1. Estimate the distance over which a load of 15,000 kW at 0.85 power
factor can be delivered by a 3-phase transmission line having conductors of steel-core aluminum each of resistance of 0.56 ohms per km. The pressure delivered at the receiving end is to be 132 kV and the loss in transmission is not to exceed 7.5%.
2. What load can be delivered by a 3-phase overhead line 5 km long with a
pressure drop of 10%. Given that the station voltage is 11 kV, resistance per km of each line 0.09 ohms, reactance per km 0.08 ohm and the power factor is 0.8 lagging.
3. A 50 kW at 11 kV are received from a 3-phase transmission line each wire
of which has a resistance of 1.2 ohms and reactance of 1 ohm. Calculate the supply pressure when the power factor of the load is a.unity b.0.5 leading
4. A 3-phase, 50-Hz transmission line 10 km long delivers 2,500 kVA at 10
kV. The p.f. of the load is 0.8 lagging. The resistance of each conductor is 0.3 ohms/km and the inductance is 1.82 mH/km. a.Find the voltage and p.f. at the sending b.The efficiency of transmission and c.The percent regulation of the line.
5. The input to an induction motor from a 13 kV, 60 Hz line is 1000 kVA, at
0.8 pf lagging. A capacitor is placed in parallel with the motor to improve the pf. Calculate the capacitance required raising the power factor to 0.9 leading.
6. A three-balanced load draws a line current of 80 A at 0.9 lagging power
factor. Solve the minimum size in kVAR of the capacitor bank needed to raise the power factor to 0.95 leading, if the line-to-line voltage is 13,200 volts.
7. Two Y-connected, induction motors are fed by a 4160 V, line to line, 3-
phase 60 Hz motor-control center 20 feet away. Motor 1 drives a 600-Hp compressor. The efficiency of this motor is 90% and its power factor is 0.5. Motor 2 indicates 1730 kW, 277 amperes. Determine the capacity in microfarads per phase of a wye-connected bank that is required to correct the power factor of the total load to 0.966 lagging.
8. A 2.3 kV three-phase system supplies a 120-kW, 0.6 pf lagging balanced
load. Determine the capacitance in each phase of a wye-connected capacitor bank to adjust the power to 0.9 lagging.
9. Three Y-connected, loads are fed by a 4160 V, line to line, 3-phase 60
Hz. Load 1 drives a 500-Hp compressor. The efficiency of this load is 90% and its power factor is 0.6 lagging. Load 2 has a rating of 1600 kW, and draws 250 amperes lagging. Load 3 draws a current of 150 A with a power factor of 0.8 leading. Determine the capacity in microfarads per phase of a wye-connected bank that is required to correct the power factor of the total load to 0.966 lagging.