The distance between low water line in the receiver up to the highest point pumped 10 Meter
Total distance for lifting line from lowest level to pumped level + static head 69 Meter
Get required pump head = 1.20*(static head + static/10 + total pipe length *4/100)
= 1.2 X ( 10 + 10 / 10 + 4 / 100 X 69 ) =
= 16.6 Meter
Note
- when the receiving basin collects the discharge sanitary wastes it is called an Ejector Pump
- when the receiving basin collects storm water or other clear water it is called a Sump Pump
Getting receving basin depth = Distance between low & high level + invert level of entering pipe + suction level