11

PVsyst - Simulation report


Grid-Connected System

Project: sanlucar la mayor


Variant: Nueva variante de simulación
Tracking system
System power: 228.3 MWp
Villarán - España

Author
Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Project summary
Geographical Site Situation Project settings
Villarán Latitude 37.45 °N Albedo 0.20
España Longitude -6.27 °W
Altitude 80 m
Time zone UTC+1

Meteo data
Villarán
PVGIS api TMY

System summary
Grid-Connected System Tracking system

PV Field Orientation Near Shadings


Orientation Tracking algorithm Linear shadings
Tracking plane, tilted axis Astronomic calculation
Avg axis tilt 1.1 °
Avg axis azim. 0.0 °

System information
PV Array Inverters
Nb. of modules 351189 units Nb. of units 587 units
Pnom total 228.3 MWp Pnom total 176.1 MWac
Pnom ratio 1.296

User's needs
Unlimited load (grid)

Results summary
Produced Energy 465 GWh/year Specific production 2037 kWh/kWp/year Perf. Ratio PR 79.13 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 5
Main results 6
Loss diagram 7
Special graphs 8

03/04/24 PVsyst Licensed to Page 2/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

General parameters
Grid-Connected System Tracking system

PV Field Orientation
Orientation Tracking algorithm Trackers configuration
Tracking plane, tilted axis Astronomic calculation Nb. of trackers 12060 units
Avg axis tilt 1.1 ° Sizes
Avg axis azim. 0.0 ° Tracker Spacing 6.00 m
Collector width 2.40 m
Ground Cov. Ratio (GCR) 40.0 %
Phi min / max. -/+ 55.0 °
Shading limit angles
Phi limits +/- 66.2 °
Models used
Transposition Perez
Diffuse Imported
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon Linear shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer CSI Solar Co., Ltd. Manufacturer Huawei Technologies
Model CS7N-650MS 1500V Model SUN2000-330KTL-H1
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 650 Wp Unit Nom. Power 300 kWac
Number of PV modules 351189 units Number of inverters 587 units
Nominal (STC) 228.3 MWp Total power 176100 kWac
Modules 13007 Strings x 27 In series Operating voltage 500-1500 V
At operating cond. (50°C) Max. power (=>25°C) 330 kWac
Pmpp 209.1 MWp Pnom ratio (DC:AC) 1.30
U mpp 913 V
I mpp 229121 A

Total PV power Total inverter power


Nominal (STC) 228273 kWp Total power 176100 kWac
Total 351189 modules Number of inverters 587 units
Module area 1090917 m² Pnom ratio 1.30

Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 0.066 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Serie Diode Loss Module Quality Loss Module mismatch losses


Voltage drop 0.7 V Loss Fraction -0.4 % Loss Fraction 2.0 % at MPP
Loss Fraction 0.1 % at STC

Strings Mismatch loss


Loss Fraction 0.1 %

03/04/24 PVsyst Licensed to Page 3/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Array losses
IAM loss factor
Incidence effect (IAM): User defined profile

10° 20° 30° 40° 50° 60° 70° 80° 90°


0.998 0.998 0.995 0.992 0.986 0.970 0.917 0.763 0.000

AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 800 Vac tri
Loss Fraction 0.00 % at STC
Inverter: SUN2000-330KTL-H1
Wire section (587 Inv.) Copper 587 x 3 x 120 mm²
Average wires length 0m

MV line up to Injection
MV Voltage 20 kV
Wires Alu 3 x 10000 mm²
Length 2000 m
Loss Fraction 0.34 % at STC

AC losses in transformers
MV transfo
Grid voltage 20 kV
Operating losses at STC
Nominal power at STC 217582 kVA
Iron loss (24/24 Connexion) 217.58 kW
Loss Fraction 0.10 % at STC
Coils equivalent resistance 3 x 0.03 mΩ
Loss Fraction 1.00 % at STC

03/04/24 PVsyst Licensed to Page 4/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Near shadings parameter


Perspective of the PV-field and surrounding shading scene

Iso-shadings diagram
Orientation #1

03/04/24 PVsyst Licensed to Page 5/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Main results
System Production
Produced Energy 465 GWh/year Specific production 2037 kWh/kWp/year
Performance Ratio PR 79.13 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² GWh GWh ratio
January 81.2 27.75 10.50 124.1 108.1 24.12 22.83 0.806
February 87.2 38.26 11.94 124.0 110.8 24.48 23.16 0.818
March 109.0 52.12 13.23 147.2 133.7 29.13 27.42 0.816
April 179.5 64.08 17.24 242.6 223.0 47.01 44.59 0.805
May 190.8 74.36 19.68 254.7 234.5 48.81 46.28 0.796
June 245.7 61.12 24.63 336.6 311.4 62.91 59.82 0.779
July 258.2 54.96 26.82 361.1 333.2 66.45 63.21 0.767
August 221.0 50.51 26.23 312.3 287.4 57.94 55.10 0.773
September 163.9 51.55 24.02 227.4 208.8 42.96 40.85 0.787
October 134.1 38.32 19.45 196.6 177.4 37.66 35.79 0.797
November 94.9 31.49 13.69 139.9 125.3 27.56 26.24 0.822
December 70.2 27.34 11.11 108.0 93.3 20.88 19.76 0.802
Year 1835.6 571.87 18.24 2574.6 2346.9 489.90 465.06 0.791

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

03/04/24 PVsyst Licensed to Page 6/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Loss diagram
1836 kWh/m² Global horizontal irradiation
+40.3% Global incident in coll. plane

-6.21% Near Shadings: irradiance loss

-0.82% IAM factor on global

-2.00% Soiling loss factor

2347 kWh/m² * 1090917 m² coll. Effective irradiation on collectors

efficiency at STC = 21.01% PV conversion

538016 MWh Array nominal energy (at STC effic.)


+0.08% PV loss due to irradiance level

-6.12% PV loss due to temperature

+0.37% Module quality loss

-2.10% Mismatch loss, modules and strings

-1.26% Ohmic wiring loss


490476 MWh Array virtual energy at MPP

-3.81% Inverter Loss during operation (efficiency)

-0.12% Inverter Loss over nominal inv. power


0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
471199 MWh Available Energy at Inverter Output

0.00% AC ohmic loss


-1.07% Medium voltage transfo loss
-0.23% MV line ohmic loss
465055 MWh Energy injected into grid

03/04/24 PVsyst Licensed to Page 7/8


Project: sanlucar la mayor
Variant: Nueva variante de simulación

PVsyst V7.2.11
VC0, Simulation date:
03/04/24 14:35
with v7.2.11

Special graphs
Diagrama entrada/salida diaria

Distribución de potencia de salida del sistema

03/04/24 PVsyst Licensed to Page 8/8