Professional Documents
Culture Documents
Introduction
Electrical installation design for a building provides primarily the necessary energy/power
requirement of the building in order to facilitate the functional service the buildings constructed
for. Power supply installation is used to provide the energy requirement for illumination/lighting
the area, socket outlet for electronics gadget and heat for cooking and water boiling, water pump,
air conditioning service and other auxiliary services. Besides these other services such as
telecommunication, informational data transfer and multimedia installation should be included in
the design procedure. These services installation depends on the type of building, the function of
the room or area and the scale of the demand of the user or owner.
Protection and safety against electric shocks & electric fires consists in providing provision for
basic protection (protection against direct contact) with coordinated provision for fault protection
(protection against indirect contact- earth leakage current). The provision for fault protection
consists measures of automatic disconnection of supply as well as the implementation of a system
earthing and equipotential bonding (TT, TN and IT system). Protection against external fault
(Lightning protection) should consider the probability and possible magnitude of lightning stroke
and the associated risk assessment for life and equipment damage encountered.
Electrical design procedure needs to consider compliance with regulations. Regulations may be
based on national (EBCS-10) or international standards such as the IEC 60364 series. Conformity
of equipment according to the appropriate product standards used within the installation is also of
prime importance for the level of safety and quality. Environmental conditions as well as energy
efficiency will become more and more stringent and will need to be considered at the design stage
of the installation during material selection. Implementation of active energy efficiency measures
within the electrical installation can produce high benefits for the user or owner: reduced power
consumption, reduced cost of energy, better use of electrical equipment.
A review of all applications needing to be supplied with electricity is to be done. Any possible
extensions or modifications during the whole life of the electrical installation are to be considered.
The total current or power demand can be calculated from the data relative to the location and
power of each load, together with the knowledge of the operating modes (steady state demand,
starting conditions, non-simultaneous operation, etc.) Estimation of the maximum power demand
may use various factors depending on the type of application; type of equipment and type of
circuits used within the electrical installation.
Determination of the most suitable architecture of the LV main distribution and LV power
distribution level is often the result of optimization and compromise. The distribution equipment
(panelboards, switchgears, circuit connections, ...) are determined from building plans and from
the location and grouping of loads. The type of premises and allocation can influence their
immunity to external disturbances. In most electrical installation, different external influences may
be encountered and need to be considered independently. As a result of these external influences
proper selection of equipment according to their IP or IK codes has to be made.
The Low Voltage level electrical installation will be connected to the local power network and
service provider, in this case the Ethiopian Electric Power Utility (EEU), and will (necessarily)
be metered according to LV tariffs.
Number of Floor: Nine (basement floor, ground floor, first up to seventh floor)
• The power supply to the building will be tapped off from the Transformer at 400 V, three
phase, four wire and 50Hz system with solidly grounded neutral, TN-S earthing
arrangement. The service-main cable from the distribution transformer to the KVAh meter
is buried in the ground inside 90 mm PVC conduit. The Distribution Transformer is fed
from nearest feeder at 15 kV, 3 phase 3 wire system. The installation, commissioning
authorization of the distribution transformer is done by local power supply service
provider, in this case EEU.
Low Voltage Electrical System Installation Design Includes:
Lamp Selection
Each category has different operating characteristics and is appropriate in different circumstances,
depending on the relative importance of cost, life, color appearance, color rendering and luminous
efficacy, aesthetics and mode of the environment.
It should be noted that the Building Regulations now require the use, in most cases, of energy
efficient lamps. However, the luxurious nature of the hotel dictates to consider aesthetics and
modes of the service the rooms provide.
The following table is a quick reference of the most common lamp types, comparing their energy
use, color rendering, life, and where they are typically used.
Light Source Energy Color Life Lighting Mode of Sample
efficiency Rendering Function environment Application
Index (Apparent
(CRI) color)
Luminaire Selection
For good lighting practice, it is important for visual performance, the feeling of comfort and well-
being as well as safety of the personnel to be considered. In this regard, selection of appropriate
Luminaire (light fitting) plays a vital role. During the selection of luminaire, the following
parameters determine luminous environment:
Note: Lighting control can be required to achieve adequate flexibility for the variety of tasks
performed.
The CIBSE Code for Interior Lighting Design as well as European standard for interior workplace
lighting EN 12464 series gives recommended maintained illuminances for a wide variety of
installations. The level of illuminance required depends on four factors:
The method used for Interior Lighting Design in this project is LUMEN (luminous flux) METHOD
OF LIGHT CALCULATION. This method considers down lighting scheme and used to calculate
the average illuminance on working planes, or to calculate the number of luminaires required to
provide a specified average illuminance in rooms. The following formula is used:
N(n ∙ ϕ) × MF × UF E×A
E= or N =
A MF × UF × n × ϕ
Where:
MF = Maintenance factor
UF = Utilization factor
Lamp flux output – Consider an installation where lamps are to be replaced after 6000 hours use.
Therefore, the lamp manufacturer's data is checked to see the lamp output after 6000 hours of use.
Maintenance Factor (MF) – take account of the reduction in illuminance over the maintenance
period.
Where:
Utilization factor (UF) – takes account of the loss of light due to absorption on room surfaces.
L×W
RI =
(L + W) × Hm
Where:
Hm = the height of the luminaires above the working plane (working plane taken as 0.7
meter above the floor)
Sample Calculation:
Note:
• Light points are grouped in maximum number of 10 to form a single circuit not to exceed
10A single-phase circuit breakers.
• Generally switching mechanism shall be based on the following scenario:
Exterior lighting shall be managed with Tumbler switch.
Interior lighting shall be controlled with surface/ flush mounted switches
• Lighting of the entire building is proposed to use light fixtures with energy saving LED,
compact fluorescent lamps, and regular fluorescent tube lamps with electronic ballasts with
high PF =0.90 or greater correction.
2. Estimation of Power Demand and Current Requirement of Different Loads
• Power rating of the elevator
ρ × Q × g × Heffective
Pin = Watt
η
Where:
Hresidual = residual height increments due to pipe surface friction and pipe bending
(taken as a maximum 20% of the elevational height of water tanker = 5 m)
Hence,
Note: Socket outlets not exceeding six in numbers are grouped into a single circuit with 16A
single-phase circuit breakers. The socket outlets are grouped in such away as not to exceed
1.6KW per circuit.
3. Conductor (wire or cable) Selection, Sizing and Containment (conduit, trunk, duct …)
P
Ib = for single phase circuit
V × cos ∅
P
Ib = for three phase circuit
√3 × V × cos ∅
P × kb
Ib = for lighting cuircuit
v × cos ∅
Where;
kb = a coefficient which has a value 1 for lamps which do not need any auxiliary starter
and 1.25 for lamps which need auxiliary starter
The current carrying capacity of the Conductor and its corresponding size is determined as per
standard table B.52.4 of IEC 60364-5-52, which take into consideration the conductor type,
insulation and sheath type, and method of installation.
Note: As code of practice, the minimum conductor size for any circuit load is taken to be 2.5 mm2.
The basic criterion to select a conductor/cable size is;
Ib ≤ Iz
Where;
Iz is the current carrying capacity of the conductor or cable under specified condition.
when carrying load current there is a voltage drop between the origin of the circuit and the load
terminals. The correct operation of a load (a motor, lighting circuit, etc.) depends on the voltage at
its terminals being maintained at a value close to its rated value. The cable size which is determined
by current capacity should be evaluated for voltage drop from the point of supply to the load.
For an electrical conductor with impedance Z, the voltage drop is calculated by the following
formula:
L
∆V = k × Z × Ib = k × Ib × (r cos φ + x sin φ) volt
n
Where;
Ib [A] is the load current; if no information is available, the cable carrying capacity Iz shall
be considered;
Normally, the percentage value in relation to the rated value V is calculated by:
∆V
∆V% = × 100
V
Ib ≤ In ≤ Iz
Ie ≤ 1.45Iz
Where:
In is the rated current of the protective device; for adjustable protective releases, the rated
current In is the set current;
Ie is the current ensuring effective operation in the conventional time of the protective
device.
A cable is protected against short-circuit if the specific let-through energy of the protective device
(I2t) is lower or equal to the withstood energy of the cable (k2S2):
I2 × t ≤ K 2 × A2
Where:
I2t is the specific let-through energy of the protective device which can be read on the curves
supplied by the manufacturer or from a direct calculation in the case of devices that are not limiting
and delaying; I is short circuit current and t is breaker tripping time
A is the cable cross section [mm2]; in the case of conductors in parallel it is the cross section of
the single conductor;
K is a factor that depends on the cable insulating and conducting material (in this case, K = 115 as
per IEC 60364-4-43).
In × 100 S × 103
Isc = where In =
Vsc √3 × Vo
Where:
Vsc = short-circuit impedance voltage of the transformer in %. (For oil immersed type, Vsc
= 4 for 50 – 750 kVA or = 6 for 800 – 3200 kVA)
• In case of several transformers in parallel feeding a busbar, the value of fault current on an
outgoing circuit immediately downstream of the busbars can be estimated as the sum of
the Isc from each transformer calculated separately.
Vo
Isc =
√3 × ZT
Where:
Vo = phase-to-phase voltage of the open circuited secondary windings of the power supply
transformer(s).
ZT = total impedance per phase of the installation upstream of the fault location (in Ω)
➢ For network upstream of the MV/LV transformer: The 3-phase short-circuit fault level Psc,
in kA or in MVA is given by the power supply authority concerned, from which an
equivalent impedance can be deduced. A formula which makes this deduction and at the
same time converts the impedance to an equivalent value at LV is given, as follows:
Vo2
Zs =
Psc
Where:
For Transformers: The impedance Ztr of a transformer, viewed from the LV terminals, is given by
the formula:
Vo2
Ztr = Vsc ×
Sn
Where:
In the absence of more precise information on transformer characteristics, Cenelec 50480 suggests
to use the following guidelines: if Vo is not known, it may be assumed to be 1.05 Vn.
For Busbars and Circuit conductors: The resistance of busbars is generally negligible, so that the
impedance is practically all reactive, and amounts to approximately 0.15 mΩ/meter length for LV
busbars
Where:
• ρ has to be considered:
• Cable reactance values can be obtained from the manufacturers. For cross-sectional area
of less than 50 mm2 reactance may be ignored. In the absence of other information, a value
of 0.08 mΩ/meter may be used (for 50 Hz systems) or 0.096 mΩ/meter (for 60 Hz systems).
• Values of r as a function of the temperature, cable insulation and cable core material,
according to IEC60909-0 and Cenelec TR 50480 (in mΩ.mm²/m).
20 °C PR/XLPE 90 °C PVC 70 °C
Note: All wires and cables shall run in rigid thermoplastic conduit of appropriate size (that confirm
to DIN 49017) of not less than 16mm diameter under plastered wall or slab and/or ceiling.
Sample Calculation
Protection against indirect contact hazards can be achieved by automatic disconnection of the
supply as well as the exposed-conductive-parts of equipment are properly earthed.
IT earthing system with the neutral point of its power supply source is connected to earth through
high standard impedance. In this system, all exposed and extraneous-conductive-parts of the
installation are earthed via an installation earth electrode. A permanent monitoring of the insulation
of phase to earth must be provided, coupled with an alarm signal (audio and/or flashing lights, etc.)
operating in the event of a first earth fault.
The maximum length of a circuit or the maximum protected length (MPL) in a IT-earthed installation
is given by the formula:
0.8 × √3 × 𝑉 × 𝐴𝑝ℎ
𝐿𝑚𝑎𝑥 = 𝑓𝑜𝑟 3 − phase 3 − wire installation
2 × 𝜌 × 𝐼𝑎 × (1 + 𝑚)
0.8 × 𝑉 × 𝐴𝑝ℎ
𝐿𝑚𝑎𝑥 = 𝑓𝑜𝑟 3 − phase 4 − wire installation (This is the design case)
2 × 𝜌 × 𝐼𝑎 × (1 + 𝑚)
Where:
Ia = the current which assures operation of the protective fuse concerned, in the specified
time.
m = Aph/APE =
Aph = cross-sectional area of the phase conductors of the circuit concerned in mm2.
APE = cross-sectional area of the protective conductor concerned in mm2.
Protective conductor cross section for phase and protective conductors having the same insulation
and conductive material.
Phase conductor cross section, Aph Protective conductor cross section, APE
[mm2] [mm2]
A ≤ 16 A
16 < A ≤ 35 16
A > 35 A/2
5. LV main distribution, LV sub distribution architecture and LV switchgear Design
Incoming middle voltage (15 kV) power from EEU transformed into 3-phase 400 V by
customer DT and then let through three-phase energy meter to reaches to the Main Distribution
Board (MDB-BF) located on the basement floor.
All Distribution Boards is rated with 3-phase 400V supply and having reserve capacity of a
minimum 25% spare space of enclosure, and 35% spare load capacity. Sub Distribution Boards
(SDBs) are situated in suitable location on every floor in accessible locations for safety and
operational requirements.
Further all final circuits are fed through PVC insulated HOV5-U conductors inside PVC
conduits of 16mm, 19mm, 21mm, 27 mm, 32 mm … diameters as appropriate and as shown
on the drawings.
Circuit breakers for branch circuits rated up to 60 amps shall be MCB (miniature circuit
breakers) as per IEC 60947-2. Breakers for circuits with loads beyond 60 amps shall also be
molded case type. Alongside the main circuit breakers, additional Residual Current Device
(RCD) of appropriate rating (30mA, 100mA) are recommended to ensure safety measures
against the risk of electrocution, and fire caused by earth faults.
The cabling part shall have corresponding labels. The cables shall have a label at each end.
Unless indicated otherwise the conduit diameter to individual outlets is 19mm & 25mm as
shown on BOQ. Conduit for group of cables to pull boxes shall be sized to accommodate the
number of cables to be contained. Maximum conduit size used shall be 50mm diameter. Use
parallel conduits to contain cables in excess of 50mm diameter conduit.
General‐purpose Dynamic Moving Coil Microphone having low impedance with long line and
uni‐directional characteristics for reducing acoustic feedback/howling specially in indoor
sound system. Sensitivity of the microphone shall be of the order of ‐55dB relative to 0.0002
dyne/cm for an impedance of 50 ohms. The microphone chosen should have uniform
frequency response within ± 3.0 dB from 100 to 10000 Hz.
Use of more than one microphone may be essential in large stages. In such cases, output from
several microphones should be mixed in a mixing system and the common output fed to the
amplifier, where the amplifier itself is capable of mixing individual microphone inputs,
separate mixing system is not required.
The microphone plugs and sockets should be of multi‐contact (three or more) type and freely
interchangeable.
A windscreen consisting of a wire framework covered with silk, designed to fit over the outside
of a microphone to reduce the effects of wind noise, should be included.
Microphone should be, as far as possible, behind the loudspeaker in order to minimize the
acoustic feed-back.
Microphone cord is provided with each microphone. Length of this cord is about 10 meters to
20 meters. This cord is a three-core braided shield cable connected with jack plug at one end
and XLR plug at another end. Jack plug is inserted in amplifier’s microphone socket and XLR
plug is connected with microphone.
All the loudspeakers in each group should be connected in parallel and in phase across the
output line.
Cone type, Category “A”, and High-Fidelity Column loudspeakers are employed and shall be
installed vertically at a height of 1.5 m above the platform level and inclined at an angle of 8
degree to 10 degree towards the ground.
All the loudspeakers in each group should be connected in parallel and in phase across the
output line.
The output power of the amplifying system should be so chosen as to be capable of establishing
at any point amongst the audience, a sound level of 80 dB during operation, the gain controls
of the amplifying system should be so set that the signal reach each member of audience at
comfortable listening level.
The amplifying system should have sensitivity sufficient to operate directly from the lowest
and highest input voltages. The frequency response of the amplifiers should be within ± 3.0
dB from 100 to 12000 Hz for "A" Category reproduction.
The output transformer of the amplifier should have impedance tapping of 4,8 & 16 ohms to
enable operation with loudspeakers of these standard impedances. For constant voltage
working, the transformer should be provided with 70 to 100 volts constant voltage tapings.