PVsyst - Simulation report


Stand alone system

PVsyst TRIAL
Project: Moyobamba 1
Variant: Nueva variante de simulación
Stand alone system with batteries
System power: 2080 Wp
Moyobamba - Peru

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL Author


Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

Project summary
Geographical Site Situation Project settings
Moyobamba Latitude -6.04 °S Albedo 0.20
Peru Longitude -76.99 °W
Altitude 864 m

PVsyst TRIAL
Time zone UTC-5

Meteo data
Moyobamba
Meteonorm 7.3, Sat=100% - Sintético

System summary
Stand alone system Stand alone system with batteries

PV Field Orientation User's needs


Seasonal tilt adjustment Daily household consumers
azimuth 0° Constant over the year
Summer Tilt 20 ° Average 48 kWh/Day
winter 50 °
Apr.-May-June-July-Aug.-Sep.-

PVsyst TRIAL
System information
PV Array
Nb. of modules
Pnom total
8 units
2080 Wp
Battery pack
Technology
Nb. of units
Voltage
Capacity
Lead-acid, vented, plates
4 units
24 V
200 Ah

Results summary
Available Energy 3359 kWh/year Specific production 1615 kWh/kWp/year Perf. Ratio PR 143.46 %
Used Energy 5834 kWh/year Solar Fraction SF 33.28 %

Table of contents

PVsyst TRIAL
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Detailed User's needs 4
Main results 5
Loss diagram 6
Special graphs 7

PVsyst TRIAL
24/01/21 PVsyst Evaluation mode Page 2/7
Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

General parameters
Stand alone system Stand alone system with batteries

PV Field Orientation User's needs


Orientation Models used Daily household consumers

PVsyst TRIAL
Seasonal tilt adjustment Transposition Perez Constant over the year
azimuth 0° Diffuse Perez, Meteonorm Average 48 kWh/Day
Summer Tilt 20 ° Circumsolar separate
winter 50 °
Apr.-May-June-July-Aug.-Sep.-

PV Array Characteristics
PV module Battery
Manufacturer Generic Manufacturer Generic
Model AS-P603-260 Model Open 12V / 100 Ah
(Original PVsyst database) Technology Lead-acid, vented, plates
Unit Nom. Power 260 Wp Nb. of units 2 in parallel x 2 in series
Number of PV modules 8 units Discharging min. SOC 20.0 %
Nominal (STC) 2080 Wp Stored energy 3.8 kWh

PVsyst TRIAL
Modules 1 String x 8 In series Battery Pack Characteristics
At operating cond. (50°C) Voltage 24 V
Pmpp 1873 Wp Nominal Capacity 200 Ah (C10)
U mpp 221 V Temperature Fixed 20 °C
I mpp 8.5 A

Controller Battery Management control


Universal controller Threshold commands as SOC calculation
Technology MPPT converter Charging SOC = 0.92 / 0.75
Temp coeff. -5.0 mV/°C/Elem approx. 27.7 / 24.8 V
Converter Discharging SOC = 0.20 / 0.45
Maxi and EURO efficiencies 97.0 / 95.0 % approx. 21.0 / 24.1 V

Total PV power
Nominal (STC) 2 kWp

PVsyst TRIAL
Total 8 modules
Module area 13.0 m²

Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 438 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.3 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module Quality Loss Module mismatch losses Strings Mismatch loss


Loss Fraction -0.5 % Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %

IAM loss factor


Incidence effect (IAM): Fresnel AR coating, n(glass)=1.526, n(AR)=1.290

PVsyst TRIAL
0° 30° 50° 60° 70° 75° 80° 85° 90°
1.000 0.999 0.987 0.962 0.892 0.816 0.681 0.440 0.000

24/01/21 PVsyst Evaluation mode Page 3/7


Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

Detailed User's needs


Daily household consumers, Constant over the year, average = 48 kWh/day
Annual values Hourly distribution

Number Power Use Energy

PVsyst TRIAL
W Hour/day Wh/day
Motobomba 4 2400W/app 5.0 48000
Consumidores en espera 24.0 24
Total daily energy 48024Wh/day

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
24/01/21 PVsyst Evaluation mode Page 4/7
Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

Main results
System Production
Available Energy 3359 kWh/year Specific production 1615 kWh/kWp/year
Used Energy 5834 kWh/year Performance Ratio PR 143.46 %
Excess (unused) 2 kWh/year Solar Fraction SF 33.28 %

PVsyst TRIAL
Loss of Load Battery aging (State of Wear)
Time Fraction 83.0 % Cycles SOW 90.8 %
Missing Energy 11695 kWh/year Static SOW 90.0 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL Balances and main results

GlobHor GlobEff E_Avail EUnused E_Miss E_User E_Load SolFrac


kWh/m² kWh/m² kWh kWh kWh kWh kWh ratio
January 166.8 140.4 246.0 0.018 1046 442.8 1489 0.297
February 148.8 132.5 230.4 0.009 932 412.8 1345 0.307
March 168.2 159.8 273.5 2.048 1024 465.0 1489 0.312
April 169.7 156.3 275.2 0.000 935 506.1 1441 0.351

PVsyst TRIAL
May 172.1 185.6 323.6 0.000 951 538.0 1489 0.361
June 158.8 183.8 322.1 0.009 918 522.4 1441 0.363
July 165.1 188.6 333.0 0.000 950 538.7 1489 0.362
August 175.7 175.5 311.9 0.000 977 512.2 1489 0.344
September 178.1 144.5 260.3 0.000 956 484.7 1441 0.336
October 176.0 161.0 283.7 0.009 990 498.8 1489 0.335
November 165.6 140.3 250.2 0.000 992 449.1 1441 0.312
December 173.5 140.8 249.0 0.000 1026 463.2 1489 0.311
Year 2018.5 1908.9 3359.0 2.092 11695 5833.8 17529 0.333

Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)

PVsyst TRIAL
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy

24/01/21 PVsyst Evaluation mode Page 5/7


Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

Loss diagram
2018 kWh/m² Global horizontal irradiation

-3.14% Global incident in coll. plane

PVsyst TRIAL
-2.36% IAM factor on global

1909 kWh/m² * 13 m² coll. Effective irradiation on collectors

efficiency at STC = 16.04% PV conversion

3984 kWh Array nominal energy (at STC effic.)


-0.48% PV loss due to irradiance level

-8.82% PV loss due to temperature

+0.50% Module quality loss

-2.10% Mismatch loss, modules and strings

-1.38% Ohmic wiring loss

PVsyst TRIAL 3505 kWh


-0.06%

-4.20%

-0.04%
Unused energy (battery full)
Effective energy at the output of the array

Converter Loss during operation (efficiency)

Converter Loss due to power threshold


0.00% Converter Loss over nominal conv. voltage
Missing energy 0.00% Converter Loss due to voltage threshold
66.72% 3357 kWh Converter losses (effic, overload)
Direct use Stored Battery Storage
19.4% 80.6%
-0.10% Battery Stored Energy balance

PVsyst TRIAL +96.15% Battery efficiency loss

-1.16% Charge/Disch. Current Efficiency Loss

0.00% Gassing Current (electrolyte dissociation)


-0.02% Battery Self-discharge Current

PVsyst TRIAL
11695 kWh 5834 kWh

17529 kWh
Energy supplied to the user

Energy need of the user (Load)

24/01/21 PVsyst Evaluation mode Page 6/7


Project: Moyobamba 1
Variant: Nueva variante de simulación

PVsyst V7.1.2
VC0, Simulation date:
24/01/21 01:47
with v7.1.2

Special graphs
Diagrama entrada/salida diaria

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
24/01/21 PVsyst Evaluation mode Page 7/7