You are on page 1of 2

Form. No.

LAD-QHSE-08/FR-03
Fire Risk Assessment
REV/ISSUE 0/1
Children Museum
DATE 01-12-17

Fire Risk assessment – STO-3-LG-01 Store Date: 08-08-18


Ref - FRA-0

Introduction:

This Fire risk assessment report is subjected to ensure the fire and safety of stored Tissues in storage room
and to control the fire load and apply the appropriate controls and mitigation plans, this store is located in
LGF near public pathway to children’s museum through lower plaza and this room is protected by automatic
sprinkler system. The below pictures are hazards existing in the building and detail Fire risk assessments are
carried out to reduce the risk level and attached underneath of pictures.

1. Existing store room condition

Electrical light source Fire protection Tissues

2. Additional control measure recommended

Sprinkler arrangement Electrical light source

Page 1 of 2
Form. No. LAD-QHSE-08/FR-03
Fire Risk Assessment
REV/ISSUE 0/1
Children Museum
DATE 01-12-17

Fire Risk Assessment


Project Name Louvre Abu Dhabi FRA No. FLS-FRA-0 Implementation date 08/08/2018 Review Date
Description of activity/Task Fire Risk Assessment of store room
Equipment or tools used
Applicable Legal requirement UAE Life Safety Code

Routine/No routine Without Control Measures Existing Control Measures With Control Measures
Type of activity.

Risk Rating Risk Rating

Sr. Condition or Responsibility

Probability (P)

Probability (P)

Residual Risk
Hazards

Severity (S)

Severity (S)
Who / what Risk / (What do we do to prevent

Initial Risk
No Activity

Outcome

Outcome
Additional Control Measures

(S)x(P)

(S)x(P)
is at risk Consequences incidents and reduce the effect?)

1. 1.Routine PPM need to carryout


1.Visitors

Medium
Routine

Electrical 1.Fire Occurrences 1.FLS team daily inspection. 2.Fire retardant to be provided to
2.Staffs.

Low
1 sources(lights Fire Hazard. 2.fire propagation 4 3 12 2.Fire hose cabinet and fire cover the materials 1 3 3 1. MAB
3.Property
fire) extinguisher. 3.Stacking of materials to be
3.Fire detector available controlled

1.Fire hose reel Available within


Inappropriate 1.
Routine

1.Visitors 25mtr
Fire hazard, 1.Sprinkler location need to shift

HIgh
1. Delayed firefighting

Low
2 coverage of fire 2.Staffs. 4 4 16 2.Fire safety daily inspection 2 2 4 1. ASO/DSS
Fire load, 2.Fire propagation as required
protection 3.Property carryout

1. High source of
High ignition

Medium
Routine

1.Visitors ignition fuel 1.Fire compartmentation should 1.A fire curtain need to provide
Fire hazard,
HIgh
3 materials 2.Staffs. 2. Undefined Fire 4 4 16 be apply 3 2 6 2. MAB
Fire load, propagation
(Tissue) 3.Property 2.

Risk Assessment Committee

Fire Safety Team Leader Midhun

QHSE & FLS Manager Shehnas