Professional Documents
Culture Documents
Revisions
Rev. No. Date Document Owner Alt SME SME
24 01/29/13 A.S. Beckett W.J. Frichtl W.J. Frichtl
23 07/09/12 A.S. Beckett W.J. Frichtl W.J. Frichtl
22 02/08/10 R. C. Annett W.J. Frichtl
21 01/09/08 R. C. Annett W.J. Frichtl
20 06/12/07 P.G. McDevitt W.J. Frichtl
19 02/20/07 P.G. McDevitt W.J. Frichtl
18 11/15/06 P.G. McDevitt W.J. Frichtl
17 09/05/06 P.G. McDevitt W.J. Frichtl
16 04/26/06 P.G. McDevitt W.J. Frichtl
15 01/23/06 P.G. McDevitt W.J. Frichtl
14 04/06/05 P.G. McDevitt W.J. Frichtl
13 10/27/04 P.G. McDevitt W.J. Frichtl
12 09/09/04 P.G. McDevitt W.J. Frichtl
11 06/25/03 P.G. McDevitt D.J. Knutson W.J. Frichtl
10 04/30/03 P.G. McDevitt D.J. Knutson W.J. Frichtl
9 10/16/02 P.G. McDevitt D.J. Knutson W.J. Frichtl
8 07/11/02 J. Roddick G.O. Dunham W.J. Frichtl
7 3/31/01 J. Roddick G.O. Dunham W.J. Frichtl
6 1/16/98 M.J. Scully W.J. Frichtl
5 Unknown M.J. Scully W.J. Frichtl
4 9/15/97 M.J. Scully W.J. Frichtl
3 10/04/95 W.J. Frichtl
2 5/24/95 W.J. Frichtl
1 9/20/94 W.J. Frichtl
Revision History
Master Specification E-400
Approved by: Harold Colgrove, Technical Standards Manager
Rev. No. Date Comments
• Full review
29 10/28/19
• Updated terms and requirements
Administrative Change
Rev. No. Date Comments
• Administrative Change: Updated SA-38 title references to reflect Ed. 7,
28 06/07/18
Rev. 0.
Approved by: David Heimke, Engineering Technical Standards Manager
Rev. No. Date Comments
• Complete revision of document and update to Electrical Standards. Added
27 05/24/17
Records Section. There are no change bars in this document.
• Updated Records Section.
• Updated References in document.
26 09/28/15
• Minor administrative change in Section 2.1.2, Bill of Material changed
statutes to state Statutes.
• The ownership statement on the title page of the document was replaced
with the Express Statement Marking, no.6 from AMS-006-01, Business or
Security Sensitive Information Procedure, Appendix B, “Express Language
Matrix.”
• Updated title of document to state from Specification E-400 to state Master
Specification E-400, Construction Specification – Electrical.
• Removed old Section 1.7.5, Design for Inertia Loading.
25 09/25/15 • Minor editorial to:
• Section 2.1,7, Modifications.
• Section 2.2.2, NRTL- updated verbiage in paragraph.
• Section 2.3.4, Safety Signs.
• Section 3.3.19, Electrical Heat Trace – removed EE-14, Electrical Heat Trace
Performance Report from document throughout as it was cancelled.
• Appendix A, Required Forms, removed EE-14 reference.
Approved by: Alan S. Beckett, Design Engineering Manager
24 01/29/13 Revised term DCR to read ICR.
• Updated the following Sections to clarify and improve document in response
to MAC Subtask 11424 and MAC Action 11780.
• Section 3.3.13, Terminations.
• Table 16. Single Pair no.16 with Gas Blocking Kits installed in the Type EYS
Seals Fill Table.
23 07/09/12
• Appendix K. Cable Block Kit Installation Terminal Boxes, Fittings or Seals.
• Figure 10. Installation Detail for Cable Block Kit.
• Table 17. List of Material.
• Table 18. Material Required for each Kit.
• Deleted Appendix O. U.S. Standards – Bolts.
Accountable Resources
Title Roles and Accountabilities
Lead technical resource assigned to the project; also known as the Project
Engineer or Assigned Engineer, provides the technical expertise to define
Alyeska Assigned Engineer
problems, needs, opportuntities, solutions, and produce technical
deliverables.
Assigns SME reviewers from pertinent engineering technical disciplines to
Alyeska Technical review design basis and approve the finished design basis documents. Also
Standards provides SME reviewers to provide in-progress and final reviews of detailed
design work.
Reviews design for adequacy, technical suitability, accuracy and
completeness. Also provides in-progress review and technical direction, as
Alyeska Electrical SME
well as final, review of design packages for adequacy, technical suitability,
accuracy and completeness.
Specifies when specification is used and has oversight of engineering design
Project Engineer
package.
Construction Lead Uses specification as construction standard
Construction Contractor Uses specification as construction standard
Responsiible Engineer Uses specification as design standard
Records
• All documents as stated in All records generated as a result of this document will be retained in
Appendix A. accordance with CW-200, Records Retention Schedule.
Contents
Revisions ii
Revision History ......................................................................................................................................................... iii
Accountable Resources .............................................................................................................................................. v
Records v
Contents vi
Tables viii
Figures viii
1.0 General .............................................................................................................................................1
1.1 Scope ...........................................................................................................................................................1
1.2 References ...................................................................................................................................................1
1.3 Definition of Terms .......................................................................................................................................1
1.4 Drawings ......................................................................................................................................................2
1.5 Alternate Design ...........................................................................................................................................2
1.6 Site Environmental Conditions .....................................................................................................................3
1.6.1 Arctic Duty .............................................................................................................................................3
1.7 Painting ........................................................................................................................................................3
1.8 Site Clean-Up ...............................................................................................................................................3
1.9 Delivery, Storage, and Handling ..................................................................................................................3
2.0 Equipment and Material ....................................................................................................................4
2.1 Equipment and Material Requirements ........................................................................................................4
2.1.1 Material Standards ................................................................................................................................4
2.1.2 Material Handling ..................................................................................................................................4
2.1.3 Inspect Material .....................................................................................................................................5
2.1.4 Corrosion Resistant ..............................................................................................................................5
2.1.5 Intrinsically Safe Equipment..................................................................................................................5
2.1.6 Temporary Storage ...............................................................................................................................5
2.2 Bulk Materials ...............................................................................................................................................5
2.3 Identification .................................................................................................................................................5
2.3.1 Nameplate Material and Lettering .........................................................................................................5
2.3.2 Equipment Nameplate Attachment .......................................................................................................6
2.3.3 Identification Nameplates......................................................................................................................6
2.3.4 Arc Flash Labels ...................................................................................................................................6
2.3.5 Equipment, Cable and Conductor Identification ...................................................................................6
2.3.6 Intrinsically Safe Equipment..................................................................................................................7
3.0 Construction Requirements ..............................................................................................................7
3.1 Temporary Construction (Alyeska)...............................................................................................................7
3.2 Execution......................................................................................................................................................8
3.2.1 Complete System ..................................................................................................................................8
3.2.2 Electrical Credentials ............................................................................................................................8
3.2.3 Workmanlike Manner ............................................................................................................................8
3.2.4 Area Classification ................................................................................................................................8
3.2.5 Tie-In .....................................................................................................................................................8
3.2.6 Demolition .............................................................................................................................................8
3.3 Performance Characteristics ........................................................................................................................9
3.3.1 Scope of Work ......................................................................................................................................9
3.3.2 Supports and Welding...........................................................................................................................9
3.3.3 Conduits ................................................................................................................................................9
Tables
Table 1. Conduit Body Fill – Class I, Division 1, Group D Area (Crouse –Hinds Type GUA Fittings) ................ 51
Table 2. Conduit Body Fill – Class I, Division 1, Group D Area .......................................................................... 51
Table 3. Conduit Body Fill – Class I, Division 2, Group D and Unclassified Area (Crouse–Hinds MARK 9
Fittings) .................................................................................................................................................. 52
Table 4. Conduit Body Fill – Class I, Division 2 or Unclassified Areas................................................................ 52
Table 5. Volume Required per Conductor in Each Conduit Body or Box [Table is identical to NEC Table 370-
16(b)] ..................................................................................................................................................... 52
Table 6. 25% Fill (Maximum Number of 600V Single Conductors with NEC Type XHHW Insulation) ............... 53
Table 7. 40% Fill (Maximum Number of 600V Single Conductors with NEC Type XHHW Insulation) ............... 54
Table 8. 600V Multi-Conductor Cable Type “EYS” Seal Fill Table ...................................................................... 55
Table 9. 600V Multi-Conductor Cable Type “EYS” Seal Fill Table ...................................................................... 56
Table 10. Dimensions and Percent Area of Conduit ............................................................................................. 57
Table 11. 300 Volt Instrument Multi-Pair/Triad Type “EYS” Seal Fill Table .......................................................... 58
Table 12. 300 Volt Instrument Multi-Pair/Triad Cable Type EYS” Seal Fill Table ................................................. 59
Table 13. Maximum Number of #20 AWG and/or #16 AWG Conductors Permitted in “EYS” Seals at 25% Area
Fill (Drain Wires Considered Same Size) .............................................................................................. 60
Table 14. 300V Instrument Single Pair Cable Type “EYS” Seal Fill Table ............................................................ 61
Table 15. 300V Instrument Single Pair Cable Type “EYS” Seal Fill Table ............................................................ 61
Table 16. Single Pair #16 or Triad #16 with Gas Blocking Kits Installed in the Type “EYS” Seals Fill Table ....... 62
Table 17. List of Material ....................................................................................................................................... 65
Table 18. Material Required for Each Kit ............................................................................................................... 65
Table 19. Temperature Correction Factors for Insulation Resistance to 15.6°C (60°F) ....................................... 68
Figures
Figure 1. Bonding of structural steel to station ground grid. ................................................................................. 27
Figure 2. Single Conductor ................................................................................................................................... 39
Figure 3. Three Conductor Cable ......................................................................................................................... 40
Figure 4. Minimum Conduit, Fitting, and Equipment Installation Clearances ....................................................... 44
Figure 5. Conduit Connection to Explosion Proof Enclosure – Preferred Method ............................................... 45
Figure 6. Conduit Connection to Explosion Proof Enclosure – Alternate Method ................................................ 46
Figure 7. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued) ............................. 47
Figure 8. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued) ............................. 48
Figure 9. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued) ............................. 48
Figure 10. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued) ............................. 49
Figure 11. Installation Detail for Cable Block Kit..................................................................................................... 64
Figure 12. Panel Grounding .................................................................................................................................... 66
Figure 13. Nameplates ............................................................................................................................................ 67
1.0 General
1.1 Scope
This specification covers installation of electrical equipment in facilities operated by Alyeska Pipeline
Service Company (Alyeska) and is intended to apply to new electrical installations, alterations to existing
facilities and modules fabricated offsite.
In general, the work shall consist of, but not be limited to, installation of conduit; cable tray and other
raceway systems; wire, cable, and equipment for power and lighting; motor controls; process controls and
instrumentation; alarms; fire and gas detection, alarms, and protection; communications;
telecommunication; uninterruptible power supply systems; grounding; heat tracing; distributed controls and
emergency shutdown systems; power generation, distribution and transmission systems; and other
electrical systems, including inspection, testing and commissioning of the completed systems.
Any conflict between this specification and specific modification drawings shall be brought to the Alyeska
Project Technical Lead Engineer or the Electrical SME for resolution. In general, however, the more
stringent requirement shall govern technically. It shall be the Contractor's responsibility to identify any
conflicting requirements prior to award of the Contract.
The Contractor shall furnish all labor, small tools, installation equipment, rigging, consumable items,
temporary supplies and facilities, supervision, transportation, material receiving and storage, insurance and
every item of expense necessary to complete the electrical installation described herein.
All work, when finished, shall be in a complete operable and undamaged state at the time of acceptance
by the Owner.
No revisions and/or addendums shall be made to this specification without the review and approval of the
SME of this specification or their approved designee.
All interpretations of this specification shall be addressed by the SME of this specification or their approved
designee.
1.2 References
The codes, standards and specification listed in Appendix B, “Reference Publications,” shall be considered
as part of this specification.
The references in Appendix B are a listing of references used in this specification. Comply with the current
or specified editions of these references as noted in the text.
Vendor A firm or individual who enters into an agreement to supply material, equipment or
services or both for the Owner of the project. The Vendor can also be a manufacturer.
Manufacturer A firm that enters into an agreement with a Vendor or Purchaser to design, fabricate,
construct and test the material and equipment, and also provide the services, if
requested, for the Owner of the project.
1.4 Drawings
1. The drawings shall be accurately followed. Should there be any discrepancy between the drawings and
actual installed items, the discrepancy shall be documented and the Owner notified immediately. The
Owner may require submission of a design change request or a similar document to correct the
discrepancy.
2. Unless otherwise noted on the drawings, conduit routings and equipment locations are approximate.
Determine actual routing in the field.
3. Upon completion of work, a set of up to date "As-Built" drawings shall be furnished to the Owner. All
authorized changes, additions, and deletions which took place during the construction period shall be
clearly indicated on this set of drawings. This set of "As-Built" drawings shall be given to the Owner for
approval upon completion of the electrical work prior to project commissioning and closeout. "As-Built"
drawings shall be as per the Owner's procedure which identifies drawings to be "As-Built". See
Appendix D, “Preparation of As-Built Drawings,” for the preparation and criteria for "As-Built" drawings.
4. Drawings and supplemental data shall be maintained in a clean and orderly file for ready reference. All
field initiated sketches, notes, and similar data shall be sufficiently clear as to permit photo reproduction
when required.
5. Construction shall develop detailed design sketches incorporating conduits from various systems in
accordance with the requirements of this specification and referenced documents. The additional work
required to install required supports, fittings, pull boxes, field bends, does not constitute extra work.
6. Locations of process equipment and instruments, shown on equipment on electrical drawings are
approximate only. For actual location, refer to respective equipment drawing.
7. Drawings do not show all fittings and pull points required. Construction shall add fittings as required to
meet Code and conductor pulling requirements.
8. Alyeska standard installation details for commonly used equipment shall be used where possible.
1.7 Painting
Construction shall do all touch-up painting required on electrical equipment on painted and galvanized
surfaces which have been damaged through cutting, grinding, welding, or other means to expose bare
steel. The preferred touch-up paint shall be corrosion-resistant formulation colored ANSI-61 light gray
unless otherwise directed by the Owner. All other paint shall be furnished by the Contractor and shall be in
accordance with the Owner's specification. The floor areas under equipment shall be primed or painted to
match existing surface prior to equipment installation. Recoat damaged and uncoated areas of hot-dip
galvanized steel with an approved cold galvanizing compound such as Devoe Catha-coat 304V, Carboline
Carbozinc 11HS in accordance with ASTM A780 and APSC Master Specification B-400.
2.3 Identification
Each operating device, control station, lighting panel, terminal box, relay box, control panel, electrical
instrument and other electrical equipment shall be identified by means of a nameplate with inscription as
shown on the contract documents or drawings or as approved by the Owner. The Contractor shall furnish
and install engraved nameplates for all these electrical devices.
embossed characters, in two rows where required. Conduit labels shall be attached with appropriately
sized stainless steel cable ties, Panduit MLT No. S-CP or approved equal. Where cables enter panels
or boxes, T&B, Tyco/Raychem, Brady or Owner-approved equal cable markers shall be used.
5. Each motor starter, terminal box (for instrumentation, power, lighting, control, etc.), control station,
distribution panel and transformer shall have a nametag of the type shown in Appendix M,
“Nameplates.”
6. Conduits that penetrate the module floor through the module soffit shall be tagged directly above the
module floor and just below the soffit.
7. Conduits that penetrate the control room firewalls shall be tagged on both sides of the firewall.
7. To prevent corrosion from condensation or water infiltration when stored outdoors, internal equipment
space heaters and motor block or winding heaters provided by the Manufacturer or the project shall be
provided with temporary power until equipment and or modules are installed and permanently heated.
3.2 Execution
3.2.1 Complete System
The scope of work to be performed by the Construction Contractor consists of but not limited to the following
furnishing all necessary labor, supervision, equipment, small tools, consumables, material, test instruments,
services, supplies, and necessary incidentals to construct, install and test the complete electrical system,
unless otherwise specified by written agreement or contract. This shall be done in accordance with this
Specification and to the extent indicated on the drawings.
3.2.5 Tie-In
Electrical connections and tie-ins to existing operating facilities will be thoroughly reviewed with and
approved by the Owner. Coordinate with Operations any electrical connections and tie-ins to existing
operating facilities.
3.2.6 Demolition
When existing equipment (to include wire, cable, or conduit) is determined to be of no further use as the
result of a modification, the project or work order is responsible for removing it unless agreed upon
otherwise and specifically noted in the design as described in E-500, Design Criteria - Electrical.
Wiring and cables abandoned in place shall be tagged at its termination and junction points as “Abandoned
in Place” or removed from all accessible areas and insulated from contact with other live electrical wiring
and devices. Equipment abandoned in place, including switchboards, panelboards, disconnect switches
and the like shall be permanently labeled as “Abandoned in Place/Deenergized.” Cabinets, boxes, conduit
and fittings to be abandoned in place shall have all unused openings capped, plugged or covered in
compliance with NEC 110.12(A).
3.3.3 Conduits
The conduit system provides mechanical protection for cables, and a fault current return path in the case
of metallic conduit.
Conduit systems shall be installed in a manner that allows cables to be installed without exceeding rated
cable pull tension and sidewall pressure limits.
The installation shall minimize the total number of bend-degrees between pull points and to make any
bends as shallow as possible. In no case shall there be more than the equivalent of three 90° bends
between pull-points.
Conduit systems shall use junction boxes, pull boxes, and condulets where necessary to facilitate easy
installation of cables.
Horizantal conduit support spacing shall not exceed 10 feet. Conduit shall be securely supported within 3-
feet of any termination.
Vertical cable supports shall be used in long vertical runs of conduit. Vertical cable support spacing shall
be in accordance with NEC 300.19.
Pull boxes shall be sized to ensure the cable bend radius limits are not exceeded.
Conduit fill shall be in accordance with the NEC Chapter 9 conduit tables.
Conduits containing three single-conductor power cables shall be sized to avoid critical jamming ratio
diameters. Cable jamming can occur when three equal size single-conductor power cables are pulled into
the same conduit or duct and the sum of their individual diameters (d) equals the inner diameter (D) of the
conduit/duct. If the jam ratio is greater than 2.8, increase the conduit size.
Metallic conduit shall be electrically continuous.
Construction shall install all conduits, including fittings, unions, couplings, drains, plugs, reducers, seals,
bushings, expansion joints, outlets, junction and terminal boxes and other associated items, to the extent
indicated on the drawings for a complete system.
7. All conduit threads shall be full and continuous. The length of field cut threads on each size conduit
shall not be less than the length of factory made threads on the same size conduit and shall be in
accordance with UL Standard 6. Conduit and fittings shall be made up wrench tight with a minimum
engagement of five threads. The use of running threads shall not be permitted. Excessive thread
showing on made-up conduit is not acceptable. All conduit shall be threaded using a NPT Standard
Conduit cutting die that provides ¾-inch taper per foot.
8. Field bends in ¾-inch and 1-inch conduit or tubing may be made with a hand conduit bending tool.
Bends in larger size conduits shall be made with a bending machine. Minimum radius of conduit bends
shall be in accordance with the NEC Table 2, Chapter 9. All conduits, after bending, shall be true round
with full inside area for entire length of the bend. Conduits routed on common supports shall be installed
with concentric bends. Minimum radius of conduit bends shall be in accordance with the NEC Table
344.24.
9. Conduit shall be installed parallel with or at right angles to walls, floors, columns, and beams. When
conduit enters or leaves a main conduit run it shall change elevation so as not to block installation of
future conduits.
10. Conduit, fittings, cables, and equipment shall be installed to provide adequate clearances as follows
and as shown in Appendix F, “Minimum Conduit, Fitting & Equipment Installation Clearances.”
a. Operating Areas:
Vertical Head Room Clearance = 7' 0" minimum(7' 6" preferred minimum).
b. Operating Passages:
Horizontal Clearance = 2' 6" minimum
c. Truck Access Areas:
Vertical Clearance = 14' -0" minimum
d. Maintenance Roadways:
Vertical Clearance = 18' 0" minimum
e. Stairs, Stair Ladders and Ramps: See Appendix F.
f. Conduit shall not be installed at platform levels in such a manner that may cause a false or insecure
step.
11. Conduit crossing non-insulated hot pipes shall have minimum clearance of 6 inches. Those running
parallel to non-insulated hot pipes shall have a minimum clearance of 12 inches. Conduit crossing or
running parallel to insulated hot pipes shall clear insulation by a minimum distance of 3 inches. High
reflective and/or insulating thermal barriers must be installed between the conduit and hot surface if
these minimum distances cannot be maintained. Hot pipes are defined as those having a temperature
of 160°F or above.
12. Conduits shall be routed for maximum practical accessibility of junction and pull boxes.
13. The positive and negative polarity conductors connecting the station batteries to the DC power
distribution equipment shall be run in separate conduits.
14. Conduit systems shall accomodate crossing vibration joints and expansion joints. Consideration shall
be given to raceway seismic shake space design provisions where applicable.
15. Conduit shall be installed to minimize collection of trapped condensation. Whenever possible, conduit
shall enter boxes, equipment etc., from the side or bottom. Raceways and enclosures installed outdoors
or in wet locations shall be arranged to drain and shall be approved for use in outdoor locations. Drains
shall be installed at the bottom of conduit boxes when shown on the project drawings. All drains shall
be thoroughly cleaned to ensure proper operation (Reference NEC 225.22).
16. Conduit shall be supported at maximum intervals of 10 feet, unless otherwise noted on the drawings.
Additional support shall be provided at bends, fittings, and fixtures as required to make the conduit
system rigid and free from vibration. Raceways and cable shall not be used to support other raceway
or cable unless specifically authorized. Similarly, conduit shall not be supported from hangers attached
to process and utility piping, except as specifically shown on the drawings and approved by Owner in
writing.
17. All straight conduit runs of 150 feet or longer (either indoor or outdoor, Class I, Division 2 or unclassified)
shall be provided with an approved type of conduit expansion joint with one unit required for every 150
feet, starting 100 feet from each terminal box or pull box. Bonding jumpers shall be installed around all
expansion joints unless the expansion joint is listed as an effective ground current return path.
18. Install grounding hubs at all rigid conduits entering NEMA 1, 3, 4, and 12 enclosures.
19. The installation of liquid-tight flexible metal conduit shall be in accordance with NEC Article 350. Special
care shall be taken to assure that the radius of flexible conduit bends is not less than Manufacturer's
recommended bending radius.
20. Explosion proof flexible conduit couplings shall be NRTL listed per UL 886 as suitable for Class I,
Division 1 Classified Areas. The vendor shall identify the minimum bending radius of each Explosion
proof Flexible Conduit Coupling.
21. Standard conduit clamps and multiple conduit hangers are acceptable supports. One-hole malleable
iron clamps or "C" strut channel and pipe straps with a vibration cushion shall be used to support
conduits installed on pipeways or structures subject to vibration or movement.
22. Conduit pull fittings shall not be located in inaccessible places where difficulty would be experienced in
wire pulling.
23. All conduit runs shall be snaked and swabbed with a mandrel to clean and remove all foreign material
and moisture before installing the wire or cable.
24. Explosion proof conduit fittings shall have threaded covers.
25. Wires and cables in vertical raceways shall be supported as required in Article 300.19 of the NEC.
26. Spare conduits over 10 feet long shall have a 200 pound test polyethylene pull line installed for future
use. These conduits shall be capped weather tight at both ends. Attach a durable tag at each end of
the conduit that identifies it as a spare to be re-used. Identification shall be by means of embossed
stainless steel tag provided with integral means of attachment or else attached by stainless steel wire
or ties. The label shall include the word SPARE, description of the physical location of the other end,
the use for which it is intended (e.g. Comm., Instr., Pwr., etc.) and the project or work order number
under which the work took place.
7. Install conduit seals on stub-ups in classified areas in accordance with the NEC, Article 501.15.
8. Underground conduit and wired utilities are to be reflected on L21 survey drawings.
manufacturer for the duration specified. The assigned Alyeska engineering technical lead shall specify
the Electrical Inspection requirements during sealing installation.
7. Sealing compound and fiber that is used shall be per manufacturer’s instructions and shall be approved
for use with the seal fitting. Only one brand sealing compound shall be used to prevent the possibility
of improper mixing of different brands of sealing compound. Appleton, Crouse-Hinds, and O-Z/Gedney
sealing fittings have all been listed by UL as approved for use with Crouse-Hinds Chico sealing
compound. Where Vendors or others have provided a different brand of sealing fittings from those
provided by the field construction, the Owner's electrical representative shall determine the approved
brand of sealing compound to use.
8. Completed and approved seals shall be identified by painting the seal plug or cover red. A cable tie
shall be installed around the seal fitting at the time the seal is poured to indicate that the seal does not
contain asbestos material. This requirement applies only to conduit seals that have been poured with
the standard grout-like material. The cable tie should be black heavy-duty, T&B p/n TY-528MX or equal.
9. Seals installed as environmental barriers in unclassified areas shall be filled with Chico, Kwiko A,
Duxseal, or other approved equivalent sealing compound. Do not use substances that can damage
insulation or harden and cannot be removed. Note that environmental barriers need not use explosion-
proof seal fittings.
10. Where explosion-proof seals are used at conduit entrances to enclosures, install a union between the
seal and the enclosure. (The seal must still be within 18 inches of the enclosure.)
11. Explosion proof seals shall be installed on conduits that stub up in classified areas.
12. Conduits that stub up in equipment that do not require explosion proof seals shall be sealed with an
approved sealing compound.
Bonding jumpers, #1/0 AWG, or larger, finely stranded, copper shall be installed on the outer surface
of each side of the trays at every expansion joint and at all adjustable connectors to ensure ground
continuity. Bonding jumpers shall be rated to withstand the short circuit current in excess of the short-
circuit current rating of the cable tray. Bonding jumpers shall be flexible to allow expansion and
contraction with temperature. Bonding jumpers shall be tinned to minimize or prevent possible corrosion
with aluminum cable trays. NO-OX-ID, Penetrox or other Owner approved conductive lubricant
compatible with the materials shall be used at all bonding jumper connection points.
5. All horizontal cable trays shall be supported at an intervals in accordance with the installation
instructions provided by the manufacturer. Sliding type supports shall be located within 2 feet of each
side of expansion connector fittings.
6. Cantilever cable tray supports shall be installed on one side of the cable tray only to facilitate installing
cables in the trays.
7. Cable tray structural supports shall comply with S-502, Design Criteria - Structural.
8. Conduit shall not be placed inside of any cable tray. An individual conduit may be supported on the
underside or side of a cable tray, when approved by the Owner. Verify the structural and seismic
support loading with Engineering prior to supporting any conduit with a cable tray or from cable tray
structural support elements.
9. The voltage level such as 5 kV power or 480V power, or function such as control or instrument must
be identified on the cable tray by 1 inch high black letters on adhesive vinyl nameplate or stenciled on
the opposite ends of each tray section (or at least every 20 feet, whichever is less).
10. Particular attention shall be given to the inside of the cable tray to ensure there are no sharp edges,
burrs, or projections that can damage the cable insulation.
11. All bolted connections shall be made with corrosion-resistant hardware. Round head carriage bolts only
shall be used for cable tray assembly. Installation of nuts, square head, hexagonal head or other
fasteners with exposed edges is not allowed. Hardware made of plastic material is not acceptable.
12. All cable tray hold down clips shall be the expansion type, unless noted otherwise on the drawings.
13. The cable tray system shall be mechanically complete, cleaned and free of debris prior to the installation
of any cable. The Electrical Inspector shall inspect the completed cable tray system and complete the
IRCL-ELEC-12, Electrical Inspection – Cable Tray Installation prior to routing any cables.
14. When dropping out of tray into conduit, environmentally seal the end of the conduit using Duxseal,
Chico sealant, or other appropriate method.
15. A bonding jumper or fitting shall be installed between tray and conduit where cable transitions from tray
to conduit.
16. Although not a requirement, installers are encouraged to use NEMA VE 2, “Cable Tray Installation
Guidelines,” or the Eaton B-Line “Cable Tray Manual.”
17. Cable trays shall not pass through fire-rated barriers. Penetrations in fire-rated walls, floors and ceilings
shall be sealed with a listed fire stop material in accordance with manufacturer’s instructions. Roxtec
modular fire stop assemblies are preferred.
10. Cables installed in cable tray shall be in one continuous run and NRTL listed for tray use and certified
by the Manufacturer for arctic environment. Cables installed in cable tray shall be laid neatly and
segregated according to type or class. Bunching, crossovers, or sharp bending of cables is not
acceptable.
11. Wire and cable shall not be bent to radius smaller than that specified by the Manufacturer or allowed
by NEC, whichever is greater. Correct size pull box or larger conduit, whether or not shown on the
drawings, shall be used to meet the required bending radius.
12. Wire and cable shall be continuous from terminal strip to terminal strip where possible. However, where
splices are necessary and are shown on the drawings, they shall be made only in approved fittings or
junction boxes of adequate size per NEC and shall be subject to written approval by the Owner. Wire
splices shall be made only at terminals. The use of wire nuts, crimp connectors, butt splices, or quick
disconnects are acceptable only in approved junction or terminal boxes shown on facility design
drawings.
13. When Construction is directed in writing by the Alyeska Project Technical Lead or the Electrical SME
to splice wire, compression type connectors shall be used. For all low voltage circuits the following butt
splice shall be used. T&B Sta-Kon, with nylon insulation for #10 AWG and smaller, Burndy YS for #8
AWG and larger. Only appropriate compression tools made by the same Manufacturer as the splice
shall be used unless another brand of ratcheting compression tool is specifically approved for use with
T & B or Burndy compression splices. For medium voltage circuits, splices and taps shall be made in
accordance with the Manufacturer's instructions, using the best craft practices. These connections shall
be mechanically and electrically equivalent to the original characteristics of the wire and cable. All low
voltage spliced wires shall maintain color-codes and shall have wire tags.
14. Scotch 3M #23 EPR rubber electrical tape or equal approved by the Alyeska Electrical SME shall be
used to insulate all joints made on conductors with thermoplastic insulation. Dual-wall (adhesive lined)
non-vinyl heat shrink tubing such as 3M EPS-300 shall be used as an outer insulation layer for all butt-
splice joints.
15. Pulling lubricants shall be used when pulling wire or cable in conduit. Lubricants shall be NRTL listed
and suitable for arctic environments and for the type of wire or cable insulation involved. Soap suds,
soap flakes, oil, or grease shall not be used.
16. Nylon or polyethylene rope shall be used for pulling wire or cable. Bare steel or other non-insulated
metal fish tape is not acceptable.
17. Wire or cable shall be pulled into conduit terminating in switchgear, motor control centers, or similar
equipment, only after such equipment has been completely installed and permanently mounted in place
and conduits secured to enclosure.
18. Cables and wires including spares shall be tagged at both ends and also in pull boxes with tag numbers
shown on drawings and/or conduit and cable schedules.
19. Use Raychem Corporation, Thermofit Marking System (TMS), ShrinkMark, Panduit, or an owner
approved equal for identifying cables and conductors. Use white markers with black permanent
characters printed a minimum of 3/32-inch high. The wire markers must provide a snug fit over the
wires.
20. An equipment grounding conductor shall be run in the same raceway with each power, receptacle, and
lighting circuit.
21. The minimum voltage rating of the splices and terminations shall be at least equal to the cable insulation
voltage rating, unless otherwise specified.
22. Medium voltage power cable shall not be spliced unless approved by in writing by Alyeska Electrical
Engineering SME. Termination shall be in accordance with the cable manufacturer's recommendations.
Stress cones (Raychem Corporation or equal approved by the Owner) shall be installed on all shielded
power cables. Shields shall be grounded at each splice or termination.
23. In all cable handling, pulling and during splicing and terminating work, the cable or individual conductors
shall not be bent to a radius smaller than that permitted by the NEC. NOTE: The minimum bending
radius must be increased to 150 percent (of normally allowed minimum) if cable is bent under pulling
tension. If a cable section is bent too sharply, it shall be cut off and discarded.
24. Direct burial cables shall be placed at a minimum depth of 24 inches unless otherwise specified on the
drawings, and placed on top of a layer of sand 6 inches thick. Cover with a layer of sand 6 inches deep
as measured from the top of the largest cable. Install detectable flagging tape at least 12 inches above
the cable as a warning that electrical cable is buried there. Sand should be 3/8” minus. Conduit and
cables shall not be routed directly on the ground.
3.3.13 Terminations
As each of the wiring systems has been completely installed, the electrician shall make final terminations
at both ends of the run. After completing power wiring termination connectors, each circuit shall be tested
for continuity and compared with wiring diagrams and cable schedules. Electrical tests shall be performed
as described in Section 3.5 of this specification and shall be validated as acceptable before final termination.
1. Splices in cables and wiring other than lighting and receptacle circuits are permitted only when
approved by the Alyeska Electrical SME. Make splices only in junction or outlet boxes or in fittings and
raceways approved for this purpose.
2. Route wire and cables in neat and workmanlike manner. Cut field wiring to final lengths as shown on
the wiring diagram after routing through panel has been determined.
3. Wire and cable shall be neatly dressed at the terminal blocks. Wire tag numbers shall be visible.
4. Wire nuts can be used on lighting and receptacle circuits and at other devices or equipment designed
by manufacturer to use wire nuts, unless specified otherwise (see item 12 below).
5. All wire terminations for stranded wires #10 AWG and smaller shall be compression type, single bolt
lug, tinned copper only, T&B Sta-Kon, with nylon insulation. All wire termination for stranded wires #8
AWG and larger shall be Burndy Type YA or approved equal, two-hole tinned copper compression type
lugs only. Setscrew compression lugs furnished with equipment shall be replaced with YA-type
connectors where practical. The lugs shall be for the proper wire size. The correct size silicon-bronze
or stainless steel type bolts and nuts shall be used for all connections; Durabolt or equal approved by
Owner is acceptable. Stainless steel hardware shall be used to connect dissimilar metals and for
aluminum-aluminum connections. Galvanized steel hardware is not acceptable for this application.
Regardless of the types of materials to be joined, the contact area should first be thoroughly cleaned
and a suitable oxide inhibiding compound applied prior to making the connection.
6. All bolted connections shall be tightened in accordance with manufacturer’s specifications or Torque
Table 1 in E-402, Electrical Inspection and Testing. Note: silicon-bronze bolts are one-time-use and
cannot be determinated and reused once they have been torqued down. New unused bolts and nuts
must be installed should determination be necessary.
7. Compression tools made by the same Manufacturer as the lug shall be used to attach the lugs to the
stranded wire, unless another brand of ratcheting compression tool is specifically approved for use with
T & B, ILSCO or Burndy lugs. The Burndy Hylug® compression lugs and tools are preferred for #8 AWG
and larger wire sizes.Terminal blocks shall be of the screw clamp type with enclosed, finger-safe (IP-
20) design, rated 75°C or higher, and rated for the available short circuit current (SCCR) of the panel
or enclosure. Minimum voltage rating for 120V control wiring, shall be 300 VAC,and for 480V power,
shall be 600 VAC. If power and control wire terminations are grouped together, the minimum voltage
rating of the terminal shall be 600 VAC. The minimum current rating for power and control wiring shall
be 15 amps. All protective relaying, current and potential transformer terminations shall be terminated
in accordance with manufacturer’s recommendations. Install shielded pair and triad instrumentation
cables to maintain continuity and isolation of the shield (isolated from other shields and building
ground). When necessary, use thin wall shrink tube to ensure isolation of drain wires. Insulate shields
and drain wires with heat shrinkable tubing to ensure they are not inadvertently grounded in junction
boxes.
8. All equipment that is furnished with set screw type lugs for external wiring shall be replaced with crimp
type lugs, except for equipment that is designed to accept set screw type lugs only, such as circuit
breakers and motor circuit protector units.
9. Connections to low voltage motors and other removable devices shall be made with T&B motor lead
connectors or other approved compression-type connector. For 480V or higher voltage services, the
connections shall be insulated using 3M or Raychem heat shrink insulation kits, rated for the service or
equal approved by the Owner in writing. Long barrel compression lugs shall be used on all 480 V
andMedium Voltage 480V power circuits using #2/0 AWG and larger size conductors.
10. All Medium Voltage circuits shall be terminated with double or four-hole bolt lugs.
11. When different metals are bolted together for current carrying connections, stainless steel hardware
and compression type washers (Belleville or equal approved by the Owner) shall be used.
12. All terminations shall be made in accordance with the cable and terminator manufacturer's
recommendations with particular attention given to the make-up dimensions.
13. Crimp type lugs shall be installed with crimping tool specified by lug manufacturer.
2. All 120/208 VAC lighting and power circuit wiring shall be identified as follows:
Phase Color Marking
A Black Circuit number (for paralleled feeds only)
B Red Circuit number (for paralleled feeds only)
C Blue Circuit number (for paralleled feeds only)
Neutral White Circuit number (for paralleled feeds only)
Ground wire Green
UPS Note: Isolated ground (IG) receptacles also require orange
Orange
Receptacles triangle mark
3. All 277/480 VAC lighting and power circuit wiring shall be identified as follows:
Phase Color Marking
A Brown Circuit number (for paralleled feeds only)
B Orange Circuit number (for paralleled feeds only)
C Yellow Circuit number (for paralleled feeds only)
Neutral White or Gray
Ground wire Green
Phase Terminals
A T1
B T2
C T3
Ground Green
b. For Two Speed, Two Windings Motors:
Phase Terminals
A T1 and T11
B T2 and T12
C T3 and T13
6. Direct Current power distribution, DC Power Supplies, battery banks, battery chargers:
7. Control circuit voltages shall be 24 VDC standard; 120 VAC, and 125 VDC controls are permissible for
existing installations when required for system compatibility. The conductors shall be color-coded with
pigmented insulation or at each termination with low temperature 3M Scotch No. 35 PVC tape as
follows:
NOTE
With the approval of the responsible design engineer, other control wire colors (except white or green)
and other instrumentation wire colors (except green) may be used.
14. Ground wires and bonding jumpers must have green insulation when installed in conduit.
15. Do not use exothermic welding on any pipe, pipeline, pressure vessel, or pressure point without an
approved Standard Welding Application Schedule (SWAS).
16. Insulate the isolated instrument reference ground bus bar provided in each input/output (I/O) cabinet,
local panel, vendor-furnished packaged instrument equipment, and programmable logic controller
(PLC) cabinet from any local ground point. Tie it back to one point on the plant main ground bus by
insulated single-path conductors. Install the main ground bus in the switchgear room of the plant. Daisy-
chaining will be permitted only within a motor control center or in other areas where instrument systems
are in close physical proximity.
17. The electrical continuity of metal raceway and enclosures for wire and cable must be assured between
terminations. Do not use nonmetallic conduit sections or fittings in metal conduit systems unless
conduits are bonded around the nonmetallic conduit or fittings.
18. Ground all 480 V and above power circuit conduits at MCCs and switchgear to the ground bus at the
motor control center or power source. Use a soft drawn copper ground wire that is either bare or with
green insulation. Connect the ground to the conduits via an approved grounding-type bushing. Multiple
conduit penetration may have a common bonding jumper that connects several conduits to a ground
bus providing the bonding jumper is sized for the largest phase conductor in the group of conduits per
the NEC, Table 250.122.
19. Where a high resistance grounding (HRG) system is available, ground power transformer neutrals to
the HRG bus.
20. Ground the neutral of lighting and power distribution transformers within the transformer. The neutral
and ground conductors will be carried throughout all panels.
21. Construction shall complete the grounding systems as specified, and as required. The grounding and
bonding system shall conform to the requirements of Article 250 in the NEC.
a. Ground conductor sizes and types: grounding and bonding conductors shall be soft drawn bare
copper (SDBC) Class B stranded copper, sized as shown on the drawings except where otherwise
noted. To prevent galvanic reaction, ground wires and bonding jumpers shall have green color
insulation when installed in conduit or cable tray. Green insulated conductor shall not be used for
any other purpose, except for grounding.
b. Exothermic welding connections shall be used for all below grade connections and for attachments
to structural steel, stairs, platforms, ladders, structural and equipment modules, pigtails, concrete
encased rebar, and other exterior grounding connections.
c. Burndy Hy-Ground YGA-type 2-hole compression connectors installed with the appropriate
approved tool shall be used for indoor ground connections. The Electrical Inspector shall inspect
and approve the compression connections used for grounding. Install 2-hole YGA compression
lugs for connections to ground buses, motor bases, battery racks and other equipment, as
applicable.
d. Bolts may be stud-welded to steel for ground connections. Copper-plated steel or stainless steel
with stainless nuts and washers are permitted. Zinc galvanized hardware shall not be used with
copper. NRTL Listed grounding clamps shall be provided for connections to cable trays, fencelines,
pipes, etc. Steel structures, including those on modules, shall be connected to the system ground
as shown on design documents. At grade level, connect every other steel column directly to the
station ground grid using #4/0 AWG conductors. Provide #4/0 bonding jumpers where required to
ensure continuity of the entire building structure. Rebar embedded in concrete building foundations
shall be bonded into the station ground grid. Building column anchor bolts may serve as bonding
means provided they are tied or welded to the foundation rebar as shown in Figure 1 below.
Figure 1. Bonding of structural steel to station ground grid.
#4/0
e. Grounding conductor pigtails and stub-ups from concrete pads or slabs installed entirely exposed
on the surface of the concrete. Stub-ups shall be planned so they do not leave the concrete at
location where they may be exposed to damage, cause a tripping hazard, etc.
f. Ground rods shall be 3/4” diameter copper clad steel and 10 feet in length. Ground rods shall be
driven to a depth of at least 1-foot below finished grade and exothermically welded to the grounding
electrode conductor.
g. Metal tanks shall be provided with at least two #2/0 copper grounding electrode connections spaced
100 feet apart or less and located on diametrically opposite sides of the tank. Where the tank is
over 200 feet in circumference, additional grounding connections are required. directly to the station
ground grid.
h. Metal platforms and handrails shall be effectively grounded. Platforms that are not attached directly
to grounded structural columns shall be provided with #4/0 AWG grounding conductors extended
to the station ground grid or to the nearest directly grounded steel building column. Platforms and
gratings over 8 feet in length shall have at least two connections to ground located on opposite
ends of the platform.
i. Switchgear, motor control centers, transformers, vessels, and similar equipment metallic
enclosures shall be bonded to the steel structure or deck plate.
j. All motors shall be grounded with a separate insulated ground wire run inside the raceway with the
phase conductors and terminated inside the motor connection box. The frame of all motors shall
be bonded to the steel structure or deck plate. The frame of 460V rated motors shall be bonded
only at one point. The frame of 4000V rated motors shall be bonded at two points that are diagonally
opposite.
3.3.19 Equipment
1. Construction shall install all pushbutton stations, selector switches, relays, relay boxes and other
related items as indicated on the drawings.
a. Pushbuttons and selector switches shall be rated 600 VAC, of the heavy duty, oil-tight, factory
sealed type, or as shown on the drawings. Contacts shall be double break, silver-plated, and rated
for not less than 6 amperes continuous at 120 VAC. Color code pushbuttons in accordance with
NFPA 79, Section 10.2.2.
b. For switchgear indicating lights, Green indicates "OPEN" or "DE-ENERGIZED" condition and Red
indicates "On" or 'ENERGIZED' condition.
c. Control relays shall be of type required to perform the required function and shall be rated in
accordance with NEMA Standard ICS for Class B type relays.
2. Construction shall install all major electrical equipment as indicated on the modification drawings. Exact
locations will be checked by Construction to avoid any possible interference. Any changes shall be
documented in writing and agreed to by the Owner. Care shall be taken to protect delicate items
mounted on the equipment. The major electrical equipment includes, but is not limited to, the following:
a. Medium voltage metal-clad switchgear, including grounding resistor assembly when furnished; unit
substation(s), including grounding resistor assembly when furnished; 480V motor control centers;
emergency power switchboards and associated auxiliary equipment; 480V emergency power
distribution panelboards; uninterruptible power supply systems (UPS), including battery charger,
inverter, batteries and racks, static switch and associated equipment; fire and gas detection
systems; Halon or Novec fire suppression systems; instrument consoles, control panelboards and
telemetering cabinets; Electric motors.
3. Construction is responsible for mounting, connecting all conduits and terminating all wires to electrical
equipment & instruments, except where such equipment or instruments are already mounted and/or
pre-wired on "Package" Units including, but not limited to, the following:
a. Alarm and control switches (pressure, level, flow, temperature, etc.); solenoid operated valves;
analyzer circuits; thermocouples and RTD's; DC instruments (transmitters, transducers,
millimeters, etc.); miscellaneous equipment such as vibration switches and monitors; special cable
and cable assemblies associated with "package" units (gas turbine/compressor for instance); other
equipment specified elsewhere that requires electrical connection.
4. Construction shall install lighting fixtures, transformers, panels, switches, stanchions, supports, etc.
a. Lighting transformers, panelboards, fixtures, and receptacles shall be installed in such a manner
that they will not affect or obstruct the normal passageway clearances for personnel or equipment.
Refer to Appendix F for the required clearances. Care shall also be taken to place the lighting
fixtures in such a fashion that they can be maintained from the existing structure without the need
for scaffolding. All lighting fixtures and receptacles shall be left clean and operating properly at time
of final acceptance.
b. 120 volt single and duplex receptacles shall be rated as shown on the drawings, and shall be three-
wire, grounding type, with polarized tandem phase slots and U-shaped ground slot. The receptacles
shall conform to the requirements of NEMA Standard WD-1. Contact arrangement shall be such
that contact is made on both sides of each prong of the plug. Receptacles shall be side-wired with
two screws per terminal.
c. Receptacles installed outdoors and in nonhazardous process areas shall be mounted in a box
provided with a neoprene gasketed, weatherproof, cast-metal, cover plate and cap over each
receptacle opening. The cap shall be threaded type, and permanently attached to the box cover
plate with a short length of bead chain or cap shall be of a spring-hinged flap type. Receptacles
shall be of the GFCI type or supplied from a GFCI-type circuit breaker.No wire smaller than #12
AWG shall be used for any branch circuit supplying convenience receptacles. No receptacles shall
be supplied by any circuit that also serves one or more lighting outlets.
d. Receptacle circuits shall be controlled by circuit breakers as indicated on the drawings.
e. Whever practical, distribution and lighting transformers shall be installed indoors. Transformers
shall be general purpose, dry type, with an enclosure rated for the installation location.
f. The panelboards shall be installed as shown on the drawings and in accordance with the
Manufacturer's installation instructions. The panels shall be mounted with the height of the top of
the switch handle not exceeding 6 feet from the finished floor. An as-built panel schedule shall be
provided for each panelboard to indicate the function of each circuit in the panel. The panel
schedule shall be printed (not hand-written), and shall be permanently affixed to the panelboard or
of sufficient durability to withstand the installation environment.
g. Lighting fixtures shall be installed by Construction and shall be of type indicated on the drawings.
Lamps shall be of the proper type, wattage, and voltage rating for each lighting fixture. Final
adjustment in aiming fixtures shall be by Construction under the direction of the Alyeska Project
Engineer or Construction Supervisor.
5. Metal cable tray containrng power circuits shall contain a minimum of one (1) #4/0 copper grounding
conductor for each run of a cable tray. The grounding conductor shall be fastened to the cable tray on
the outside of the tray rail within 24 inches of the end point or splice plate of each cable tray section
with a ul approved ground clamp. All other trays in stack shall be grounded together at a maximum of
100' - 0" intervals and to the ground grid or building steel. Continuous cable tray system is grounded
within 2'-0" of every end point of a main run, or in the event of a closed loop within a building: the cable
tray loop is grounded at the dlagonally opposite points within the building.
6. Electrical equipment, trays, and conduit shall be bonded together to insure electrical continuity. all
conduit from cable trays to electrical equipment shall be bonded to the tray or to the grounding
conductor on the tray.
a. Load centers and power transformers shall be provided with a grounding connection from the
station ground grid to the transformer grounding terminal using 2-hole YGA-style compression
connectors or as specified by the design engineer. Ground conductor shall be #2 AWG for 50 kVA
or smaller transformers, #2/0 for 50 kVA through 150 kVA transformers, and #4/0 AWG for
transformers larger than 150 kVA. Threaded joints in conduit system shall be made up wrench tight
to provide a solid, low resistance ground return path. Where corrosion may be an issue such as
outdoor installations at PS01 or Valdez, cut threads shall be lubricated with a suitable rust inhibiting,
conductive thread sealer as described in Section 3.3.3 to ensure a reliable short-circuit current
return path.
b. All separate ground wires in each piece of equipment shall be connected together with bonding
jumpers. All metallic raceways (conduits, etc.) entering equipment enclosures (switchgear, motor
control center, lighting panelboard, lighting transformer, etc.) shall be bonded to the enclosure case.
c. Conduit hubs shall be used for terminating conduit in a sheet metal enclosure or box. The hub shall
be properly aligned and wrench tightened to ensure the continuity of the equipment grounding.
Bonding jumper between the conduit and the sheet metal enclosure or box is not required. For all
circuits over 250 volts to ground and all circuits with one or more end(s) in a classified location, a
bonding type locknut shall be used on the conduit hubs and a bonding wire shall be installed
between the locknut and building steel on both ends of the conduit.
d. All ground wires and bonding jumpers shall be sized In accordance with Table 250.122 in the NEC,
or larger.
e. External bonding jumpers shall be used on liquid-tight flexible metal conduit.
f. The isolated instrument reference ground bus bar provided in each input/output (I/O) cabinet, local
panel, Vendor furnished packaged instrument and control equipment and PLC cabinets shall be
insulated from any local ground point and tied back to one point on the plant main ground bus by
insulated single-path conductor(s). The main ground bus shall be located in the switchgear room
of the plant. Daisy-chaining will be permitted only within a motor control center or in other areas
where instrument systems are in close physical proximity.
g. All 480 volt and above power circuit conduits shall be grounded to the ground bus at the panelboard,
motor control center, or other power source. Where a resistance grounding system is available, the
neutral conductors shall be bonded to the neutral grounding resistor bus. The ground wire shall be
soft drawn copper, either bare or with green insulation. The ground wire shall be connected to the
conduits via an approved ground bushing. Multiple conduit penetrations may have a common
bonding jumper that connects several conduits to a ground bus providing the bonding jumper is
sized for the largest phase conductor in the group of conduits per table below:
Phase Conductor Bonding Jumper
#12 AWG #8 AWG
#10 AWG #8 AWG
#8 AWG #8 AWG
#6 AWG #6 AWG
#4 AWG #2 AWG
#2 AWG #2 AWG
#2/0 #2/0
#4/0 #4/0
350 kcmil #4/0
500 kcmil #4/0
report shall be performed in accordance with EE-15, Heat Trace Tape Test Report, and IRCL-ELEC-
08, Electrical Inspection – Heat Trace, or as alternatively with E-403-DAS-001 through E-403-DAS-
007, and as follows:
a. Heat-tracing cable shall be continuous from power source to splice box and splice box to splice
box. Splice boxes shall be installed only when specifically identified on the drawings and approved
by the Owner in writing.
b. Power connection boxes, splice boxes, termination kits and, particularly, grommets shall be given
special attention as to their correct type and size for the type of heat-tracing cable to be installed.
All power connection boxes and splice boxes shall be installed on upper quadrant of the pipe. The
installation of this equipment shall be in accordance with the Manufacturer's instruction. The cable
shall enter the bottom of the device enclosure with a loop to prevent water ingress.
c. Power cable shall be consistently color-coded at every connection. The heat-tracing cable shall be
correctly connected to each phase of the power cable using approved compression connectors or
terminal blocks. Field deviations of heat-tracing cable length from the construction drawings should
be kept within 5 percent (±2 1/2 percent) tolerance of individual circuit length. The Owner must be
informed of changes so that possible redesign of the system can be made.
d. The following are general provisions for installation, inspection, and testing of heat tracing systems
using self-regulating heat cable.
1) It is the Installer's responsibility to be familiar with piping and electrical isometric drawings
(ISO's), electrical details, and Manufacturer's installation instructions and details to verify the
proper size and type of heat trace cable, power connection kits, splice boxes, end-of-line (EOL)
devices, etc., required to complete the project.
2) After the piping system is completed and signed off by the piping inspector, Construction shall
install heat trace cable on pipe according to ISO's and design details. Heat trace should be
Megger tested on the reel from conductors to shield braid at 2500 VDC for 60 seconds. Pentair
cable insulation resistance testing less than 1000 MΩ should be rejected and marked as
defective for return to the vendor. Nelson or Thermon heat trace testing above 20 MΩ may be
accepted. Extra heat trace cable must be wrapped at all pipe supports, and other heat sinks.
Care shall be taken to maintain the minimum cable bending radius specified by the cable
manufacturer. Construction shall allow sufficient slack at all removable components (valves,
blind flanges, etc.) to facilitate their removal. Refer to the Manufacturer's installation instructions
for more specific information.
3) Construction shall preheat heat trace cables by putting them in a location heated to 70°F for at
least 24 hours prior to installation. Warming the cable by electrically energizing the heat trace
cable on its reel prior to pulling is is not recommended and acceptable only if explicitly approved
by the manufacturer in writing.
4) Construction shall not use mechanical cable pullers and shall not pull heater cable around
elbows or bends in the pipe.
5) Construction shall advance the heater cable around valves and other obstructions by hand.
After the heater cable is pulled through a complete section, the additional heater cable required
for the valve shall be pulled, forming a loop. Trace pipe supports, flanges, valves and other
heat sinks as recommended.
6) It is especially important that the outer jacket pass thru the environmental sealing grommet.
The braid (or shield) must not be grounded at any connection points (power connection, splice
connections and end-of-line devices).
7) Splices in the heat trace tape are allowed only if specifically identified on the drawings or
approved in writing by the Alyeska Project Technical Lead or Electrical SME. Construction is
required to identify the splice locations on the As-Built drawings.
8) When the end-of-line (EOL) device is installed, Construction shall pay particular attention to
isolating the braid (or shield) from ground. The braid (or shield) may be grounded at one
location only (normally, the power connection kit, unless otherwise specified in the design
drawings), after all construction tests are completed.
9) The recommended procedure for shield isolation at the EOL device is to strip off the outer
jacket and clip the braid as close as possible to the sealing grommet. The point where the outer
jacket and braid end at the EOL device shall be isolated with heat shrink tubing. The
recommended procedure for braid connection at splice boxes is to connect the braid inside the
splice box. Heat shrink should be used to isolate the braid as required.
10) After the pipe thermal insulation is installed, a second megger check must be performed to
ensure that no damage is done to the heat trace cable when the thermal insulation is installed.
The insulation resistance of the heat trace cable shall be re-tested between the conductors to
the braid and from the braid to ground using a 2500 VDC megger as described above. Record
final insulation resistance test values on the EE-15, EE-15 Heat Trace Test Report Form. If no
defects are found, the heat trace cable may be connected to the branch circuit at the power
connection box and the braid may be grounded at the power connection box.
11) The electrician responsible for functional testing of the heat trace system shall first test the heat
tracing control panel in accordance with the Manufacturer's test procedure and applicable
ground fault testing instructions.
12) Terminals shall be designed to prevent loosening. The terminal screws shall not make direct
contact with the conductors. The conductor shall be clamped between a metal yoke and a
copper current bar or suitable ring lugs where specified by the manufacturer. The terminals
shall be specifically approved by a Nationally Recognized Testing Laboratory (NRTL) for the
size of conductors they are used for. Only one conductor should be connected to each terminal.
If more than one conductor is connected to a single terminal, the terminal shall be specifically
listed by a NRTL for the number and size of conductors installed.
13) When all heat trace circuits are installed, inspected, and tested, a performance report must be
completed. Current readings shall be taken on all individual circuits at startup, 10 minutes and
5 hours after startup and compared to the projected loads of each circuit. Test results shall be
recorded on the EE-15, EE-15 Heat Trace Tape Test Report.
e. After each complete section is pulled, and prior to making any electrical connections, the heater
insulation integrity shall be tested.
f. After all connections are made, and before the installation of the pipe joint insulation, the electrical
and insulation integrity of the entire circuit shall be tested and documented by the Construction and
the Electrical Inspector.
c. Confirm that cables are neatly routed and tied, proper cable bending radius is maintained, labels
and phase identification tape are properly applied and agree with wiring diagrams, sufficient
separation is provided between power and signal cables, etc.
2. Cable Testing:
a. Prior to terminating cables, perform electrical tests on power and control cables as specified in the
IFC design package, on the IRCL-00 and EE-00 forms and in accordance with E-402; typically
Megger testing for low voltage power and control cables, and Hipot testing for Medium Voltage
cables. Low voltage instrument cable is not to be Megger tested; megohm and continuity tests
using a standard DMM of the signal conductors to ground is sufficient.
b. Rework or repair cables or terminators as necessary to resolve any UNSAT conditions found by
the inspector.
c. If station technicians are to perform “blue-line” point-to-point verification of modification project
cable connections, this work should be completed prior to final torque-down of terminal
connections.
d. Land cables on factory supplied terminal blocks or on two-hole YA-style compression connectors
using silicon-bronze or stainless steel hardware and torque to specified values. Apply torque
marking paint to completed connections.
e. Testing After Splicing and Terminating Cables
For final acceptance, all medium voltage cables shall pass the following tests in order given:
1) First, Shield and Conductor Continuity Test in accordance with Section 3.5, “Field Quality
Control-Electrical Inspection and Testing” of this specification.
2) Second, Insulation Resistance Test in accordance with Section 3.5 of this specification.
3) Third, Direct Current High Potential Test in accordance with Section 3.5 of this specification.
The Owner shall be notified 48 hours prior to this test. The Owner or its designated
representative shall witness test, record data, and interpret results.
Tests shall be performed prior to connection to equipment (bolting the lugs to the equipment).
5. . The Electrical Inspector shall inspect the completed cable tray system and complete the IRCL-ELEC-
12, Electrical Inspection – Cable Tray Installation prior to routing any cables.
6. All raceways shall be completely inspected by the Electrical Inspector. The completed inspection report
(IRLCL-ELEC-02, Electrical Inspection – Conduit Installation) shall be completed, signed, and
submitted to the Electrical Inspector for acceptance.
7. The Electrical Inspector shall inspect all heat trace environmental seals including the grommets at the
time of installation (since the proper grommet cannot be verified after box assembly).
8. The Electrical Inspector shall inspect heat trace installation to verify compliance with the isometric
piping details and the Manufacturer's installation instructions. The insulation resistance shall be
measured between the conductors to braid, and braid to ground using a 2500 VDC megger. The cable
tests shall be performed at 2500 VDC. Voltage shall be maintained for 60 seconds and then the
insulation resistance value recorded. The minimum acceptable insulation resistance value is 1000 MΩ
for Pentaire cable. Nelson or Thermon heat trace testing above 20 MΩ may be considered acceptable.
Values shall be recorded on the EE-15, EE-15 Heat Trace Test Report Form. If the cable fails at any
point to pass the insulation resistance test, suspend testing and troubleshoot and repair or contact
engineering for direction. These tests must be completed and verified as satisfactory by the electrical
inspector before pipe thermal insulation is installed. For in-service or follow-up maintenance testing of
heat trace cables, a resistance test value of 20 MΩ at 500 VDC shall be considered acceptable.
9. The Electrical Inspector shall document the accepted inspection of the heat trace by completing IRCL-
ELEC-08, Electrical Inspection – Heat Trace.
PHASE A
SHIELD
120 VAC
PHASE B
SHIELD
PHASE C
SAFETY METERED SHIELD
GROUND RETURN
Note
CONTROL UNIT No Connection is Made to
CONTROL CABLE the By-Pass Return
FIGURE #1
SINGLE CONDUCTOR CABLE
CONSTANT VOLTAGE TYPICAL CONNECTION DIAGRAM
TRANSFORMER Associated Research Model 5321A
DC HYPOT TESTER
GROUND
SAFETY METERED
GROUND RETURN
SHIELD
PHASE C
SHIELD
PHASE B
120 VAC
SHIELD
PHASE A
10. Transmit record file to Owner Assigned Engineer via Transmittal Letter and drawing index. Ensure
index includes complete and accurate drawing numbers, sheet numbers, revision numbers, and titles
for all drawings. A copy of approved redlined markup drawings are left on site for maintenance and
operations.
Appendix E. Reserved
MIN.
7 76
TOE
MIN.
CLEAR BODY
BENT
68
50° - 60°
30
FIXED LADDERS STAIR LADDERS
MIN.
80 SAME 80
WIDTH
PREFER AS STAIRS
90
30° - 35°
OPTIMUM
5 - 15°
NOTES:
1. All dimensions are minimum clearances for locating conduit, fittings, and equipment.
2. Dimensions are in inches.
REFERENCE:
• Architectural Standards, Seventh Edition by American Institute of Architects.
Conduit Nipple
(Minimum Length) Explosion Proof
Terminal Box
(COUNTERBORE BOX
IF REQUIRED PER
UL STANDARD 886)
Female Union
Rigid
Aluminum
Conduit
G.1 Application
Crouse-Hinds LNR Non-Metallic Conduit Liner is a cylindrical plastic insert installed at the end of rigid and
intermediate metallic conduit to provide for the smooth entry of conductors into hazardous and non-
hazardous enclosures. No tools are required for installation.
A smooth entry is required under NEC Article 344.46, UL 514B, and UL-886 to protect conductor insulation
from possible damage when being pulled through conduit into or out of enclosures.
NOTE
LNR bushings are not designed to be inserted over male unions as the union has a smooth throat. In
cases where the union does not thread completely through the enclosure wall, a close nipple and bushing
can be installed from the top if there are enough threads, or a nipple and female union need to be used
as the preferred method shows.
G.2 Installation
Crouse-Hinds LNR conduit liner is used with rigid metallic conduit in the following installation conditions:
Figure 6. Conduit Connection to Explosion Proof Enclosure – Alternate Method
1. Place the unflanged end of the liner into the installed conduit (from inside the enclosure) as shown in
Figure 8.
2. Push the liner into the conduit until the flange butts against the end of the conduit or box. See Figure
9.
Figure 9. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued)
G.3 Removal
LNR Liners are not designed to be reused. If removal is necessary, grasp the end of the liner by the flange
and pull. Discard the liner and install a new one. See Figure 10.
Figure 10. Conduit Connection to Explosion Proof Enclosure – Alternate Method (continued)
NOTES:
• The volume, based on wire size, of any device mounted in the fitting shall be deducted. Type GUA,
GUAB, GUAC, GUAD, GUAL, GUAN GUAT & GUAX have identical volumes for equal size.
• For combination of different wire sizes installed in a conduit body, the volume required shall be
calculated.
Table 2. Conduit Body Fill – Class I, Division 1, Group D Area
Body Type Crouse-Hinds Cat. No. Volume (In.3) Remarks
¾” GUA_ 26 - SA 13.5 —
1” GUA_ 36 – SA 15.5 —
1 ½” GUA_ 59 – SA 77.8 —
2” GUA_ 69 – SA 80.0 —
Table 3. Conduit Body Fill – Class I, Division 2, Group D and Unclassified Area (Crouse–Hinds
MARK 9 Fittings)
Conduit Body Size
¾" 1" 1 1/2" 2"
_29 _39 _59 _69
Conductor Size 10 cu. In. 12 cu. In. 35 cu. In. 75 cu. In.
#14 AWG 5 6 17 37
#12 AWG 4 5 15 33
#10 AWG 4 4 14 30
#8 AWG 3 4 11 25
#6 AWG — 2 7 15
NOTES:
• The volume, based on wire size, of any device mounted in the fitting shall be deducted. Type C, LB,
LL, LR, T. TB & X have identical volumes for equal sizes.
• For combination of different wire sizes installed in a conduit body, the volume required shall be
calculated.
Table 4. Conduit Body Fill – Class I, Division 2 or Unclassified Areas
Body Type Crouse-Hinds Cat. No. Volume (In.3) Remarks
Covers and gaskets must
¾” _-29 10
be ordered separately
Covers and gaskets must
1” _-39 12
be ordered separately
Covers and gaskets must
1 ½” _-59 35
be ordered separately
Covers and gaskets must
2” _-69 75
be ordered separately
Table 5. Volume Required per Conductor in Each Conduit Body or Box [Table is identical to NEC
Table 370-16(b)]
Conductor Size Free Space Box or Body for Each Conductor
NO. 18 1.5 in.3
NO. 16 1.75 in.3
NO. 14 2 in.3
NO. 12 2.25 in.3
NO. 10 2.5 in.3
NO. 8 3 in.3
NO. 6 5 in.3
Table 7. 40% Fill (Maximum Number of 600V Single Conductors with NEC Type XHHW Insulation)
Conduit and Seal Trade Size
CONDUCTOR SIZE 1/2" 3/4" 1" 1-1/2" 2" 3" 4"
AREA
IN SQ.
AWG OR kcmil IN. 0.12 0.21 0.34 0.82 1.34 2.95 5.00
#18, 16 & 14 AWG 0.0139 9 15 25 50 — — —
#12 AWG 0.0181 7 12 20 47 50 — —
#10 AWG 0.0243 5 9 15 37 50 — —
#8 AWG 0.0437 2 4 7 17 28 50 —
#6 AWG 0.059 1 2 4 10 16 36 50
#4 AWG 0.814 1 2 4 9 16 35 50
#2 AWG 0.1146 1 2 3 7 11 25 43
#1/0 AWG 0.1825 — 1 2 4 7 15 27
#2/0 AWG 0.219 — 1 1 3 6 13 22
#4/0 AWG 0.3197 — — 1 2 4 9 15
250 kcmil 0.3904 — — 1 2 3 7 12
350 kcmil 0.5166 — — — 1 2 5 9
500 kcmil 0.6984 — — — 1 2 4 7
*40% fill is achievable only when using Appleton Type “EYSEF” and “EYDEF” expanded fill sealing fitting.
Available in ½” through 4” sizes only.
4. Conduit seal fills for multiconductor and multi-pair/triad cables are based on 50% of the seal cross
sectional area available for sealing around the cable jacket – considering the cable as incapable of
transmitting fluid through the core per NEC.
5. Cable seal fills are based on 25% of the seal cross sectional area available for sealing individual
conductors of multiconductor and multi-pair/triad cables per UL 886.
6. Table 2 is based on the largest diameter of either Okonite X-Olene-Okoseal Type TC (XLPE insulation
with Arctic Grade PVC Jacket), Rockbestos Firewall III (XLPE insulation with Chlorosolfonated
polyethylene jacket), Rockbestos Pyro-Trol (FR-XLPE with Arctic Grade PVC Jacket) or Continental
FREP-LT (EP insulation and Flame-retardant, low temperature PVC jacket).
7. Table 3 is based on the largest diameter of either Okonite X-Olene Okoseal Type TC Cable (XHHW
insulation and Arctic Grade PVC Jacket), Rockbestos Firewall III 90°C Type TC (XLPE insulation, XLPE
Jacket), or Cablec/Continental FREP LT (EP insulation and Flame-Retardant, low temperature PVC
Jacket).
Table 10. Dimensions and Percent Area of Conduit
A Bc C D E F
Requirements
for This Spec.
Over 2 Over 2
Internal Total Area 1 Conductor Conductors Conductors
Diameter 100% Fill Sq. 53% Fill Sq. 40% Fill Sq. 25% Fill Sq.
Trade size Inches Inches Inches Inches Inches
½” 0.632 0.314 0.166 0.125 0.079
¾” .0836 0.549 0.291 0.220 0.137
1” 1.063 0.888 0.470 0.355 0.222
1 ½” 1.624 2.071 1.098 0.829 0.518
2” 2.083 3.408 1.806 1.363 0.852
3” 3.090 7.499 3.975 3.000 1.875
4” 4.050 12.883 6.828 5.153 3.221
5” 5.073 20.213 10.713 8.085 5.053
6” 6.093 29.158 15.454 11.663 7.29
Table 11. 300 Volt Instrument Multi-Pair/Triad Type “EYS” Seal Fill Table
300V Cables
(Pairs or Maximum Size of Size of
Triads O.D. of Area of “EYS” Type “EYS” Type
Overall Conductor Cables Cable (Sq. of Cable of Conduit
shield Only) Size (AWG) (Inches) Inches) Seal Seal Remarks
1 TRIAD #16 0.320 0.80 ½” or ¾” ½” or ¾” See Table 9
4 TRIAD #16 0.627 0.309 1” 1”
4 TRIAD #20 0.521 0.213 1” ¾”
1 PR #16 0.300 0.070 ½” or ¾” ½” or ¾”
4PR #16 0.500 0.196 1” ¾”
8 PR #16 0.630 0.311 1” 1”
12 PR #16 0.750 0.441 1 ½” 1”
24 PR #16 1.990 0.769 2” 1 ½”
36 PR #16 1.235 1.198 3” 2”
4 PR #20 0.442 0.153 ¾” ¾”
6 PR #20 1.53 0.22 1” ¾”
8 PR #20 0.537 0.226 1” ¾”
12 PR #20 0.631 0.313 1 ½” 1”
24 PR #20 0.850 0.567 1 ½” 1 ½”
36 PR #20 1.000 0.785 1 ½”
Gaitronics 5 # 18 and
Cable – 8/C 3 #14 0.63 0.31 1” 1”
Table 12. 300 Volt Instrument Multi-Pair/Triad Cable Type EYS” Seal Fill Table
300V Cables
(Pairs or Maximum Size of Size of
Triads O.D. of Area of “EYS” Type “EYS” Type
Overall Conductor Cables Cable (Sq. of Cable of Conduit
shield Only) Size (AWG) (Inches) Inches) Seal Seal Remarks
4 TRIAD #16 0.580 0.264 1” ¾”
8 TRIAD #16 0.790 0.490 1 ½” 1 ½”
12 TRIAD #16 1.980 0.754 1 ½” 1 ½”
16 TRIAD #16 1.175 1.084 2” 2”
4 TRIAD #20 0.538 0.227 1” ¾”
8 TRIAD #20 0.69 0.37 1 ½” 1”
12 TRIAD #20 0.843 0.558 2” 1 ½”
16 TRIAD #20 0.930 0.679 2” 1 ½”
24 TRIAD #20 1.10 0.95 3” 1 ½”
4 PR #16 0.540 0.229 1” ¾”
8 PR #16 0.710 0.395 1 ½” 1”
12 PR #16 0.850 0.567 1 ½” 1 ½”
24 PR #16 1.190 1.112 3” 2”
36 PR #16 1.350 1.431 3” 2”
4 PR #20 0.483 0.183 1” ¾”
6 PR #20 0.540 0.229 1” ¾”
8 PR #20 0.598 0.284 1 ½” 1”
12 PR #20 0.741 0.431 1 ½” 1”
24 PR #20 1.016 0.810 3” 1 ½”
36 PR #20 1.149 1.037 3” 2”
4/C (QUAD) #16 0.50 0.20 ½” or ¾” ¾”
Combinations of multiconductor instrument cables installed in one seal shall be limited per Table 7.
Table 13. Maximum Number of #20 AWG and/or #16 AWG Conductors Permitted in “EYS” Seals
at 25% Area Fill (Drain Wires Considered Same Size)
No. of Conductors 5 9 15 37 50
Example: One 4 Triad #16 (Individually Shielded) cable and one 8 Pair #20 (Individually Shielded)
cable are to be installed in one conduit and sealed with a conduit and a cable seal.
1. Conduit and Conduit Seal Size Required:
4 triad #16 = 0.33 sq. inches
8 pair #20 = 0.28 sq. inches
TOTAL: = 0.61 sq. inches
From 25% Fill Column (Table 6) on Sheet 7, Table 4, conduit size is 2".
Note: Each cable is considered one conductor.
2. Cable Seal Size Required:
4 triad #16 = 4 x 4 = 16 + 1 (Overall Shield Drain) = 17 Conductors
8 pair #20 = 8 x 3 = 24 + 1 (Overall Shield Drain) = 25 Conductors
TOTAL: = 42 Conductors
From Table 7, Cable Seal Size Required is 2".
Table 14. 300V Instrument Single Pair Cable Type “EYS” Seal Fill Table
Maximum
Number of Single
Pairs Minimum Size of Minimum Size of
(Individually “EYS” Type “EYS” Type
Shielded) Conductor Size Cable Seal Conduit Seal Remarks
1 #16 1/2" 1/2" SEE NOTE 4
2 #16 3/4" 3/4" SEE NOTE 4
3 #16 1" 1" SEE NOTE 4
7 #16 1 1/2" 1 1/2" SEE NOTE 4
12 #16 2" 2" SEE NOTE 4
28 #16 3" 3" SEE NOTE 4
Table 15. 300V Instrument Single Pair Cable Type “EYS” Seal Fill Table
Maximum
Number of Single
Triads Minimum Size of Minimum Size of
(Individually “EYS” Type “EYS” Type
Shielded) Conductor Size Cable Seal Conduit Seal Remarks
1 #16 1/2" 1/2" SEE NOTE 4
2 #16 3/4" 3/4" SEE NOTE 4
3 #16 1" 1" SEE NOTE 4
7 #16 1 1/2" 1 1/2" SEE NOTE 4
11 #16 2" 2" SEE NOTE 4
25 #16 3" 3" SEE NOTE 4
Table 16. Single Pair #16 or Triad #16 with Gas Blocking Kits Installed in the Type “EYS” Seals Fill
Table
Shielded Single Pair:
Maximum No. of Pairs Seal Fill (Sq. Inches)
Minimum Size of “EYS” Gas Blocked in Seal Based on O.D. of
Type Conduit Seal with Kits Cable Size and Type Blocking Kit
¾” 1 #16 T/S – 300V 50% MAX
1” 1 #16 T/S – 300V 50% MAX
1 ½” 3 #16 T/S – 300V 25% MAX
2” 4 #16 T/S – 300V 25% MAX
3” 10 #16 T/S – 300V 25% MAX
Hazardous Area
Termination Box
Fitting or "EYS" Seal Conduit
INSTALLATION DETAIL
NOTE:
When installing cable seals, the outer jacket shall be removed so that sealant will
surround each individual insulated conductor and outer jacket as indicated
above. After installation, the blocking kit shall be installed in fitting, seal or
adjacent to terminal blocks in
terminal box per interconnection diagram.
Field to supply the following material when kits are supplied in bulk form:
1. Aluminum foil (Reynolds or equal) for heat deflector shields.
2. Trichloroethane solution, concentration: 1, 1, 1 for cable cleaner.
Number of Hot Melt Sealant Sleeves to Use per Cable:
1. Instrument pairs and gas sensor triads with individual shields Field to install one hot melt sealant sleeve
for each pair or triad and one hot meld sealant sleeve for each pair or triad drain wire.
Examples: A. 1 Pair #16 = 2 Sleeves
B. 1 Triad #16 = 2 Sleeves
C. 1 Quad #16 = 3 Sleeves
Appendix M. Nameplates
Figure 13. Nameplates
3-1/2" (See notes, Typical)
3-1/8 "
3/16"
5/8"
2 HOLES 9/64”
1-1/4"
1/32" BEVEL
SAMPLE
LETTERING
18 LETTERS OR SPACES
TOP OR BOTTOM ROWS
SAMPLE
LETTERING
REQUIRED
15 LETTERS OR SPACES
CENTER ROW
NOTES:
1. Dimensions are minimum, increase as required.
2. Material: Laminated Bakelite, 1/16-inch thick, white surface, black core.
3. Engraving: Engrave through white surface to expose black core. Lettering style shall be condensed
Gothic, ¼-inch high.
4. Lettering: Arrange all lettering to the center of the plate. Use one, two or three lines of lettering as shown
on nameplate schedule.
5. Attachment to NEMA 7 Enclosures shall be in accordance with UL Standards for Safety 698, 886, and
1604.
Purchaser:
A firm or individual who enters into an agreement to purchase material, equipment or services or both for
the Owner of the project. The Owner may also be the Purchaser.
Shop Drawings:
Working drawings created by a Manufacturer or fabricator that specify all dimensional and fabrication details
necessary to build an assembly.
Thermal Output:
A manufacturing acceptance test designed to verify the power output in wattage output per unit length of a
self regulating heat trace tape as measured at 50°F.
Vendor:
A firm or individual who enters into an agreement to supply material, equipment or services or both for the
Owner of the project. The Vendor can also be a manufacturer.