ULTRASONIC EXAMINATION REPORT

REPORT No & Rev no:


Date of GPTI-QICL-030 PAGE: 1 OF 1
Examination: 22.08.2023
Client: AIR PRODUCTS/NEOM / QICL Job No:- J932
Location: QICL,HAMRIYAH PHASE 2 Item Id: J932-12-2022
Project: NEOM HIDC Drawing No: - QICL-J932-11-12-DRG-GEN-01 REV-E
PM210014-QICL-9V3-00011 Rev. 04
Connecting cable type and length: LEMO TO MICRODOT Special attachment/ Equipment/Blocks: N/A
Examination Method and Technique : CONTACT METHOD AND PULSE Tag No:
ECHO
Calibration Block No: Thk: Reference Reflectors: BWE
CALIBRATION DATA
Reflector Beam Reflector
Probe Reflector No. % Echo Beam Path % Echo % Echo Beam Path
No Path No

Acceptance Criteria:
Damping / Reject Setting: OFF/ZERO

UT Procedure & Rev.:


PROBE TYPE TR/00 45 0 60 0 70 0
Flaw Detector: USM 35 X DAC
Make WK NA NA NA

Sr. No. 42685 NA NA NA Serial No: 17283

Crystal Size / Diameter Calibration Certification No: GPTI/UT/CAL -019/2022


mm 10Ø NA NA NA

Frequency MHz 5 MHZ NA NA NA Calibration Certificate Due Date : 30.07.2024

Base Metal Type & Thickness: CS,& 80mm


Primary Reference dB 1st BWE@80% of FSH NA NA NA
Weld Type / Configuration: DOUBLE V BUTT
Scanning Sensitivity dB +6 NA NA NA
Test Range (mm) 0-100 NA NA NA Couplant Brand Name & Type: POLYCELL
Surface Condition Scan Face : FROM OD SURFACE
/Preparation WELDED & SMOOTH
Access Limitations (if Any):
* UT (NORMAL BEAM ONLY) SCANNING WAS CARRIED OUT ON REMAINING WELD AFTER GOUGING ON LONG
SEAM WELD ID DLS-06 OF VESSEL J932 -12-22 FROM OD SIDE AT LOCATION 200 TO 450mm.

* NO RELEVANT FLAW INDICATION OBSERVED.

ACCEPT REJECT

TEST RESULT ✘

CLIENT REP. : AI / TPI. :


TECHNICIAN : SANDIP BHOWMICK
NAME : NAME ;
LEVEL : II
SIGNATURE : SIGNATURE :
SIGNATURE :

DATE : 22.08.2023 DATE : DATE :

Report Form no-GPI/NDT/UT/001, REV-4 (Rev-date : 26/07/2020)


Disclaimer : This report is a property of GPTI & valid only if signed and stamped by GPTI Technician. Under no Circumstances will GPTI accept any
liability for loss or damage; consequential or otherwise caused by use or misuse of the test results. The test report shall not be reproduced in full or in part for
any promotional or publicity purpose without the written consent from GPTI
Report Form no-GPI/NDT/UT/001, REV-4 (Rev-date : 26/07/2020)
Disclaimer : This report is a property of GPTI & valid only if signed and stamped by GPTI Technician. Under no Circumstances will GPTI accept any
liability for loss or damage; consequential or otherwise caused by use or misuse of the test results. The test report shall not be reproduced in full or in part for
any promotional or publicity purpose without the written consent from GPTI

You might also like