Executive Summary Report

Site Sodamoda, Rajasthan 220 KV SS

Date 16.03.2020

Sr. No. M/c Detail Dir. No Particuler Cause Photos Remarks Order Details

TR LV OC getting trip in different fault Electromagnetic relays need to


1 Consider relay replacement.
value for individual phases. replace with numerical one.

1 TR 1

PRV & Other control cables wornout


2 Aging Need to attend fix before total damage.
bluntly on TR top.

1 HV 86 1 & 2 was faulty. Coil opened Replace with spare panel.

2 TR 2

2 HV to LV inter trip not happening. Not available in scheme. Need to assgin physically.

1.) OLTC PRV Control cable not


available in TR MK.
2.) Buchholz Alarm
3.) HV-LV WTI trip/ Alarm not
1 Many auxiliary protection not working. working Pls. attend fix ASAP
4.) Cooling fan not working.
Selector switches needs to
replace.

3 TR 3

Oil leakage from R phase Tandelta


2 Pls. attend fix ASAP
point.

Page 1 of 2
Executive Summary Report
Sr. No. M/c Detail Dir. No Particuler Cause Photos Remarks Order Details

Electromagnetic relays need to


1 EF only gets trip after 0.5 Amps. replace with numerical one. Consider relay replacement.

4 FDR 1

Electromagnetic relays need to Consider relay replacement. Replaced


2 OC Y & B Phase Faulty. replace with numerical one. with feeder 2 for instance.

R phase of breaker in close condition Breaker replacement alredy planned.


5 FDR 2 1
732 Kohm. Currently Charged through TBC.

Electromagnetic relays need to


6 FDR 3 1 EF Relay Tripping in DT only. replace with numerical one. Consider relay replacement.

Easily can be fixed by de-soldering same


Relay IED unit cannot reset nor HMI malfunctioned of down press
7 FDR 14 1 button.
accessible. button.
Protection function seems fine.

8 FDR 15 1 Abnormal CRM of isolator Isolator rod wornout bluntly. Need to replace.

B Phase Second core to earth IR - 58


9 Line 1 1 Kohms. Problem with JB to MK cable Need to replace.

Distance relay settings not accessible Only LMS X/R & 86 Trip verified. For
10 Line 2 1 from HMI & Not able to communicate
information. Report will be not provided.
with laptop by several tries.

+ve to Earth = o V
11 DC Leakage 1 Pls. attend fix ASAP.
-ve to Earth = 110 V

Note:- Pls. change all Electromagnetic relays with numerical one.

END