OFFICE OF THE SUPERINTENDING ENGINEER (O&M)

RABS HPS, MPPGCL,BARGI NAGAR, JABALPUR(M.P.)482056.


Ph: 0761-2880268, Fax: 2880412. Email- seoandmbargi@gmail.com

NO.SE(O&M)/BARGI/P&W/ 1306 Barginagar,dt. 05.01.2019.


To,

“on mppgcl web-site”

Sub- Enquiry for supply of 4 nos., Indian Origin, Hermetically sealed, Out door, Oilfilled,Self Cooled,
Three core, Dead Tank, 33KV Current Transformer having porcelain Insulators, with Hot Dip Galvanized
Tank ,Single phase, CTR 400-200/1-1-1 Amp and Cree page Distance 900 mm for 2x45 MW RABS HPS
Barginagar .

Dear Sir,
Being the manufacturer of Indian Origine, Hermetically sealed, Out door, Oilfilled,Self Cooled,
Three core, Dead Tank, 33KV Current Transformer having porcelain Insulators, with Hot Dip Galvanized
Tank, Creepage distance 900 mm and suitable 8 nos. Bi metallic connector for ACSR Zebra conductor
Single phase, CTR 400-200/1-1-1 Amp. You are hereby requested to submit your quotation for supply
of 3 nos. CT including Freight , Insurance and packaging forwarding charges on single enquiry basis in
our official address as mentioned above as per enclosed supply schedule and technical details . The
terms and condition of enquiry shall be as mentioned bellow-

1.Due Date- Your offer should reach this office by registered post by 25.01.2019 at 15.00 hrs and shall
be opened on same date on 16.00hrs.

2 Price – The Price shall be firm and fixed on FOR destination basis and shall be inclusive of
freight, insurance, packaging forwarding charges and GST . The validity of offer shall be180 days from
the date of opening of Bid.

3. Payment- 100% payment shall be made to firm within 45 days or as per queue whichever is later
after receipt of material in full and good condition in our store .
4.Guarantee- Supplied material shall be Guaranteed for one year from the date of commissioning or 18
months from date of supply. During Guarantee period the firm shall be responsible of
epair/replacement of defective CT free of cost at site ,if it is arisen due to poor workmanship on
supplied CT or due to defective metallurgy of material .
5. Security deposit - Not required.

6. Earnest Money - not required .

7. Penalty- In case of delay in supply of material beyond the delivery schedule as stipulated in
purchase order shall attract penalty as liquidated damage at the rate of 0.5% per week subject to
maximum 10% of order value.
…02…

8. Inspection - The firm shall offer inspection of CTs before dispatch. MPPGCL shall have the right to
waive off the inspection.

9. Delivery schedule- Within 8-10 weeks after date of inspection or waival.

10. Standards- The current Transformer shall fully comply with the latest issue of Indian Standard
2705 (Part-1,ii,iii&iv)with latest amendment thereof upto the date of issue of this tender.

11. Consignee- Assistant Engineer (Stores), RABS HPS Barginagar ,Dist- Jabalpur (MP) 482056.

12. Transportation & Insurance- shall be arrange by the firm at HPS site stores.

13. Estimated amount - Rs . 162000/- including freight, Insurance and package forwarding Charges
and GST.

14. SUBMISSION OF BID:- Single envelope containing GST, previous order copy, Price bid.

15. The supplied CT & terminal connector must comply the attached technical specification as per
anexeure-3 and firm shall responsible for it

16 . Court of jurisdiction- IN case of any dispute the competent court shall be at Jabalpur.

Enclosures - Price Bid Format.


Supply schedule.
Technical Specification of 33 KV CT.

(P C Mishra)
SUPERINTENTING ENGINEER (O&M)
RABS HPS BARGINAGAR
NO.SE(O&M)/BARGI/P&W/ 1306 Barginagar,dt. 05.01.2019.

Annexure -1

SUPPLY SCHEDULE

Sl.No. Description of CT Quantity


required
1 Out Door, Three core ,Oil Filled ,Hermetically sealed,Self cooled Single pole multi 4nos.
cored,Dead Tank,33 KV Current Transformer with porcelain insulator having Creepage
distance of 900 mm(min.)and terminal connector suitable for ACSR Zebra conductor .
CTR 400-200/1A-1A-1A . And according to the technical specification attached in
Annexure- 3 .

Nominal system Voltage 33/36 kV ,System Neutral -effectively earthed


BIL 36/70/170 kV
Applicable standard latest issue of Indian Standard 2705 (Part-1,ii,iii&iv)with
latest amendment thereof up to the date of issue of this
enquiry.
2 Bimetallic Connector For ACSR Zebra 8 nos.

(P C Mishra)
SUPERINTENTING ENGINEER (O&M)
RABS HPS BARGINAGAR
NO.SE(O&M)/BARGI/P&W/ 1306 Barginagar,dt. 05.01.2019.

Annexure -2

PRICE BID FORMAT

Sl.No Description of CT Quantity Unit rate Total


Required Amount
1 three core, dead tank, Oil filled, Self Cooled ,Single 4Nos.
Pole and multicored, Hermetically sealed,33 KV
current Transformer with porcelain insulator having
Cree page distance of 25 mm/KV i.e. 900mm(min.)and
terminal connector suitable for ACSR Zebra
Conductor.
CTR 400/1-1-1 Amp. anbd according to the attached
technical specification in Annexure 3

2 Bimetallic Connector For ACSR Zebra 8 nos.


3 Freight
4 Packaging forwording Charges
5 Insurance
6 Total Value
7 IGST/SGST/CGST@.....
8 Total Cost Of Supply

Authorized Signatory of Firm


and Rubber Seal
NO.SE(O&M)/BARGI/P&W/ 1306 Barginagar,dt. 05.01.2019.

TECHNICAL SPECIFICATION Annexure -3

Sl.No. Particulars 33 KV CT Specification


1 Manufacture’s type Out Door
designation of CT
2 CTR 400-200/1-1-1 A
3 Rated Voltage 33/36 KV, effectively earth system
3 Core Core1 Core2 (Metering) Core 3
(Protection)
Rated VA 30 30 -
Accuracy Class 5P20 0.2S PS Vk≥464V,Ie≤100mAat Vk
Rated Secondary 1 Amp 1 AMP 1 Amp
current
Short Time Thermal 25 kA 25 kA 25 kA
Current for 3 Sec.
Frequency 50 Hz 50 Hz 50hz
SLF/ISF 10 =/<7.5
4 BIL 36/70 /170
5 Rated Cont. 120 % of normal primary current
Thermal Current
6 Applicable Latest issue of Indian Standard 2705 /1992 (Part-1,ii,iii&iv)with latest amendment thereof upto the
date of issue of this enquiry.
Standard
7 Compatible to Type 1.Short Time Current Test
2.Temperature rise Test
Test
3.Lightning Impulse Voltage
withstand test.
4.High Voltage Power Frequency
wet withstand voltage test.
5.determination of errors according
to the requirements of
appropriate accuracy class.
8 Compatible to 1.Verification of terminal markings
and Polarities.
Routine Test
2.Power Frequency Dry
withstanding test on primary
windings.
3.Power Frequency Dry
withstanding test on secondary
windings.
4. Over Voltage inter turn test.
5. determination of errors
according to requirement of the
appropriate accuracy class.
6. Pressure test on one CT’s Tank.
9 Porcelain Insulator BIL of Porcelain Insulator shall be as specified and porcelain shall be free from cavity and other flow.
This shall be so designed as to have ample insulation and mechanical strength.
10. Dynamic Rating Peak value of the rated dynamic current which CT can withstand without being Damage electrically or
mechanically with the secondary winding short circuited shall not be less than 2.5 times the rated
short time thermal current.

(P C Mishra)
SUPERINTENTING ENGINEER (O&M)
RABS HPS BARGINAGAR
NO.SE(O&M)/BARGI/P&W/ 1306 Barginagar,dt. 05.01.2019.

TECHNICAL SPECIFICATION
Annexure -3
Sl.No. Perticulars 33 KVCT Specification
11 Terminal connectors 1.Terminal connector shall be manufactured
by pressure die casting& tested as per
IS:5561.
2.ALL Casting Shall be free from blow holes
,surface blisters, craks and cavity. All sharp
edges and corner shall be blurred and
rounded off. No part of Clamp shall be less
than 12 mm thick.
3.The Nut, bolts and washer shall be hot dip
galvanized.
4.The bimetallic strips/sleeves liner of
minimum thickness of 2 mm shall be made
by electroplating.
5.All current carrying parts parts shall have
minimum contact resistance.
6. it shall be suitable for ACSR Zebra
conductor.
12 Secondary Terminal 1.The secondary terminal invariably be
maked as –
1S1 &,1S2 &1S3for protection core and 2S1
.2S2&3S3 for Metering Core.
The weather proof terminal box shall be
provided with one cable gland for each core
for 4 core 1100 Volt grade PVC/XLPE
insulated 2.5 sq. mm copper control cable .
13. Highest System Voltage withstanding Capacity (rms) 36 KV
14. Design of core Cores shall be designed for minimum
saturation factor of 10 for highest setting.
15 Creepage distance 900 mm(min)
16 Gasket Used Joint less 5 mm (Min.)
17. Primary and secondary winding material Copper
18. Secondary Limiting EMF 65 V (Approx.)
19 Secondary Winding resistance at 75 degree C 0.2 Ω
20 Oil Tank Thickness Minimum 3 mm
21 Short Circuit Level 1000 MVA
22 Top Tank cover Plate It shall be overlapped to tank flange by
10mm and inclined downwards in all sides
to avoid the rain water entry in the tank.
23 CT’s Transformer oil Minimum Oil BDVof 70 KV is required.The
oil shall comply in all respect with the latest
version of IS:335:1983.
24 Insulation Class of windings Class A

(P C Mishra)
Superintenting Engineer (O&M)
RABS HPS Barginagar