Battery Sizing Calculation As per IEEE Std 485-1997

Nominal Voltage 24 Volts


Minimum Voltage 21.6 Volts
Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818181818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs

MAIN HT PANEL

S.NO DESCRIPTION LOAD IN INCOMER


WATTS FEEDER QTY

Breakers Quantity 1

1 Relays
O\C & E\F Relay 0
Trip Circuit Supervision Relay 3 3
Sensitive E\F Relay 5 5
Master Tripping Relay 5 5

2 Indications
Annunciator 9 window 13.5 6.75
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0.5
Trip Circuit Healthy 0.5 0.5

3 Energising Coils
VCB Tripping Coil 5 5
VCB Closing Coil 5 5
DC operrated Motor

Total load in Watts


Load Current

LOAD NAME TIME IN MIN LOAD IN AMPS


A1 1 12.5416666666667
A2 119 12.4166666666667
A3 480 4.08333333333333

1 2 3
Period Load in Amps Change in Load
(Amps)

Section-1
1 12.5416666666667 12.5416666666667

Section-2
1 12.5416666666667 12.5416666666667
2 12.4166666666667 -0.125

Section-3
1 12.5416666666667 12.5416666666667
2 12.4166666666667 -0.125
3 4.08333333333333 -8.33333333333334

Uncorrected cell size


Corrected cell size
Ah rating for the battery selected asper
catolouge
Charger rating
ulation As per IEEE Std 485-1997

EDITABLE DATA

NON EDITABLE DATA

AIN HT PANEL

BUS OUTGOIN CONTINUOUS MOMENTARY EMERGENCY


COUPLER G FEEDER LOAD LOAD LOAD
QTY QTY

0 6

0 0 0
0 18 21
0 30 35
0 30 35

27 3
0 3 3.5
3 3.5

0 30 180
0 30
200

98 200 3
4.08333333333333 8.3333333333333 0.125

4 5 6 7
Duration of Time to end Capacity at T Reqd sec size
period(mins) of section minute rate K =3*6 AH
(min) factor

1 1.00 0.79
Section-1 Sub total 9.9079166666667

1 120.00 2.8 35.116666666667


119 119.00 2.8 -0.35
Section-2 Sub Total 34.766666666667

1 600.00 10.20 127.925


119 599.00 10.20 -1.275
480 480.00 8.300 -69.166666666667
Section-3 Sub Total 57.483333333333
57.483333333333
79.039583333333

120
8.8541666666667
Battery Sizing Calculation As per IEEE Std 485-1997

Nominal Voltage 24 Volts


Minimum Voltage 21.6 Volts
Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818181818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs

MAIN HT PANEL

S.NO DESCRIPTION LOAD IN INCOMER


WATTS FEEDER QTY

Breakers Quantity 0

1 Relays
O\C & E\F Relay 0 0
Trip Circuit Supervision Relay 3 0
Sensitive E\F Relay 5 0
Master Tripping Relay 5 0

2 Indications
Annunciator 9 window 13.5 0
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0
Trip Circuit Healthy 0.5 0

3 Energising Coils
VCB Tripping Coil 5 0
VCB Closing Coil 5 0
DC operrated Motor

Total load in Watts


Load Current

LOAD NAME TIME IN MIN LOAD IN AMPS


A1 1 9.625
A2 119 9.5
A3 480 1.16666666666667

1 2 3
Period Load in Amps Change in Load
(Amps)

Section-1
1 9.625 9.625

Section-2
1 9.625 9.625
2 9.5 -0.125

Section-3
1 9.625 9.625
2 9.5 -0.125
3 1.16666666666667 -8.33333333333333

Uncorrected cell size


Corrected cell size
Ah rating for the battery selected asper
catolouge
Charger rating
ulation As per IEEE Std 485-1997

EDITABLE DATA

NON EDITABLE DATA

AIN HT PANEL

BUS OUTGOIN CONTINUOUS MOMENTARY EMERGENCY


COUPLER G FEEDER LOAD LOAD LOAD
QTY QTY

0 2

0 0 0
0 6 6
0 10 10
0 10 10

9 3
0 1 1
1 1

0 10 180
0 10
200

28 200 3
1.16666666666667 8.3333333333333 0.125

4 5 6 7
Duration of Time to end Capacity at T Reqd sec size
period(mins) of section minute rate K =3*6 AH
(min) factor

1 1.00 0.79
Section-1 Sub total 7.60375

1 120.00 2.65 25.50625


119 119.00 2.63 -0.32875
Section-2 Sub Total 25.1775

1 600.00 10.20 98.175


119 599.00 10.20 -1.275
480 480.00 8.300 -69.166666666667
Section-3 Sub Total 27.733333333333
27.733333333333
38.133333333333

120
4.4583333333333
CABLE USED 2Cx35SQMM COPPER XLPE ARMOURED POWER CABLE

From To load current Distance(kM) Resistane/kM Drop %drop


HT ROOM SDB-1 9.17 0.18 0.524 1.72983 7.20762
HT ROOM SDB-2 9.17 0.26 0.524 2.49864 0.1041100667
Voltage at terminal
22.2701712
21.5013584 2.5
Battery Sizing Calculation As per IEEE Std 485-1997

Nominal Voltage 24 Volts


Minimum Voltage 21.6 Volts
Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818181818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs

MAIN HT PANEL

S.NO DESCRIPTION LOAD IN INCOMER


WATTS FEEDER QTY

Breakers Quantity 0

1 Relays
O\C & E\F Relay 0 0
Trip Circuit Supervision Relay 3 0
Sensitive E\F Relay 5 0
Master Tripping Relay 9 0

2 Indications
Annunciator 9 window 13.5 0
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0
Trip Circuit Healthy 0.5 0

3 Energising Coils
VCB Tripping Coil 5 0
VCB Closing Coil 5 0
DC operrated Motor

Total load in Watts


Load Current

LOAD NAME TIME IN MIN LOAD IN AMPS


A1 1 9.17708333333333
A2 119 9.08333333333333
A3 480 0.75
ulation As per IEEE Std 485-1997

EDITABLE DATA

NON EDITABLE DATA

AIN HT PANEL

BUS OUTGOIN CONTINUOUS MOMENTARY EMERGENCY


COUPLER G FEEDER LOAD LOAD LOAD
QTY QTY

0 1

0 0 0
0 3 3
0 5 5
0 9 9

4.5 2.25
0 0.5 0.5
0.5 0.5

0 5
0 5
200

18 200 2.25
0.75 8.3333333333333 0.09375