Professional Documents
Culture Documents
Grundfosliterature 1073119
Grundfosliterature 1073119
Stephan Göttsche
General Manager
2
Fire NKF - diesel
Installation and operating instructions 4
3
CONTENTS 9.7 Replacing the V-belt 22
9.8 Controller 22
Page
10. Fault finding chart 23
1. Symbols used in this document 4
1.1 Systems according to VdS 5 11. Service, spare parts, accessories 24
2. Applications 5 12. Warranty 24
3. Delivery, transport, storage 5 13. Accompanying documentation 24
3.1 Delivery 5 14. Disposal 24
3.2 Transport 5 15. Appendix 25
3.3 Storage 5 15.1 Dimensions and weights 25
3.3.1 Pump 5 15.2 Engine data 25
3.3.2 Engine 5
4. Product description 6 Warning
4.1 General construction 6
Prior to installation, read these installation and
4.1.1 Pump 9
operating instructions. Installation and operation
4.1.2 Engine 9
must comply with local regulations and accepted
4.1.3 Controller 9
codes of good practice.
4.2 Description of function 10
4.3 Identification 11
4.3.1 Type key for pump unit 11 1. Symbols used in this document
4.3.2 Codes for shaft seal 11
4.3.3 Type key for engine 11 Warning
4.4 Technical data 12 If these safety instructions are not observed, it
4.4.1 Complete pump unit 12 may result in personal injury!
4.4.2 Pump 12
4.4.3 Engine 12 If these safety instructions are not observed, it
4.4.4 Battery 13 Caution may result in malfunction or damage to the
4.4.5 Controller 13 equipment!
4.5 Operating conditions 13
4.5.1 Minimum inlet pressure 13 Notes or instructions that make the job easier
Note
4.5.2 Maximum inlet pressure 13 and ensure safe operation.
4.5.3 Minimum flow rate 13
4.5.4 Bypass connection 13 Safety instructions placed directly on the pump unit:
4.5.5 Pumped liquids 13
4.5.6 Liquid temperature 13
4.5.7 Pump speed 13 WARNING Warning
THIS EQUIPMENT STARTS
4.5.8 Maximum operating pressure 13 AUTOMATICALLY The engine will start automatically!
4.5.9 Ambient temperature 13 USE EAR PROTECTION Wear hearing protection!
C13187
4.5.10 Relative air humidity 13
4.5.11 Effect of ambient temperature and altitude on engine
output 13 WARNING
5. Installation 14 KEEP
Warning
GUARDS
5.1 Mounting 14 IN PLACE Do not remove safety devices!
5.1.1 Installation site 14 C13190
5.1.2 Foundation 14
5.1.3 Vibration dampening 15 Warning
5.1.4 Pipework 15 WARNING Fill the engine with a cooling liquid
PREMIXING 50%
5.1.5 Fresh air supply 15 TREATED WATER
AND 50% ANTI/FREEZE consisting of a mixture of 50 %
COOLANT SOLUTION
5.1.6 Exhaust gas system 16 PRIOR TO INSTALLING coolant and 50 % water before start-
IS REGUIRED
5.1.7 Connecting the cooling system 16 C13185
up.
5.1.8 Vent tank and test pipe 16
5.1.9 Aligning pump and engine 16
5.2 Electrical connection 17 WARNING Warning
6. Start-up 17 60 P.S.I. MAX. The pressure in the equalisation tank
must not exceed 60 psi or 4.1 bar.
7. Operation 17 C13182
PERSONAL INJURY OR
9.3.3 Fuel system 19 ENGINE DAMAGE MAY
RESULT. This may cause personal injury or
C13191
9.3.4 Exhaust gas system 19 damage to the engine.
9.3.5 Air filter 19
9.3.6 V-belt 20
9.4 Oil change with filter 20 WARNING Warning
LIFTING BRACKET
9.5 Changing the fuel filter 20 IS FOR ENGINE ONLY This lifting point is only for lifting the
9.5.1 Changing the fuel filter, JU4H and JU6H 20 engine, not the entire pump unit.
C13186
9.5.2 Changing the fuel filter, JW6H 21
9.6 Changing the cooling liquid 22
4
3.3 Storage
Lifting points for the entire pump unit. 3.3.1 Pump
Apply a suitable antirust agent on all machined, non-coated
surfaces. If the pump must be stored for more than six months
1.1 Systems according to VdS before start-up, the inner pump components must be treated with
a suitable antirust agent.
In systems made according to VdS, installation, operation and
maintenance must take place according to VdS guidelines. The antirust agent must meet these requirements:
Installation, maintenance and repair of Grundfos Fire NKF pump • It must not attack rubber parts.
units must only be carried out by qualified personnel certified by • It must be easy to remove.
the German VdS Schadenverhütung GmbH. • It must be applied according to the instructions of the
manufacturer.
2. Applications To prevent water, dust, etc. from entering the pump, all openings
The Grundfos Fire NKF pump units are designed for fire systems must be covered until pipes are connected.
for supplying water to hose reels, fire hydrants and sprinkler 3.3.2 Engine
systems.
Engines may be stored for up to 12 months in a dry room after
Warning delivery. It is recommended to protect the engines with an air-
permeable cover. At least once a month, the engine should be
The pump unit must only be used for the
checked for accumulation of dirt or water. Any dirt or water must
applications mentioned. Any other use is
be removed immediately.
considered improper use. Grundfos cannot be
held responsible for damage caused by improper If the engine is stored for more than 12 months or stopped for
use. The liability rests solely with the operator. more than six months, it must be protected against corrosion and
damage as follows:
3. Delivery, transport, storage 1. Drain the engine of oil, and replace the oil filter. See section
9.4 Oil change with filter.
Check the pump unit carefully on delivery, and 2. Fill the engine housing with MIL-L-21260 oil. See section
Note transport and store it correctly before 9.4 Oil change with filter.
installation. 3. Replace the fuel filter. See section 9.5 Changing the fuel filter.
3.1 Delivery 4. Separate the engine from the pump.
5. Turn on the engine. See section 7.2 Manual operation. Let the
The pump unit is delivered from factory in an open wooden box or
engine run for one or two minutes.
wooden/cardboard box which is specifically designed for
transport by fork-lift truck or similar device. 6. Drain oil and cooling liquid. See sections 9.4 Oil change with
filter and 9.6 Changing the cooling liquid.
3.2 Transport 7. Drain fuel. To do so, loosen the drain screw in the tank bottom
For lifting the entire pump unit, use the lifting eyes welded on the (fig. 29, pos. 9), and collect the diesel fuel in a suitable
base frame and specifically marked. When lifting, the lifting point container. After draining, tighten the drain screw in the tank
should always be above the centre of gravity of the pump unit. bottom.
See fig. 1. 8. Place a warning label on the engine: Engine without oil. Do not
start the engine.
Warning
Repeat these steps every six months.
When lifting the entire pump unit, never use the
lifting eyes of the individual components.
Use only suitable lifting equipment in proper
condition. See also weight specifications in
section 4.4 Technical data.
During transport of the pump unit, the front door
of the control cabinet must be closed and locked.
TM03 9937 4607
5
4. Product description
4.1 General construction
The complete pump unit consists of a pump, a diesel engine and
the controller. The pump and engine are connected via a flexible
coupling. All components are adapted to each other and mounted
on a common base frame ready for installation.
The pump unit comes ready for operation. The engine is filled
with cooling water, engine oil, etc. The batteries are filled with
acid and charged. The fuel system is vented, and the fuel tank
has a small quantity of diesel fuel. The correct engine speed has
been preset from factory.
All important data of the pump unit are on the pump nameplate
(fig. 2), engine nameplate (fig. 3) and controller nameplate
(fig. 4).
VdS
pump VdS-approved
6
30
8
26
1 20
2 27
7
23
Fig. 5 Pump unit with JU4H and JU6H engine, front view
4 3 16 15 13
10
18
19
17
25
24
Fig. 6 Pump unit with JU4H and JU6H engine, back view TM04 0110 5007
7
4
10 11 19
12
16
8.1
1 8.2
26
27
28 29
21
6
13
3 15
18
2
17
24
8
4.1.1 Pump 4.1.3 Controller
The pumps of the pump unit are non-self-priming, single-stage The pump unit is controlled via a Minimax controller especially
Grundfos NKF standard pumps with spiral housing. The pumps sized for diesel engines driving fire pumps. The purpose of the
have an axial suction port and a radial discharge port with PN 10 PLC controller is to start the pump automatically and monitor the
or PN 16 flanges according to EN 1092-2. diesel engine.
The NKF pumps are available in these models: As soon as the sprinklers are activated due to an alarm and water
is consumed, the pressure in the discharge pipe is reduced. If the
Model A
pressure becomes lower than the start pressure set at the
NKF 200-500. pressure switch, the pump starts automatically.
Model B The pump is stopped manually via the controller.
NKF 50-200, NKF 65-200, NKF 80-200, NKF 80-250,
NKF 150-400, NKF 150-500. The controller has a VdS approval for use in fire
Note
systems.
The impeller diameter can be reduced to customise the pump
performance to a certain duty point. The actual impeller diameter General construction
may therefore deviate from the standard diameters stated in The controller is in a control cabinet mounted on the base frame.
catalogues, data sheets etc. The actual impeller diameter is The controller is operated by means of the control panel in the
stated on the pump nameplate. cabinet door. See fig. 9. The control cabinet supplies the engine
The NKF pump is equipped with a rubber bellows seal, type with the power required for starting and operating the engine. If
BAQE, with sealing faces of metal-impregnated carbon/silicon the power supply fails, the two redundant starter sets take over
carbide. The elastomer parts are of EPDM. this task.
John Deere which has been especially adapted to meet the H11 H16
XXXXXXX
Status
JU4H-NL50 Description
fault
light
JU6H-NL30
Fire NKF 150-400 JU6H-NL50
JU6H-NL60 H1 Green Fire pump operation
JW6H-NL30 H2 White Fire pump stopped
JU6H-NL60 H3 Yellow Common fault
Fire NKF 150-500 JW6H-NL30 H4 Green Processor on
JW6H-NL40 H5 Green Blinds, air in, open
H6 Green Blinds, air out, open
The injection pump has been set from factory,
Caution H7 Green Pressure switch 1 triggered
and the setting must not be changed.
H8 Yellow Pressure switch 1 fault
The engine is cooled via a heat exchanger. The cooling liquid is
led to the heat exchanger via a pipe connected to the discharge H9 Green Pressure switch 2 triggered
port of the pump. The discharge from the heat exchanger is led H10 Yellow Pressure switch 2 fault
via an open outlet according to VdS regulations. H11 Green Starting/ready
H12 Red Error start
Note The engines meet the requirements of VdS.
H13 Red Diesel auto-start locked
H14 Yellow Battery set 1 fault
H15 Yellow Battery set 2 fault
H16 Green Motor monitoring on
H17 Red Oil pressure low
H18 Red Overtemperature
H19 Red Fuse blown
H20 Yellow Electric generator dropped out
H21 Red Fuel tap closed
H22 Yellow Transmission path fault
H23 Red Fuel shortage
H24 Yellow Transmission path fault
9
The start command lines are redundantly designed. Each
Control buttons and meters pressure switch is connected to a monitoring and start command
trigger line. Existing start commands are shown by the indications
H7 "Pressure switch 1 triggered" or H9 "Pressure switch 2
Meters
Button
Colour Description
mark
triggered".
Fault conditions, such as voltage failure of monitoring, wire
Dis. Display breakage or short-circuit, are shown for the pressure switch in
S1 Green Fire pump on, starting unit 1 question (yellow indicator light H8 "Pressure switch 1 fault", H10
"Pressure switch 2 fault").
S2 Green Fire pump on, starting unit 2
S3 Red Fire pump off Monitoring of fuel system
S4 Yellow Start error/release The position of the fuel tap and the fuel filling quantity are
monitored in the same way as the pressure switches.
S5 - Indicator light test
Fuel shortage is only indicated if the shortage exists for more
S6 - Horn off/reset
than five seconds (H23 "Fuel shortage").
S7 - Menu scrolling
Monitoring of oil pressure
H0 Horn (acoustic)
-1 If the oil pressure is reduced, a warning will be given (H17 "Oil
P1 Tachometer [min x 1000]
pressure low"). The oil pressure is monitored via a pressure
P2 Oil pressure [bar] sensor on the engine when the engine has been started and the
P3 Cooling water temperature engine monitoring has been cut in. The fault is indicated when it
P4 Amperemeter, battery set 1 has existed for more than five seconds.
P5 Voltmeter, battery set 1 Monitoring of temperature
P6 Amperemeter, battery set 2 A warning is given if the permissible engine temperature is
P7 Voltmeter, battery set 2 exceeded (H18 "Overtemperature"). The temperature is
P8 Hour counter monitored via a temperature sensor on the engine when the
engine has started and the engine monitoring is switched on. The
4.2 Description of function fault is indicated when it has existed for more than five seconds.
Control takes place via the functions described below. Monitoring of electric generator
Automatic operation A warning is given if the electric generator fails (H20 "Electric
generator dropped out"). The electric generator is monitored
If the pressure switch detects a pressure drop in the fire pump
when the engine has started and the engine monitoring (H4) is
pipes, engine starting will be activated after a delay of about 2.5
switched on. The controller monitors whether the electric
seconds. The starter will be activated for a start attempt duration
generator produces 24 V when the engine has started.
of about seven seconds. If the engine does not start, up to five
additional start attempts of seven seconds each will take place at Locking of automatic starting after several failed attempts
intervals of three seconds. Prior to each new start attempt, a After the sixth failed start attempt, a warning is given (H12 "Error
changeover between starting units takes place. start"), and automatic starting is locked (H13 "Diesel auto-start
After six failed start attempts, the controller is locked and the locked"). The lock can be cancelled with the button S4 "Start
indication H12 "Error start" is shown. To reset the indication and error/release".
return to automatic operation, press the button S4 "Start error/ While the automatic starting is locked, the engine can still be
release". If the start command is still active via the pressure started manually.
switches, the start program will be carried out again.
Monitoring of batteries
After a successful start, the engine monitoring (H4) will be
If the battery voltage falls below the specified value or no battery
switched on after a delay of about seven seconds. Faults, such
is connected, a warning will be given (H14 "Battery set 1 fault",
as H17 "Oil pressure low", H18 "Overtemperature" and H20
H15 "Battery set 2 fault"). Both battery sets are monitored.
"Electric generator dropped out", result only in alarms, not in
stopping the engine. Monitoring of engine operation
The engine can only be stopped manually by means of the button All faults are indicated acoustically by a horn. The indication is
S3 "Fire pump off". reset with button S6 "Horn off/reset".
If the automatic start command still exists while the engine is All faults are also indicated by an indicator light.
being stopped, the indication H2 "Fire pump stopped" will be The fault is indicated by a flashing indicator light. The indicator
shown. This indication will only disappear when the start light changes to permanently on when the button S6 "Horn off/
command of the pressure switch is not active any more. reset" is pressed.
Manual operation Every new fault is indicated by a flashing indicator light and must
Via the buttons S1 "Fire pump on, starting unit 1" or S2 "Fire be reset with the button S6 "Horn off/reset".
pump on, starting unit 2" the pump is started by means of starting When the faults have been cleared, the button S6 "Horn off/reset"
unit 1 or 2. must be pressed to reset the fault indications.
No automatic program run takes place in manual operation. Interruption of the fuel supply
When the two on-buttons are pressed, the starter relays will be Via a solenoid valve the controller automatically interrupts the
cut in directly and the solenoid switch of the starter will be cut in fuel supply when the pump unit is switched off.
with a time delay, i.e. when the engine has started, the on-button
Blinds control
must be released.
To ensure a sufficient supply of fresh air to the engine and a
The engine is stopped with the button S3 "Fire pump off", and the
targeted heat removal, it may be necessary to install blinds. The
controller returns to automatic operation.
blinds can be controlled via the control cabinet. The starter
Monitoring of voltage supply batteries power the motors of the blinds, which are opened with
The supply voltage is monitored to detect phase failures. In case the indication H1 "Fire pump operation" or closed when the
of mains failure, the control voltage will be obtained from the engine is switched off.
starter batteries. Cooling water heater
Monitoring of pressure switches Some pump units are equipped with a cooling water heater for the
The pressure switches are monitored by monitoring the quiescent engine. For this purpose, the control cabinet contains a 10 A
current (quiescent current resistance 470 Ohm, load current circuit breaker. The heater adjusts itself via an external cooling
resistance 470 Ohm) to detect wire breakage and short-circuit. water thermostat.
10
4.3 Identification
4.3.1 Type key for pump unit
Fire systems
Pump type
F: Pump approved for fire fighting
Nominal diameter of discharge port [mm]
Driver
D: Diesel engine
Pipe connections
D: DIN flange
Coupling
F: Flexible coupling, type Centaflex
The example shows a VdS-approved Fire NKF 80-250 pump unit, 4.3.3 Type key for engine
with the following components:
• 270 mm impeller Example: J U 4 H -NL 24
• BAQE shaft seal
Engine type
• diesel engine as driver J: John Deere-based engine
• flexible coupling.
Engine series
4.3.2 Codes for shaft seal U: Standard range
The shaft seal is described by means of a code consisting of four 4-cylinder engine = 4.5 litres
letters. See the table below. 6-cylinder engine = 6.8 litres
W: Special range
Position Code Description 6-cylinder engine = 8.1 litres
X: 6-cylinder engine = 12.5 litres
1 B Rubber bellows seal
Position Code Material Number of cylinders
4: 4 cylinders
A Metal-impregnated carbon 6: 6 cylinders
2 and 3
Q Silicon carbide
Cooling
Position Code Material H: via heat exchanger
4 E EPDM Approvals of engine
NL: non-listed
11
4.4 Technical data
Forces
4.4.1 Complete pump unit Diameter [N]
Grey cast iron
Dimensions: See section 15.1. DN
Fy Fz Fx ΣF*
Weight: See section 15.1.
50 525 473 578 910
Sound pressure level
65 648 595 735 1155
Horizontal pump,
Sound pressure 80 788 718 875 1383
Pump type Engine type z-axis, discharge port
level 150 1575 1418 1750 2748
200 2095 2600 2100 4055
Fire NKF 50-200 JU4H-NL14 97.2 dB(A)
65 735 648 595 1155
Fire NKF 65-200 JU4H-NL14 97.2 dB(A)
80 875 788 718 1383
JU4H-NL14 97.2 dB(A) Horizontal pump,
Fire NKF 80-200 100 1173 1050 945 1838
JU4H-NL24 97.2 dB(A) x-axis, suction port
200 2345 2100 1890 3658
JU4H-NL24 97.2 dB(A) 250 2980 2700 3340 5220
Fire NKF 80-250
JU4H-NL34 98.1 dB(A)
JU4H-NL50 98.6 dB(A) Torques
JU6H-NL30 99.2 dB(A) Diameter [Nm]
Grey cast iron
DN
Fire NKF 150-400 JU6H-NL50 99.2 dB(A) My Mz Mx ΣM*
JU6H-NL60 99.4 dB(A)
50 350 403 490 718
JW6H-NL30 100.3 dB(A)
65 385 420 525 770
JU6H-NL60 99.4 dB(A) Horizontal pump,
80 403 455 560 823
Fire NKF 150-500 JW6H-NL30 100.3 dB(A) z-axis, discharge port
150 613 718 875 1278
JW6H-NL40 101.4 dB(A)
200 805 928 1138 1680
The sound pressure level was measured without a silencer 65 385 420 525 770
1 metre away from the unit.
80 403 455 560 823
Horizontal pump,
The dimensions of the silencer delivered from 100 438 508 613 910
x-axis, suction port
factory are designed to meet the sound pressure 200 805 928 1138 1680
level requirements at the installation site.
Note 250 1260 1460 1780 1680
The site or the required sound pressure level
must therefore be specified when placing the
* ΣF and ΣM are the vector sums of the forces and torques.
order.
If not all loads reach the maximum permissible value, one of the
Warning values is allowed to exceed the normal limit. Contact Grundfos for
The sound pressure level when the engine is further information.
running is >70 dB(A). Hearing protection must
4.4.3 Engine
therefore be worn when working on or near the
engine. Type: 4-stroke diesel engine.
Performance: See section 15.2.
4.4.2 Pump
Speed: See section 15.2.
Permitted flange forces and torques
Weight: See section 15.1.
Diameter exhaust gas line: See section 15.2.
Discharge heat exchanger:
Amount of oil: See section 15.2.
Type of oil: API-classification CF4.
Viscosity: 15 W-40.
12
4.4.4 Battery Install a bypass pipe to ensure a minimum flow rate equal to 2 %
of the flow rate at maximum efficiency. The flow rate helps to
4-cylinder engine
dissipate any excessive heat and thus protect the pump against
4 x CLT120-12 with 12 V - 120 Ah.
overheating.
Battery dimensions L x W x H: 410 x 177 x 225 mm.
4.5.4 Bypass connection
Weight: 38 kg.
The battery is maintenance-free. Pump type Bypass connection
6-cylinder engine
NKF 50-200 Rp 3/8
4 x CLT200-12 with 12 V - 200 Ah.
NKF 65-200
Battery dimensions L x W x H: 520 x 240 x 220 mm.
NKF 80-200
Weight: 66 kg.
NKF 80-250 Rp 1/2
The battery is maintenance-free.
NKF 150-400
4.4.5 Controller
NKF 150-500
Control cabinet: Sheet steel, red.
Enclosure class: IP54. 4.5.5 Pumped liquids
Dimensions W x H x D: 800 x 1000 x 300 mm. The pump is suitable for clean and non-aggressive water, not
Weight: 80 kg. containing solid particles or fibres.
Supply voltage: 230 V / 50 Hz / N / PE. 4.5.6 Liquid temperature
Voltage tolerance: ± 10 %. Maximum liquid temperature according VdS CEA guidelines 4001
Max. current consumption is +40 °C (maximum temperature range for pump: 0 °C to
(incl. cooling water heater): 13 A. +120 °C).
Overvoltage category: III. 4.5.7 Pump speed
Rated surge voltage: 4 kV. The maximum pump speed is stated on the Certificate of
EMC-noise emission: According to EN 61000-6-3. Approval, issued by VdS and shown on the nameplate.
EMC-noise immunity: According to EN 61000-6-2. 4.5.8 Maximum operating pressure
Degree of contamination: 2. NKF, model A: 10 bar.
Control voltage: 230 V/24 V. NKF, model B: 16 bar.
Nominal voltage: 230 VAC. However, to comply with VdS requirements, NKF pump heads
Battery charger power supply: 24 V. must not exceed 110 metres (11 bar).
Permanent charging voltage: 26.7 V.
4.5.9 Ambient temperature
Indication undervoltage: 24 V.
Minimum ambient temperature
Battery voltage: 24 V.
• +4 °C if the engine includes preheating.
Max. battery capacity: 400 Ah/200 Ah.
• +10 °C if the engine does not include preheating.
Battery type: CLT (Pb).
Maximum ambient temperature
Outputs
The maximum ambient temperature at the air filter inlet is +40 °C.
Common fault (indication is inverted)
Fuel monitoring 4.5.10 Relative air humidity
Sprinkler pump operation The relative air humidity must not be too high, to prevent
condensation of moisture in the air, as this can lead to damage of
Pressure switch triggered
the controller or the engine. If humidity is a problem, install a
Sprinkler pump deactivated space heater with a humidistat.
IF-message (message is inverted)
4.5.11 Effect of ambient temperature and altitude on engine
All outputs are twofold potential-free. output
If the ambient temperature exceeds +25 °C (fig. 11) or if the
4.5 Operating conditions
engine is installed more than 90 metres above sea level (fig. 12),
4.5.1 Minimum inlet pressure the engine must not be operated at full capacity. In these cases, it
The minimum inlet pressure must correspond to the NPSH curve may be necessary to use a larger engine.
at maximum permissible flow rate plus a safety margin of 1 metre.
The safety margin is specified in VdS CEA 4001: 2005-09 (02). P2
[%]
4.5.2 Maximum inlet pressure 100
The sum of actual inlet pressure plus pump pressure against a
closed valve must always be lower than the maximum 90
permissible operating pressure.
80
For the NKF series, the maximum permissible inlet pressure is
9 bar. For pumps with a nominal impeller diameter of 400 mm, the 70
maximum permissible inlet pressure is 7 bar.
4.5.3 Minimum flow rate 60
13
P2
[%]
100
90
80
70
60
50
hf
TM03 4717 2606
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[m]
Lf
0 2000 4000 6000 8000 10000 12000 14000 [ft]
5. Installation
Bf
The instructions of VdS must be followed.
5.1 Mounting
5.1.1 Installation site Fig. 13 Foundation
Place the pump unit in a dry, frost-free and well-ventilated Installation of pump unit
location.
Place the pump unit on the foundation and anchor it with
Warning adequately sized bolts. The entire base frame must be supported.
An adequate supply of air for engine combustion See figs 14 and 15. In addition, we recommend to fit vibration
must be ensured, and an adequate removal of dampers under the pump unit. See section 5.1.3 Vibration
heat and exhaust gases. dampening.
Non-compliance or impairment of the ventilation
or exhaust gas system may result in danger of
suffocation.
Allow sufficient clearance around pump and engine to enable
inspection, repair and assembly work.
5.1.2 Foundation
m pump × 1.5
h f = -----------------------------------------------
L f × B f × δ concrete
m pump × 5
h f = -----------------------------------------------
L f × B f × δ concrete
14
5.1.3 Vibration dampening 5.1.4 Pipework
To prevent vibrations from being transmitted to the building and
The pipework must not stress the pump housing
pipework, we recommend that you fit expansion joints and
or transfer any forces to the pump housing. Non-
vibration dampers. See fig. 16.
Caution compliance may damage the pump. Permitted
flange forces and torques. See section
Expansion joint 4.4.2 Pump.
The pipes must be of an adequate size, taking the pump inlet
pressure into consideration.
Install the pipes so that air locks are avoided, especially on the
suction side of the pump. See fig. 17.
Expansion joints
Expansion joints provide the following functions:
• Absorption of thermal expansion and contraction of pipework
caused by variations in liquid temperature. Fig. 17 Installation of pipes
• Reduction of mechanical influences in connection with
pressure surges in the pipework. Secure the pipes close to the pump on the suction and discharge
side with pipe brackets attached to the building (wall, ceiling,
• Isolation of structure-borne noise in the pipework (only rubber
floor). See fig. 18.
bellows expansion joints).
The pipes should lie true against the pump flanges without being
Do not fit expansion joints to make up for stressed. Otherwise, the pump may be damaged.
Caution inaccuracy in the pipework, e.g. centre
displacement or misalignment of flanges.
Fit the expansion joints both on the suction and the discharge
sides. The distance from the pump should be at least 1 - 1½ x DN
diameter. This prevents turbulence in the joints and ensures
optimum suction conditions and minimum pressure drop on the
discharge side.
At high water velocities (> 5 m/s), we recommend that you fit
larger expansion joints matching the pipework.
Vibration dampers
The selection of vibration damper differs from installation to 5.1.5 Fresh air supply
installation. A wrong damper may, in certain cases, increase the
vibration level. Vibration dampers should therefore be sized by
the supplier.
If the pump is installed on a foundation with vibration dampers, fit
expansion joints on both sides of the pump. This prevents the
pump from "hanging" from the flanges.
TM03 5501 3706
40
30
50
20
60
10
70
0
80
90
15
5.1.6 Exhaust gas system 5.1.9 Aligning pump and engine
A flexible coupling connects engine and pump. See fig. 21.
Warning
The exhaust gas system must be installed
correctly according to local regulations and must
have no leaks. Operation without exhaust gas
system is not permitted.
Exhaust gases are to be directed safely to the
open air through the exhaust system.
Exhaust fumes must not escape indoors.
Danger of suffocation!
Hot exhaust pipes must be protected to prevent
Z
Z
must not be smaller than the outlet on the heat exchanger.
The cooling circuit consists of the pipe system, a shut-off
cock (A), a diaphragm valve (B) and a pressure gauge (C).
See fig. 20.
In addition to the suction pipe of the pump, an extra pipe must be A careful alignment is important for a long
installed. This pipe prevents water from escaping out of the service life of the coupling. This is particularly
storage tank via the pump and the heat exchanger, when the Caution important with increased engine speed.
filling level in the storage tank is above the open discharge of the Follow the installation instructions of the
heat exchanger. The pressure on the suction side then ensures coupling manufacturer.
the closure of the diaphragm valve (fig. 20, pos. B). The shut-off
cock (fig. 20, pos. A) is closed during normal operation. It should Checking the alignment
only be opened if the diaphragm valve is faulty and remains in the
Warning
closed position. A diaphragm valve blocked in the closed position
is indicated by a lack of pressure on the pressure gauge (fig. 20, Before removing the coupling guard, disconnect
pos. C). the battery cable.
5.1.8 Vent tank and test pipe 1. Disconnect the battery (negative pole).
If the pump unit is supplied from a storage tank, a pump priming 2. Remove the coupling guard.
tank must be installed on the suction side, in accordance with the 3. Measure the distance "Z" at the rubber element of all axially
regional regulations, see VdS CEA guidelines for sprinkler bolted points. See fig. 22. The distance must be 50 mm. If the
systems. alignment is correct, proceed with step 4; otherwise align
A test pipe diverging from the pressure pipe and leading to the pump and engine. See next point.
storage tank must be installed. Both the pressure pipe and the 4. Refit the coupling guard.
test pipe must be fitted with isolating valves. If the pump unit is 5. Reconnect the battery.
fed directly from the public water supply, the test pipe must have
a free outlet, see VdS CEA guidelines for sprinkler systems.
16
Aligning pump and engine 5. Set the pressure values on the pressure switches.
1. Unscrew axial and radial bolts from the coupling and push See operating instructions of the pressure switch. The "system
shaft sleeve on the shaft in the direction of the pump. pressure - 0.5 bar" can be used as a standard value for
2. Loosen the screws of the pump base. settings.
3. Insert shims or foil sheets under the pump base. 6. Switch on the pump unit by switching the fuses F1, F4, F5, F8,
F9, F6 and F7 in the control cabinet (fig. 5 or fig. 7, pos. 26)
4. Retighten the screws of the pump base.
(position ON). Wait until the PLC is running and the indicator
5. Push shaft sleeve on the shaft in the direction of the engine light H4 "Processor on" is flashing.
and refasten axial and radial bolts. Always insert the axial
7. Open the fuel tap (fig. 5 or fig. 7, pos. 7).
bolts first. Bolts can be re-used a maximum of 3 times.
After that use new self-securing bolts. The bolts must never be 8. Open the isolating valve on the suction side of the pump.
Close the isolating valve on the discharge side of the pump.
fastened with threadlocker, as this can damage the rubber
Open the isolating valve to the test pipe.
compound.
9. Start the pump manually. See section 7.2 Manual operation.
6. Re-check the alignment.
If the engine does not start, check the error
Note messages and instructions on the display.
Other causes, see section 10. Fault finding chart.
10.Slowly open the isolating valve on the discharge side.
11.When the pump reaches operating pressure, open the
isolating valve sufficiently to reach the duty point.
12.Compare the oil pressure, temperature and speed with the
nominal values. See section 4.4.3 Engine.
13.Stop the pump manually. See section 7.2 Manual operation.
TM04 0058 4907 The pump unit is now operational and in automatic mode.
In connection with the start-up, a final test run must be carried
out, according to VdS. To do this, activate the automatic start-up
command by lowering the pressure in the discharge pipe with a
closed fuel tap. Every starting cycle consists of a 15-second
Fig. 23 Axial and radial fixation of the shaft sleeve
starting phase followed by a 15-second pause. After six failed
5.2 Electrical connection start attempts, a start failure warning must be activated. When
the fuel tap has been opened and the fault indication has been
removed by pressing the button S4, the pump should start
Warning
properly.
Before starting, check that the voltage specified
on the nameplate of the control cabinet
corresponds to the available mains voltage.
7. Operation
The electrical connection should only be carried 7.1 Automatic operation
out by qualified personnel in accordance with
Once the pump unit has been installed and started up according
local specifications and regulations.
to the instructions, no further preparation is necessary. The pump
• The connection to the mains supply must be fitted with a fuse unit works automatically and switches itself on according to use,
of the correct size, in accordance with the regional regulations, as soon as water is taken from the sprinkler system and the
and connected to the terminal block X1, terminals 1, 2 and 3 in pressure switch therefore detects a pressure drop.
the control cabinet. See wiring diagram.
The unit can be switched off via button S3. Emergency shut-down
• Connect both external pressure switches to the terminal block is possible by pulling the STOP-lever on the injection pump.
X11, terminals 3 and 4 and terminals 5 and 6 (see wiring See fig. 24. Alternatively, close the fuel tap on the tank.
diagram) in the control cabinet. See fig. 5 or fig. 7, pos. 7.
• Two blind motors can be connected to terminal block X4,
terminals 5 to 7 and terminals 8 to 9 in the control cabinet.
(See wiring diagram).
• For remote monitoring, specific signals can be channelled
through terminal block X16.
6. Start-up
Warning
Start-up may only be carried out by authorised
TM04 0114 5007
17
7.2 Manual operation 9.2.2 Lubrication of pump bearings
For a test run, servicing or temporary switching on or off of the The type of bearing and lubrication appears in the following table:
engine during start-up, the pump unit can be started manually by
pressing the buttons S1 "Fire pump on, starting unit 1" or S2 Pump Bearing Lubrication
"Fire pump on, starting unit 2". The engine is then stopped with
NKF 50-200
the button S3 "Fire pump off". NKF 65-200
For an emergency shut-down, pull the STOP-lever on the NKF 80-200 Maintenance-free, greased-
injection pump. See fig. 24. Alternatively, close the fuel tap on the 6306.2ZR.C3
NKF 80-250 for-life bearings.
tank. See fig. 5 or fig. 7, pos. 7. NKF 150-400
NKF 150-500
Regular test runs to ensure operation efficiency
Note should be limited to a maximum of 30 minutes To grease the bearings, use lithium-based grease according to
per week. these specifications:
• NLGI class 2 or 3.
8. Taking the pump out of operation • Viscosity of basic oil: 70 to 150 cSt at +40 °C.
Procedure
9.3 Routine engine checks
1. Close the isolating valve on the discharge side.
The following filling levels and components must be checked
2. Close the isolating valve on the suction side.
regularly:
3. Close the fuel tap (fig. 5 or fig. 7, pos. 7).
Oil level Once a week.
4. Switch off fuses F1, F4, F5, F8, F9, F6 and F7 in the control
Cooling system: Once a week.
cabinet (fig. 5 or fig. 7, pos. 26).
Fuel system: Once a week.
5. Disconnect the battery.
Exhaust gas system: Once a week.
If the pump is to be drained for a long period of inactivity, inject a
few drops of silicone oil on the shaft. This will prevent the shaft Air filter: Once a week.
seal faces from sticking. Turn the shaft by hand once a month. V-belt: Once a month.
To do this, loosen the coupling as described in section
9.3.1 Oil level
5.1.9 Aligning pump and engine.
During extended periods of inactivity, follow the measures listed JU4H JW6H
in section 3.3 Storage.
To re-start the pump unit, refill the engine oil and cooling liquid
and align the coupling. Then continue as described in section 29
6. Start-up.
9. Maintenance
The operator is responsible for ensuring that all
maintenance, inspection and installation work is
performed by qualified personnel. A regular
Note
Warning
Before starting work on the pump, make sure that Fig. 25 Arrangement of the oil dipstick
the pump unit has been switched off and cannot
be accidentally switched on. Maintenance work To read the oil level, pull out the oil dipstick (JU4H and JU6H) or
must only be performed by qualified personnel unscrew it (JW6H) (fig. 25, pos. 29). Oil level measurements are
authorised by VdS. to be taken when the engine is cold. The oil level must be
between the minimum and maximum mark on the oil dipstick.
9.1 Checking the function of the pump unit See figs 26 and 27.
A test run should be carried out once a week. For procedure,
TM04 0117 5007
18
9.3.2 Cooling system Filling the fuel
1. Examine all the pipes of the cooling system for leaks. 4
Replace defective pipes. 6
2. Check the level of cooling liquid in the heat exchanger.
When the engine is cold, the cooling liquid must reach the
lower end of the filling port (JU4H and JU6H), or the maximum
mark (JW6H), respectively. If the fill level of the cooling liquid
is too low, re-fill with cooling liquid. B
3. Check the level of cooling liquid in the equalisation tank.
5
When the engine is cold, the fill level must reach the mark
"Full Cold". If the fill level of the cooling liquid is too low, re-fill
put the tube from the upper connection port of the hand pump into
the tank opening. Operate the hand pump to fill the tank with fuel.
When the tank is full, take the tube out of the tank and close the
tank cap. Disconnect both tubes from the hand pump.
19
9.3.6 V-belt 9.5 Changing the fuel filter
Check the V-belt and belt pulleys for wear. In addition, check the The fuel filter should be changed once a year.
V-belt tension.
9.5.1 Changing the fuel filter, JU4H and JU6H
The V-belts must be stretched according to
Caution regulations, to ensure an optimal functioning of C
the pump and electric generator.
The V-belt elasticity midway between the two V-belt pulleys must
B
be 1 to 1,5 cm. See arrow in fig. 37. The V-belt tension can be
increased by loosening both generator fixing screws (fig. 37,
pos. A) and pushing the generator outwards (fig. 37, pos. B). 20
Then refasten the screws.
Worn V-belts must be replaced. See section 9.7 Replacing the
30 Warning
Fuel expelled under pressure can penetrate the
skin and cause serious injuries. The pressure
must therefore always be released before the fuel
pipes are disconnected. Only re-pressurize once
all the pipes have been tightened securely.
1. Loosen the ventilation port (fig. 32, pos. C) on the filter holder
and turn two turns by hand.
2. Operate the lever of the fuel suction pump (fig. 32, pos. 20)
until the emergent diesel fuel at the ventilation port does not
contain air bubbles. Collect the fuel in a suitable container and
dispose of it in an environmentally sound way.
3. Carefully tighten the ventilation port. Keep operating the lever
of the fuel suction pump until no resistance is felt. Then push
the handle as far as possible in the direction of the cylinder
block.
4. Start the engine by pressing button S1 on the control panel
and check for leaks. Then press button S3 to switch the
27 engine off again.
If the engine does not start, the fuel system may also need to be
TM04 0122 5007
20
5. Start the engine by pressing button S1 on the control panel Changing the secondary filter
and check for leaks. Then press button S3 to switch the 1. Close the fuel tap (fig. 7, pos. 7).
engine off again.
2. Unscrew the ventilation port (fig. 34, pos. C) on the side of the
filter holder and remove the plug (fig. 34, pos. D) to drain the
fuel from the filter. Collect the fuel in a suitable container and
A dispose of according to regulations.
3. Press the fuel filter (fig. 34, pos. 8.2) against the holder and
remove the upper and lower retaining clips. Then remove the
fuel filter from the guide rods of the filter holder.
4. Push the new filter onto the guide rods and press it firmly
against the holder. Then secure the retaining clips, first the
21
3. Tighten the connector. 9.7 Replacing the V-belt
4. Repeat steps 1 to 3 for all injection nozzles. The V-belt must be replaced once a year.
5. Start the engine by pressing button S1 on the control panel
and check for leaks. Then press button S3 to switch the
engine off again.
23
22
10. Fault finding chart
Warning
Before any servicing of the pump, make sure that the pump unit cannot accidentally start.
23
Fault Cause Remedy
8. Engine temperature a) Insufficient cooling liquid. Refill cooling liquid. See section 9.3.2 Cooling system.
too high. b) Diaphragm valve blocked or defective. Clean or replace diaphragm valve. As an emergency
measure, open shut-off fittings to the bypass pipe.
c) Heat exchanger defective. Replace heat exchanger.
9. Engine does not a) Incorrect speed setting. Please contact Grundfos.
reach nominal b) Fuel filter partially blocked. Change fuel filter. See section 9.5 Changing the fuel
speed. filter.
c) Air in fuel system. Vent fuel system.
d) Traces of water in the fuel. Drain condensate from the fuel filter. See section
9.3.3 Fuel system.
e) Turbocharger or charge air cooler defective Replace turbocharger and charge air cooler.
(not all models)
10. Battery voltage too a) Cell short in starter battery. Replace starter batteries.
low. b) Wiring of the battery charging circuit damaged Check wiring and replace if necessary. Check terminal
or insufficient terminal contact. connections and tighten if necessary.
c) Insufficient power supply to the control Check power supply.
cabinet.
d) V-belt tension too low. Check V-belt tension and correct if necessary.
e) Battery charging unit defective. Replace battery charging unit.
11. Strong exhaust gas a) Dirty air filter. Replace air filter.
colouring.
12. Warranty
The warranty is governed by the framework of our general terms
of delivery. Liability for any damage which is a result of errors
during installation, electrical connection or incorrect use, as well
as liability for consequential damage, is excluded. The start of the
warranty period is to be verified.
14. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
24
15. Appendix
15.1 Dimensions and weights
Cooling Fuel
Engine Air Exhaust Oil Oil
Engine output liquid tank
Pump type Engine type speed requirements volume amount pressure
amount volume
Subject to alterations.
25
Argentina Denmark Korea Singapore
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS DK A/S GRUNDFOS Pumps Korea Ltd. GRUNDFOS (Singapore) Pte. Ltd.
Ruta Panamericana km. 37.500 Lote Martin Bachs Vej 3 6th Floor, Aju Building 679-5 24 Tuas West Road
34A DK-8850 Bjerringbro Yeoksam-dong, Kangnam-ku, 135-916 Jurong Town
1619 - Garin Tlf.: +45-87 50 50 50 Seoul, Korea Singapore 638381
Pcia. de Buenos Aires Telefax: +45-87 50 51 51 Phone: +82-2-5317 600 Phone: +65-6865 1222
Phone: +54-3327 414 444 E-mail: info_GDK@grundfos.com Telefax: +82-2-5633 725 Telefax: +65-6861 8402
Telefax: +54-3327 411 111 www.grundfos.com/DK
Latvia Slovenia
Australia Estonia SIA GRUNDFOS Pumps Latvia GRUNDFOS PUMPEN VERTRIEB
GRUNDFOS Pumps Pty. Ltd. GRUNDFOS Pumps Eesti OÜ Deglava biznesa centrs Ges.m.b.H.,
P.O. Box 2040 Peterburi tee 92G Augusta Deglava ielā 60, LV-1035, Rīga, Podružnica Ljubljana
Regency Park 11415 Tallinn Tālr.: + 371 714 9640, 7 149 641 Šlandrova 8b, SI-1231 Ljubljana-Črnuče
South Australia 5942 Tel: + 372 606 1690 Fakss: + 371 914 9646 Phone: +386 1 568 0610
Phone: +61-8-8461-4611 Fax: + 372 606 1691 Telefax: +386 1 568 0619
Telefax: +61-8-8340 0155 Lithuania E-mail: slovenia@grundfos.si
Finland GRUNDFOS Pumps UAB
Austria OY GRUNDFOS Pumput AB Smolensko g. 6 Spain
GRUNDFOS Pumpen Vertrieb Mestarintie 11 LT-03201 Vilnius Bombas GRUNDFOS España S.A.
Ges.m.b.H. FIN-01730 Vantaa Tel: + 370 52 395 430 Camino de la Fuentecilla, s/n
Grundfosstraße 2 Phone: +358-3066 5650 Fax: + 370 52 395 431 E-28110 Algete (Madrid)
A-5082 Grödig/Salzburg Telefax: +358-3066 56550 Tel.: +34-91-848 8800
Tel.: +43-6246-883-0 Malaysia Telefax: +34-91-628 0465
Telefax: +43-6246-883-30 France GRUNDFOS Pumps Sdn. Bhd.
Pompes GRUNDFOS Distribution S.A. 7 Jalan Peguam U1/25 Sweden
Belgium Parc d’Activités de Chesnes Glenmarie Industrial Park GRUNDFOS AB
N.V. GRUNDFOS Bellux S.A. 57, rue de Malacombe 40150 Shah Alam Box 333 (Lunnagårdsgatan 6)
Boomsesteenweg 81-83 F-38290 St. Quentin Fallavier (Lyon) Selangor 431 24 Mölndal
B-2630 Aartselaar Tél.: +33-4 74 82 15 15 Phone: +60-3-5569 2922 Tel.: +46(0)771-32 23 00
Tél.: +32-3-870 7300 Télécopie: +33-4 74 94 10 51 Telefax: +60-3-5569 2866 Telefax: +46(0)31-331 94 60
Télécopie: +32-3-870 7301
Germany México Switzerland
Belorussia GRUNDFOS GMBH Bombas GRUNDFOS de México S.A. de GRUNDFOS Pumpen AG
Представительство ГРУНДФОС в Schlüterstr. 33 C.V. Bruggacherstrasse 10
Минске 40699 Erkrath Boulevard TLC No. 15 CH-8117 Fällanden/ZH
220123, Минск, Tel.: +49-(0) 211 929 69-0 Parque Industrial Stiva Aeropuerto Tel.: +41-1-806 8111
ул. В. Хоружей, 22, оф. 1105 Telefax: +49-(0) 211 929 69-3799 Apodaca, N.L. 66600 Telefax: +41-1-806 8115
Тел.: +(37517) 233 97 65, e-mail: infoservice@grundfos.de Phone: +52-81-8144 4000
Факс: +(37517) 233 97 69 Service in Deutschland: Telefax: +52-81-8144 4010 Taiwan
E-mail: grundfos_minsk@mail.ru e-mail: kundendienst@grundfos.de GRUNDFOS Pumps (Taiwan) Ltd.
Netherlands 7 Floor, 219 Min-Chuan Road
Bosnia/Herzegovina Greece GRUNDFOS Netherlands Taichung, Taiwan, R.O.C.
GRUNDFOS Sarajevo GRUNDFOS Hellas A.E.B.E. Veluwezoom 35 Phone: +886-4-2305 0868
Trg Heroja 16, 20th km. Athinon-Markopoulou Av. 1326 AE Almere Telefax: +886-4-2305 0878
BiH-71000 Sarajevo P.O. Box 71 Postbus 22015
Phone: +387 33 713 290 GR-19002 Peania 1302 CA ALMERE Thailand
Telefax: +387 33 659 079 Phone: +0030-210-66 83 400 Tel.: +31-88-478 6336 GRUNDFOS (Thailand) Ltd.
e-mail: grundfos@bih.net.ba Telefax: +0030-210-66 46 273 Telefax: +31-88-478 6332 92 Chaloem Phrakiat Rama 9 Road,
e-mail: info_gnl@grundfos.com Dokmai, Pravej, Bangkok 10250
Brazil Hong Kong Phone: +66-2-725 8999
Mark GRUNDFOS Ltda. GRUNDFOS Pumps (Hong Kong) Ltd. New Zealand Telefax: +66-2-725 8998
Av. Humberto de Alencar Castelo Unit 1, Ground floor GRUNDFOS Pumps NZ Ltd.
Branco, 630 Siu Wai Industrial Centre 17 Beatrice Tinsley Crescent Turkey
CEP 09850 - 300 29-33 Wing Hong Street & North Harbour Industrial Estate GRUNDFOS POMPA San. ve Tic. Ltd.
São Bernardo do Campo - SP 68 King Lam Street, Cheung Sha Wan Albany, Auckland Sti.
Phone: +55-11 4393 5533 Kowloon Phone: +64-9-415 3240 Gebze Organize Sanayi Bölgesi
Telefax: +55-11 4343 5015 Phone: +852-27861706 / 27861741 Telefax: +64-9-415 3250 Ihsan dede Caddesi,
Telefax: +852-27858664 2. yol 200. Sokak No. 204
Bulgaria Norway 41490 Gebze/ Kocaeli
GRUNDFOS Pumpen Vertrieb Hungary GRUNDFOS Pumper A/S Phone: +90 - 262-679 7979
Representative Office - Bulgaria GRUNDFOS Hungária Kft. Strømsveien 344 Telefax: +90 - 262-679 7905
Bulgaria, 1421 Sofia Park u. 8 Postboks 235, Leirdal E-mail: satis@grundfos.com
Lozenetz District H-2045 Törökbálint, N-1011 Oslo
105-107 Arsenalski blvd. Phone: +36-23 511 110 Tlf.: +47-22 90 47 00 Ukraine
Phone: +359 2963 3820, 2963 5653 Telefax: +36-23 511 111 Telefax: +47-22 32 21 50 ТОВ ГРУНДФОС УКРАЇНА
Telefax: +359 2963 1305 01010 Київ, Вул. Московська 8б,
India Poland Тел.:(+38 044) 390 40 50
Canada GRUNDFOS Pumps India Private Lim- GRUNDFOS Pompy Sp. z o.o. Фах.: (+38 044) 390 40 59
GRUNDFOS Canada Inc. ited ul. Klonowa 23 E-mail: ukraine@grundfos.com
2941 Brighton Road 118 Old Mahabalipuram Road Baranowo k. Poznania
Oakville, Ontario Thoraipakkam PL-62-081 Przeźmierowo United Arab Emirates
L6H 6C9 Chennai 600 096 Tel: (+48-61) 650 13 00 GRUNDFOS Gulf Distribution
Phone: +1-905 829 9533 Phone: +91-44 2496 6800 Fax: (+48-61) 650 13 50 P.O. Box 16768
Telefax: +1-905 829 9512 Jebel Ali Free Zone
Indonesia Portugal Dubai
China PT GRUNDFOS Pompa Bombas GRUNDFOS Portugal, S.A. Phone: +971-4- 8815 166
GRUNDFOS Pumps (Shanghai) Co. Ltd. Jl. Rawa Sumur III, Blok III / CC-1 Rua Calvet de Magalhães, 241 Telefax: +971-4-8815 136
51 Floor, Raffles City Kawasan Industri, Pulogadung Apartado 1079
No. 268 Xi Zang Road. (M) Jakarta 13930 P-2770-153 Paço de Arcos United Kingdom
Shanghai 200001 Phone: +62-21-460 6909 Tel.: +351-21-440 76 00 GRUNDFOS Pumps Ltd.
PRC Telefax: +62-21-460 6910 / 460 6901 Telefax: +351-21-440 76 90 Grovebury Road
Phone: +86-021-612 252 22 Leighton Buzzard/Beds. LU7 8TL
Telefax: +86-021-612 253 33 Ireland România Phone: +44-1525-850000
GRUNDFOS (Ireland) Ltd. GRUNDFOS Pompe România SRL Telefax: +44-1525-850011
Croatia Unit A, Merrywell Business Park Bd. Biruintei, nr 103
GRUNDFOS CROATIA d.o.o. Ballymount Road Lower Pantelimon county Ilfov U.S.A.
Cebini 37, Buzin Dublin 12 Phone: +40 21 200 4100 GRUNDFOS Pumps Corporation
HR-10010 Zagreb Phone: +353-1-4089 800 Telefax: +40 21 200 4101 17100 West 118th Terrace
Phone: +385 1 6595 400 Telefax: +353-1-4089 830 E-mail: romania@grundfos.ro Olathe, Kansas 66061
Telefax: +385 1 6595 499 Phone: +1-913-227-3400
www.grundfos.hr Italy Russia Telefax: +1-913-227-3500
GRUNDFOS Pompe Italia S.r.l. ООО Грундфос
Czech Republic Via Gran Sasso 4 Россия, 109544 Москва, ул. Школьная Usbekistan
GRUNDFOS s.r.o. I-20060 Truccazzano (Milano) 39 Представительство ГРУНДФОС в
Čajkovského 21 Tel.: +39-02-95838112 Тел. (+7) 495 737 30 00, 564 88 00 Ташкенте
779 00 Olomouc Telefax: +39-02-95309290 / 95838461 Факс (+7) 495 737 75 36, 564 88 11 700000 Ташкент ул.Усмана Носира 1-й
Phone: +420-585-716 111 E-mail тупик 5
Telefax: +420-585-716 299 Japan grundfos.moscow@grundfos.com Телефон: (3712) 55-68-15
GRUNDFOS Pumps K.K. Факс: (3712) 53-36-35
Gotanda Metalion Bldg., 5F, Serbia
5-21-15, Higashi-gotanda GRUNDFOS Predstavništvo Beograd
Shiagawa-ku, Tokyo Dr. Milutina Ivkovića 2a/29
141-0022 Japan YU-11000 Beograd
Phone: +81 35 448 1391 Phone: +381 11 26 47 877 / 11 26 47
Telefax: +81 35 448 9619 496
Telefax: +381 11 26 48 340
96809328 0909
292 The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks
Repl. 96809328 0908 owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
www.grundfos.com