DESIGN COMPUTATION
Heating Load (Cool months)

Solution:
TRANSMISSION ABOVE GRADE
AREAS:

 WINDOWS
o Sliding Window (W1) = 4(1200mm)(1050mm) = 5040000mm2
o Bathroom Window (W2) = 2(300mm)(300mm) = 180000mm2
o Fixed Window (W3) = 1600mm(815mm+1400mm) = 3560000mm2
o Awning Window (W4) = 3(600mm)(1200mm) = 2160000mm2
 TOTAL = 10940000mm2 or 117.75718ft2
 DOORS
o Main Door (D1) = 900mm(2100mm) = 1890000mm2
o Back Door (D2) = 800mm(2100mm) = 1680000mm2
 TOTAL = 3570000mm2 or 38.42716ft2
 CEILING
o =(9500mm)(9000mm)-[(2700(825)+1300(2600)+1500(5650)]
 TOTAL = 71417500mm2 or 768.7316 ft2
 WALL (GROSS)
o 3000(9500+9000+4000+825+2700+1775+1300+3050+1500+3350)
 TOTAL = 111000000mm2 or 1194.7941ft2
 WALL (NET)
o GROSS AREA – TOTAL WINDOWS AREA – TOTAL DOORS AREA
o 1194.7941ft2 – 117.75718ft2 – 38.42716ft2
 TOTAL = 1038.61ft2
CENG329/ SECTION/ 2ND Semester SY2020-2021
ENGINEERING UTILITIES 2
Civil Engineering Department

R-VALUE:
WALL:
L 3.14961
R= = =1.574 hr · °F · ft2/Btu (CONCRETE FILLING)
thermal conductivity 2

R=¿0.94 hr · °F · ft2/Btu (CONCRETE BLOCK,150MM)

L 1
R= = ×2 =1 hr · °F · ft2/Btu (CONCRETE FINISH)
thermal conductivity 2
RTOTAL=1.574+0.94+1=3.514 hr · °F · ft2/Btu
FOR DOOR(HARD WOOD):
R=0.16 hr · °F · ft2/Btu
FOR WINDOW(GLASS):
R=0.96 hr · °F · ft2/Btu
FOR CIELING(SLAB):
R=0.32 hr · °F · ft2/Btu
U-FACTOR:
FOR WALL:
1 1
U= = = 0.28457 Btu/hr - ft2· °F
R T 3.514

FOR DOOR(WOOD):
1 1
U= = = 6.25 Btu/hr - ft2· °F
R T 0.16

FOR WINDOW(GLASS):
1 1
U= = = 1.041666667 Btu/hr - ft2· °F
R T 0.96
CENG329/ SECTION/ 2ND Semester SY2020-2021
ENGINEERING UTILITIES 2
Civil Engineering Department

FOR CEILING(SLAB):
1 1
U= = = 3.125 Btu/hr - ft2· °F
R T 0.32

CHANGE IN TEMPERATURE:
ΔT= 78.6℉-71.9℉=6.7℉
q=U×A×ΔT
qWALL= 0.28457(1054.14)(6.7) = 2009.843 Btu/hr
qDOOR= 6.25(38.42716)(6.7) = 1607.137 Btu/hr
qWINDOW= 1.041666667(117.75718)(6.7) = 821.850 Btu/hr
qCIELING= 3.125(768.7316)(6.7) = 16095.318Btu/hr
qT=qWALL+qDOOR+qWINDOW+qCIELING =20532.148Btu/hr
INFILTRATION:(q=AIRCHANGE×A×ΔT)
Volume = 768.7316ft2(9.842519685ft) = 7566.256 ft3
qINFIL=0.018(0.05)(7566.256)(6.7)=456.245Btu/hr
TOTAL HEATING LOAD = 20532.148Btu/hr + 456.245Btu/hr = 20992.392 Btu/hr