety Factor 10% / 5% 10374 1717 10% 5005 1
>> Total Zone Loads - 33444 10570 - 16136 2

Block Load 4.15 Page 3 of 9


System PsychrometricsforQ_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

Location: Casablanca, Morocco


Altitude: 61,9 m
Data for: Aug DESIGN COOLING DAY, 1400
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016
1

0,014

Specific Humidity ( kg/kg )


0,012
2
5

34 0,010

0,008

0,006

0,004

0,002

0,000
0 10 20 30
Temperature (C)

Block Load 4.15 Page 4 of 9


Ventilation Sizing Summary for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

Summary
Ventilation Sizing Method: Sum of Space OA Airflows
Design Ventilation Airflow Rate: 330 L/s

Space Ventilation Analysis Table

Space Name Floor Area Maximum Maximum Required Required Required Required Uncorrected
sqm Occupants Supply Air Outside Air Outside Air Outside Air Outside Air Outdoor Air
L/s L/s/person L/(s-sqm) L/s (% of supply) L/s
Q_Restaurant 136,0 70,0 2790,9 4,72 0,00 0,0 0,0 330,4
Totals 2790,8 330,4

Block Load 4.15 Page 5 of 9


Hourly Air System Design Day Loads for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

DESIGN MONTH:Jul
Hour OA SUPPLY CENTRAL CENTRAL CENTRAL PREHEAT TERMINAL TERMINAL
TEMP C AIRFLOW COOLING COOLING HEATING COIL kW COOLING HEATING
L/s SENSIBLE TOTAL kW COIL kW COILS kW COILS kW
kW
0000 30,9 2791 25,9 37,4 0,0 0,0 0,0 0,0
0100 30,7 2791 25,6 37,1 0,0 0,0 0,0 0,0
0200 30,4 2791 25,3 36,8 0,0 0,0 0,0 0,0
0300 30,2 2791 24,8 36,2 0,0 0,0 0,0 0,0
0400 30,1 2791 24,7 36,3 0,0 0,0 0,0 0,0
0500 30,0 2791 24,0 35,2 0,0 0,0 0,0 0,0
0600 30,1 2791 24,3 35,4 0,0 0,0 0,0 0,0
0700 30,4 2791 25,2 36,5 0,0 0,0 0,0 0,0
0800 30,8 2791 28,3 40,8 0,0 0,0 0,0 0,0
0900 31,5 2791 30,6 43,7 0,0 0,0 0,0 0,0
1000 32,2 2791 33,3 47,1 0,0 0,0 0,0 0,0
1100 33,1 2791 35,4 49,9 0,0 0,0 0,0 0,0
1200 33,9 2791 37,2 52,3 0,0 0,0 0,0 0,0
1300 34,5 2791 37,5 52,5 0,0 0,0 0,0 0,0
1400 34,9 2791 37,5 52,5 0,0 0,0 0,0 0,0
1500 35,0 2791 37,2 52,1 0,0 0,0 0,0 0,0
1600 34,9 2791 36,0 50,4 0,0 0,0 0,0 0,0
1700 34,5 2791 35,5 50,0 0,0 0,0 0,0 0,0
1800 34,0 2791 33,2 46,7 0,0 0,0 0,0 0,0
1900 33,3 2791 32,0 45,4 0,0 0,0 0,0 0,0
2000 32,7 2791 31,2 44,6 0,0 0,0 0,0 0,0
2100 32,1 2791 29,6 42,5 0,0 0,0 0,0 0,0
2200 31,6 2791 28,8 41,5 0,0 0,0 0,0 0,0
2300 31,2 2791 27,4 39,6 0,0 0,0 0,0 0,0
Loads calculated using Transfer Function Method

Block Load 4.15 Page 6 of 9


Hourly Zone Loads for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

ZONE: Q_Restaurant
DESIGN MONTH: Jul
Hour OA TEMP C ZONE TEMP RH (%) ZONE ZONE TERMINAL TERMINAL ZONE
C AIRFLOW SENSIBLE COOLING HEATING HEATING
L/s LOAD W COIL W COIL W UNIT W
0000 30,9 25,4 68,0 2790,9 23631,5 0,0 0,0 0,0
0100 30,7 25,3 68,0 2790,9 23051,6 0,0 0,0 0,0
0200 30,4 25,2 68,0 2790,9 22523,5 0,0 0,0 0,0
0300 30,2 25,2 69,0 2790,9 22066,9 0,0 0,0 0,0
0400 30,1 25,1 69,0 2790,9 21679,1 0,0 0,0 0,0
0500 30,0 25,2 70,0 2790,9 21387,8 0,0 0,0 0,0
0600 30,1 25,3 70,0 2790,9 21733,3 0,0 0,0 0,0
0700 30,3 25,4 68,0 2790,9 23046,2 0,0 0,0 0,0
0800 30,8 25,2 65,0 2790,9 25236,5 0,0 0,0 0,0
0900 31,4 25,3 63,0 2790,9 27752,8 0,0 0,0 0,0
1000 32,2 25,3 60,0 2790,9 30004,3 0,0 0,0 0,0
1100 33,1 25,3 58,0 2790,9 31697,7 0,0 0,0 0,0
1200 33,8 25,1 57,0 2790,9 32688,3 0,0 0,0 0,0
1300 34,4 25,2 57,0 2790,9 32984,7 0,0 0,0 0,0
1400 34,8 25,2 57,0 2790,9 32807,7 0,0 0,0 0,0
1500 35,0 25,1 57,0 2790,9 32366,8 0,0 0,0 0,0
1600 34,8 25,3 58,0 2790,9 31681,9 0,0 0,0 0,0
1700 34,5 25,1 59,0 2790,9 30783,3 0,0 0,0 0,0
1800 33,9 25,4 61,0 2790,9 29675,2 0,0 0,0 0,0
1900 33,3 25,4 62,0 2790,9 28429,6 0,0 0,0 0,0
2000 32,7 25,1 63,0 2790,9 27203,9 0,0 0,0 0,0
2100 32,1 25,2 64,0 2790,9 26098,0 0,0 0,0 0,0
2200 31,6 25,1 65,0 2790,9 25127,9 0,0 0,0 0,0
2300 31,2 25,2 66,0 2790,9 24309,6 0,0 0,0 0,0
Loads calculated using Transfer Function Method

Block Load 4.15 Page 7 of 9


System Psychrometrics Table for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

DESIGN COOLING DAY, Aug 1400

TABLE 1: SYSTEM DATA

Component Location Dry-Bulb Specific Airflow L/s Sensible Latent Heat


Temp C Humidity Heat W W
kg/kg
Ventilation Air Inlet 34,8 0,01599 330 3823 4454
Vent - Return Mixing Outlet 26,3 0,01192 2791 - -
Central Cooling Coil Outlet 15,0 0,01007 2791 37909 15096
Central Heating Coil Outlet 15,0 0,01007 2791 0 -
Supply Fan Outlet 15,3 0,01007 2791 930 -
Zone Air - 25,2 0,01138 2791 33155 10638
Return Plenum Outlet 25,2 0,01138 2791 0 -

Site Altitude = 61,9 m


Air Density x Heat Capacity x Conversion Factor = 1,1984 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor = 2926,0 W/(L/s)

TABLE 2: ZONE DATA

Zone Name Zone T-stat Mode Zone Temp Zone Airflow Reheat Coil
Sensible C L/s Load W
Load W
Q_Restaurant 33321 Cooling 25,2 2791 0

Block Load 4.15 Page 8 of 9


System Psychrometrics Table for Q_first system
Project Name: Untitled 01/21/2024
Prepared by: hmm 11:58

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Component Location Dry-Bulb Specific Airflow L/s Sensible Latent Heat


Temp C Humidity Heat W W
kg/kg
Ventilation Air Inlet 5,0 0,00275 330 -5058 0
Vent - Return Mixing Outlet 16,3 0,00275 2791 - -
Central Cooling Coil Outlet 16,3 0,00275 2791 0 0
Central Heating Coil Outlet 22,2 0,00275 2791 19876 -
Supply Fan Outlet 22,5 0,00275 2791 930 -
Zone Air - 17,8 0,00275 2791 -15748 -2
Return Plenum Outlet 17,8 0,00275 2791 0 -

Site Altitude = 61,9 m


Air Density x Heat Capacity x Conversion Factor = 1,1984 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor = 2926,0 W/(L/s)

TABLE 2: ZONE DATA

Zone Name Zone T-stat Mode Zone Temp Zone Airflow Reheat Coil
Sensible C L/s Load W
Load W
Q_Restaurant -16136 Heating 17,8 2791 0

Block Load 4.15 Page 9 of 9