Length of Building = L = 90 m.
Breadth of Building = B = 98.4 m.
Height of Building = H = 70 m.
(For Low Damage) (Refer Table 5.B.3 for
2
Ductility = m = 1.5
Framed members)
Energy Absorption (2m-1) = 2.0
Factor (a)
Notes :
1 Using the maximum height of the Building.
2 Calculations as per ASCE Publication on "Design of Blast Resisant Buildigns in
Petrochemical Facilities".
Refer 3.5
page 3-9 Shock front Velocity= U = 345*(1+0.0083*Pso)0.5 = 364.5 m/s
Refer 3.6
page 3-9 Length of Pressure = Lw = U*td = 14.58 m
Wave
Refer 3.6
page 3-9 Peak dynamic Wind = qo = (0.0032*Pso2) = 0.627 kPa
Pressure
Reflected Overpressure
Clearing Distance
S = minimum of H or B/2 = 49.2 m
3.7, page
3.-14 Stagnation Pressure
Ps = Pso+Cd*qo = 14.63 kPa
Page 1 of 6
3.9, page
3.-15 Front Wall Impulse
Iw = 0.5*(Pr-Ps)*tc+0.5Ps*td = 0.588 kPa-sec
3.10, page
3.-15 Effective Duration
te = 2Iw/Pr = 0.040 sec
3.9,
page3-16 Equivalent Load Coeffiecient
Ce = = 1 Lw/L1 = 14.58
L1~ 1 m
3.11 page
3.-16 Equivalent Peak Pressure
Pa = Ce*Pso+Cd*qo = 13.7 kPa
Rise Time
tr = L1/U = 0.003 sec
3.11 page
3.-16 Average Pressure
Pa = Ce*Pso+Cd*qo = 1.8 kPa
Rise Time
tr = L/U = 0.247 sec
Roof Loading
3.9,
page3-16 Equivalent Load Coeffiecient
Ce = = 0.7 Lw/L1 = 2.43
L1~ 6 m
Page 2 of 6
3.11 page
3.-16 Equivalent Peak Pressure
Pa = Ce*Pso+Cd*qo = 9.5 kPa
Rise Time
tr = L1/U = 0.016 sec
Total to = tr+td = 0.056 sec
For Average Pressure
3.9,
page3-16 Equivalent Load Coeffiecient
Ce = = 0.15 Lw/L = 0.162
3.11 page
3.-16 Average Pressure
Pa = Ce*Pso+Cd*qo = 1.8 kPa
Rise Time
tr = L/U = 0.247 sec
3.9,
page3-16 Equivalent Load Coeffiecient
Ce = = 0.2 Lw/S = 0.296
3.11 page
3.-16 Equivalent Peak Pressure
Pa = Ce*Pso+Cd*qo = 2.5 kPa
Time of arrival
ta = L/U = 0.247 sec
Rise Time
tr = S/U = 0.135 sec
Page 3 of 6
Numerical co efficient based on Ct = 0.049 For all other buildings.
the Type of the Structure.
Dynamic Response
Equivalent Static =
Pressure
Page 4 of 6
= 0 milliseconds
Page 5 of 6
milliseconds
Page 6 of 6