Brief Project Report

Scheme No: C21-21 Description: Approval, Inspection, Commissioning and Handover of the Electrical Reticulation for Challenge
Engineering Pte Limited's Subdivision at Natabua, Lautoka
Application Detail
Application Received 04/01/2021 Contact Person: Krishneel Reddy

Site Assessment
Distance from Base 2.5km RT Effective YES
Accessible Route YES
Vegetation Type To be cleared by developer Ground Condition CLAY SOIL

Technical Assessment
Maximum Demand 710.175kVA Number & Size of Transformer Required 2X500kVA
EOL Voltage Reading 10.98kV Feeder & Zone Substation Pineapple Corner/Natabua
Type of Conductor Helium Conductor HV Route Length 396m
No. of Poles Required 1x 11m RC Pole LV Route Length 1861.84m
Adequate Ground Clearance YES Nearest Transformer Number T4214

Other Utility Check


Telecom cable affected YES-To be confirmed by developer Road Corridor access required YES-To be confirmed by developer
Water mains affected YES-To be confirmed by developer Road Reserve Reinstatement YES-To be done by developer
Consumer Service mains affected NO

Design Technician Ronish Chandra Signature Date 9/08/2021

Cost Breakdown

Material $8,861.48
Labour $17,865.82
Cartage $240.00

Sub- Total (VEP) $26,967.30

Design, Management & Construction Cost $9,219.53

Project Capital Cost (VEP) $36,186.83


100 % Project Cost (VIP) $39,443.64

Checked By

Kaushal Maharaj Mohammed Zainal Alim(EEDP)


(TLDP)

Approved By

Basant Kumar (MNDP)