Project Name BMC MAGNOLIA

Calculation Ejector Pump and Sump Pit. Date: 26/04/2023

Ejector Pumps will be designed according to fixture unit method

Type Of Flush Flush Valve


RMPM/FG OFFICES
The receiving basin will collect sanitary from

From Fixture Unit Load = 80 GPM

The distance between low water line in the receiver up to the highest point pumped 10 Meter
Total distance for lifting line from lowest level to pumped level + static head 69 Meter

Get required pump head = 1.20*(static head + static/10 + total pipe length *4/100)
= 1.2 X ( 10 + 10 / 10 + 4 / 100 X 69 ) =
= 16.6 Meter

Pump Flow 80 GPM


Pump Head 24 PSI
Pump HP 1.9 HP Duplex 1w+1sb

Note
- when the receiving basin collects the discharge sanitary wastes it is called an Ejector Pump
- when the receiving basin collects storm water or other clear water it is called a Sump Pump

Ejector Basin Sizing


Time Required to Empty the Sum pit 5 Minute
Minimum Capacity of Storage = Pump Capacity X Time Required to empty sum pit
= 80 X 5 = 400 Gallon
Assumed using of delux system the standard diameter of tank will be 4 ft or 1.20 m
Getting the depth of the basin = Storage Capacity / ( 0.7854 * D 2 * 7.5 )
= 400 / ( 0.7854 X 4^2 X 7.5 )
= 4.249 ft distance between high level & low level
= 1.2951 m
Adding :-
Invert level of the entering pipe = 0.9 meter ( )
Low level of water must be a minimium of 0.15 cm say = 0.3 meter

Getting receving basin depth = Distance between low & high level + invert level of entering pipe + suction level
= 1.2951 + 0.9 + 0.3 = 2.4951 meter

Getting Capacity of Storage = 400 Gallon


Getting Receving Basin Depth = = 2.5 Meter
Receving Basin Diameter = 1.2 Meter
Receiving Basin Area = 2.8 M2
Diameter of lifting pipe Assumed velocity 1 m/sec 80.154 110 mm