Professional Documents
Culture Documents
Spring 2021
ASSIGNMENT 3
Design a 630 kVA distribution transformer.
Prepared By:
Shahzaib Ahmad Qureshi: F2016019065
Electric Machine Design F2016019065
Assignment#2
It is desired to design a 630 kVA distribution transformer having the input data
shown in Tables 2.6 to 2.12. If the rated line voltage of the LV winding is 200 V,
calculate the following
Volts per turn .
VLv 200
VpLv = = = 115.47V
√3 √3
VpLv
VPT = =115.47V/15 = 7.698V
TurnsLv
𝑉𝑃𝑇 7.698𝑉
𝐸𝑢 = = = 48𝑚𝑚
8.88 . 𝐶𝑆𝐹 . 𝐷. 𝐹𝐷𝑚𝑎𝑥 . 𝑓 8.88 . 0.965 . 220 .17000 . 50
No of Layers LV winding
LayersLV=Turns mainLV=15
Electric Machine Design F2016019065
Width of LV Layer
𝑇𝐷𝐿𝑉 = 𝐺 − 2 . 𝐶𝐶𝐸𝐸 . −2 . 𝐷𝐿𝑉 − 𝐶 = 261 − 2 𝑋 3 − 2 𝑋 6.5 = 242𝑚𝑚
Width of LV Conductor
𝑇𝑢𝑟𝑛 𝑤𝑖𝑑𝑡ℎ𝐿𝑉 = 𝑇𝐷𝐿𝑉 = 𝑇𝑢𝑟𝑛 𝑤𝑖𝑑𝑡ℎ 𝐿𝑉 = 242𝑚𝑚
Thickness of LV winding
𝐿𝑎𝑦𝑒𝑟𝑠𝐿𝑉
𝐵𝐿𝐷𝐿𝑉 = (𝑡𝐿𝑉 + 𝐼𝐿𝑉𝐿) 𝑋 =(0.79+0.28) x 15/0.909=17.66mm
𝐿𝐷𝑆𝑃𝐿𝑉