AC Generator Protection Schedule
AC Generator Protection Schedule
FCP
Petrochina (Halfaya)
Customer Reference :
Checked A.Polakowski
Document Number:
RELAY Siprotec 7UM62
NW0244/G05/001
SOFTWARE DIGSI v4.82
This document contains confidential and proprietary information of Siemens Industrial Turbomachinery Ltd.
(the Company). It must not be used for purposes other than that for which it is issued by the Company and
information contained must not be copied nor disclosed in any way, wholly or in part, without prior written
authority of the Company. © Siemens Industrial Turbomachinery Ltd. Copyright ©
2009
27 Under Voltage 4
32 R Reverse Power 6
40 Field Failure 8
46 Negative Phase Sequence 11
51 V Inverse-Time Overcurrent 14
51 GN Sensitive Earth Fault 16
59 Over Voltage 18
67 N Directional Earth Fault 20
81 Frequency Protection 22
87 G Generator Differential 25
Notes :
The recommended settings given in this document are for information only.
Final settings should be carried out during comissioning in consultation with the
Electrical Applications Department.
Primary Secondary
Differential : 600 1 A SLD
Protection : 600 1 A SLD
Earth Fault : 100 1 A SLD
Primary Secondary
Protection : 11000 110 V SLD
Resistor
Rating : 100 A SLD
Time 10 s SLD
Purpose
Voltage Setting
Secondary Vn 110 V
Percent 75 %
V< 82.5 V
Time Delay
t 3s
Voltage Setting
Secondary Vn 110 V
Percent 65 %
V<< 71.5 V
Time Delay
t 0.5 s
Voltage U<
U<<
Time
Diagram of the relay's settings
Purpose
Note :
The maximum reverse power rating of the generator is approximately 30%, however
the relay should be set so as to trip in the event of shear pin failure. In which case
the generator would only draw approximately 1.2 % of it's power rating as no-load
losses.
This is then referred to the secondary side of the VTs and CTs using the formula:
PNo−load _ Loss U Machine I
Setting = * * Machine
PMachine U VT _ Pr imary I CT _ Ratio
Power Setting P> REVERSE Trip
t 3s
Purpose
This function protects against a loss of power to the exciter
creating the electric fields within the generator.
Characteristics
Primary Xd 2.06 pu
1 1 I VTprim
Primary 1/Xd 0.485 pu = x n x
Xd sec Xd prim Vn CTprim
Secondary 1/Xd 0.44 pu
Characteristic Settings
Char 1 Warning
Char 1 0.464
Char 2 Warning
Char 2 is 90 % of Char 1
Char 3 Trip
Xd 2.06 pu
X'd 0.273 pu
Char 3 1.1
Angular Settings
Time Settings
(Underexcitation)
Address Parameter Value Unit
3001 UNDEREXCIT. On
3011 T SHRT Uex< 0.05 s
3012 EXCIT. VOLT. Off
3013 Excitation Voltage Superv.2.00
Pickup
V
(Characteristics)
Address Parameter Value Unit
3002 1/xd CHAR. 1 0.46
3003 ANGLE 1 70 °
3004 T CHAR. 1 10 s
3005 1/xd CHAR. 2 0.417
3006 ANGLE 2 90 °
3007 T CHAR. 2 10 s
3008 1/xd CHAR. 3 1.1
3009 ANGLE 3 90 °
3010 T CHAR. 3 0.5 s
Purpose
I2 perm 8%
IN
I 2 > = I 2 perm ×
CT ratio
I2> 7.3 %
I2>> 60 %
Time delay 3s
Settings
2
I rated
Ksec = Kprim ×
CT Primary
Primary K 20 s
Secondary K 19.37 s
Tcooldown 3125 s
K
T Cooldown = 2
I 2 perm
IN
(Unbalanced Load)
Address Parameter Value Unit
1701 UNBALANCED LOAD On
1702 I2> 7.3 %
1703 T WARN 19 s
1704 FACTOR K 19.37 s
1705 T COOL DOWN 3125 s
1706 I2>> 60 %
1707 T I2> 3s
Purpose
This function protects against a dangerously high current.
110%
Iflc
25%
Vn
(Overcurrent Protection)
Address Parameter Value Unit
1401 O/C Ip On
1402 Ip 0.98 A
1403 T Ip 0.4 s
1405 IEC CURVE Normal
1407 VOLT. INFLUENCE Voltage Restrained
Purpose
Fault Current
If Fault Current
NER rating
Primary If 100 A If =
Secondary If 1A CTratio
Percent 10 % of Secondary If
IEE> 100 mA
Time delay
T IEE> 5 seconds
Percent 80 % of Secondary If
IEE> 800 mA
Time delay
T IEE> 0.5 seconds
IEE<
This function can be applied as a Rotor Earth Fault
This item is not typically used (IEE< = 0)
Current IEE>>
IEE>
Time
Diagram of the relay's settings
Purpose
This function protects against high voltages.
Vn 110 V
Percent 110 %
U> 121 V
Time delay
t 3s
Vn 110 V
Percent 120 %
U>> 132 V
Time delay
t 0.5 s
U>>
U>
Voltage
Time
Purpose
This function monitors the earth fault currents as well as the neutral voltage
displacement in order to determine whether the fault is a machine fault or
a network fault.
Recommended
3I0> 8 mA
Secondary Vn 110 V
Recommended at 10% 10 %
U0> 11 V
Angle
Angle 15 degrees
Time delay
Siemens recommendation is that a 60/1 A core balance CT is used for this application.
Regardless of core balance CT used, ensure a sensitive input to address 5003 as
recommended above. Site commissioning will determine whether this is overly sensitive.
Purpose
Nominal Frequency 50 Hz
Frequency 1 f1 Alarm
Percent -5 %
95 %
f1 47.5 Hz
Time delay
t 3s
Frequency 2 f2 Trip
Percent -8 %
92 %
f1 46 Hz
Time delay
t 1s
Frequency 3 f3 Alarm
Percent 5%
105 %
f1 52.5 Hz
Time delay
t 3s
Frequency 4 f4 Trip
Percent 8%
108 %
f1 54 Hz
Time delay
t 1s
Percent 65 %
Umin 71.5 V
f4 Trip
Frequency
f3 Alarm
Nominal Frequency
f1 Alarm
f2 Trip
Purpose
Current settings
I-DIFF> Trip
A setting between 10-20% of Idiff / In is
recommended for generators.
I-DIFF> 0.1
I-DIFF>> Trip
A setting 10% above the steady state transient
short circuit current is recommended.
Choose a value greater than 4.03 and between 3 and 7.
I-DIFF>> 4.1 1
I - DIFF >> > IN
Graph settings X 'd
Stabilization
Idiff / In
Slope 2
I-DIFF>>