Bucket Lifting Calculation (For Ties/Embedded & Water Storage 200 Ltr)

-Dimension 800 (B) x 800 (W) x 900 (H)

900 mm

800 mm
800 mm

Load Data

1. Selfweight (DL) 2. Live Load (LL)


Selfweight diassign sebagai beban sendiri struktur. Live load diassign sebagai beban merata -0.981 kN/m2.
Dead load diassign sebagai beban merata -1.5 kN/m2.

3. Live Load (LL) Cond. 1 4. Live Load (LL) Cond. 2


Live load Condition 1. Live load Condition 2.
Load Combination

1. Load Combination Type Serviceability

2. Load Combination Type Strength

Result Analysis

1. Result Analysis 2. Displacement Analysis

UC Maks. = 0.53 < 1.00…OK!! Defleksi Maks. = 0.903 mm < 2.67 mm…OK!!
Actual SWL for UC is 53 %
Luasan Alas = 0.8 x 0.8 = 0.64 m2
0.64 m2 x 2.481 Kn = 1.58 Ton
Summary
The structure is adequate to lifting material that not more than 1.58 Ton
Drum capacity is 200 ltr = 0.220 Ton < 1.580 Ton … OK