SWITCHBOARD COMPONENTS

The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 1 of 27 of C.05 19 September 2007
SWITCHBOARD COMPONENTS CC CU KIN TRONG T IN
1 GENERAL 1 TNG QUAN
1.1 FUNCTIONAL DESCRIPTION 1.1 M T
Switchboards components cover the
scope of components for all electrical
switchboards, sub distribution boards.
Phm vi cc cu kin trong t in bao
gm cc cu kin cho tt c cc t in,
cc t phn phi ph.
1.2 CROSS REFERENCES 1.2 THAM CHIU CHO
General
Comply with the General requirements
worksection.
Tng qut
Ph hp vi chng Nhng yu cu
chung.
Related worksections
Refer to the following worksections:
Electrical General Requirements, Motor
Starters, Electrical Commissioning,
Switchboards.
Nhng chng lin quan
Tham chiu n cc chng sau:
Nhng yu cu chung v in, T in,
B khi ng mt, Chy th v
nghim thu h thng in.
1.3 STANDARD
With respect to alternative standards,
please refer to section 3.1 of this
Specification A4 worksection
1.3 TIU CHUN
V tiu chun thay th, xem li on
3.1 chng A4 ca ti liu Qui nh k
thut ny.
1.4 STANDARD 1.4 TIU CHUN
General
To BS 5486.
Electrical work: To BS 7671 & BS
50281-1-1&2
Low voltage switchgear: AS/NZS 3947
Parts 1, 2, 3, 4.1, 4.3, 5.1, 5.2, 5.3, 5.5,
5.6, 6.1, 6.2, 7.1 and 7.2.
IEC 60044 Instrument Transformer
IEC 60051 Direct Acting Indicating
Electrical Measuring Instruments and
Their Accessories.
IEC 60073 Colours of Indicator Lights
and Push Buttons
IEC 60129 AC Disconnectors (Isolators)
and Earthing Switches
IEC 947-2 Circuit breakers
IEC 60158 Low Voltage Control Gear
IEC 60186 Voltage Transformers
IEC 60255 Electrical Relays
IEC 60269-1 Low-Voltage Fuses.
Supplementary Requirements for Fuses
for Industrial Applications.
IEC 60445 Identification of Equipment
Terminals.
IEC 60473 Dimensions for Panel-
Mounted Indicating and Recording
Electrical Measuring Instruments
IEC 60715 Dimensions of Low-Voltage
Switchgear and Controlgear,
Tng qut
Theo BS 5486
Cng tc in: To BS 7671 & BS
50281-1-1&2
Thit b ng ngt h p: AS/NZS 3947
phn 1, 2, 3, 4.1, 4.3, 5.1, 5.2, 5.3, 5.5,
5.6, 6.1, 6.2, 7.1 v 7.2.
IEC 60044 My bin p o lng
IEC 60051 Cc dng c o lng in
ch th hot ng trc tip v cc ph
kin.
IEC 60073 Mu ca n ch th v nt
nhn
IEC 60129 Dao ngt xoay chiu (Cu
dao cch ly) v Cu dao tip t
IEC 947-2 Cu dao t ng.
IEC 60158 T iu khin h p
IEC 60186 My bin in p
IEC 60255 R le in
IEC 60269-1 Cu ch h p. Cc yu
cu b sung cho cu ch ca cc thit b
cng nghip.
IEC 60445 Nhn bit cc u ni thit
b.
IEC 60473 Cc kch thc cc dng c
ch th o lng v ghi in lp t.
IEC 60715 Kch thc ca cc t iu
khin v ng ngt, tiu chun ha vic
gn trn thanh ray cho cc gi c

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 2 of 27 of C.05 19 September 2007
Standardised Mounting on Rails for
Mechanical Support of Electrical
Devices in Swgr and Control-gear
Installations
IEC 60947 Low Voltage Switchgear and
Control Gear.
IEC 61641 Enclosed Low-Voltage
Switchgear and Controlgear Assemblies
Guide for Testing Under Conditions of
Arcing due to An Internal Fault.
IEC 60831 Shunt power capacitors of the
self-healing type for a.c. systems having
rated voltage up to and including 1000V.
Part 1 and Part 2.
kh ca cc thit b in trong lp t
cu kin iu khin v ng ngt.

IEC 60947 C cu iu khin v ng
ngt h p.

IEC 61641 T cha cc cu kin trong
iu khin v ng ngt - Hng dn
cc iu kin kim tra H quang in
do Dng r h quang bn trong gy ra.
IEC 60831 T in b loi t-b bn
trong cho h thng in xoay chiu
in p nh mc ln n 1000V Phn
1 v Phn 2.
1.5 INTERPRETATIONS 1.5 KHI NIM
Definitions
Rated currents: Rated currents are
continuous uninterrupted current ratings
within the assembly environment under
in-service operating conditions.
nh ngha
Dng nh mc: Dng nh mc lin
tc khng ngt qung trong mi trng
lp rp, di iu kin vn hnh ang
phc v.
Abbreviations
TTA: Type tested assemblies.
NTTA: Non-type tested assemblies.
PTTA: Partially type tested assemblies.
Ch vit tt
TTA: cc cu kin c kim tra mu.
NTTA: cc cu kin khng kim tra
mu.
PTTA: cc cu kin kim tra mu mt
phn.
1.6 DESIGN 1.6 THIT K
Discrimination
Select protective devices to grade and
coordinate for overcurrent and earth
faults, and to automatically disconnect
the supply in the event of touch
potentials exceeding the limits
prescribed by AS/NZS 3000.
S chn la
La chn dng c bo v theo cp
v kt hp vi bo v qu dng v
dng chm t, v t ng ngt ngun
trong trng hp in th tip xc vt
qu gii hn m t trong AS/NZS
3000.
Layout
Position equipment to provide safe and
easy access for operation and
maintenance. Consider functional
relationships between items of
equipment in the laying out of equipment
on the assembly.
B tr
t thit b sao cho an ton v d dng
tip cn vn hnh v bo tr. Xem
xt cc mi quan h hot ng gia cc
hng mc thit b trong vic b tr v
lp t thit b.
Statutory authoritys equipment
Liaise with the supply authority with
regard to the installation and
coordination with their protective and
control equipment.
Cc thit b ca c quan thm quyn
Gi lin lc vi c quan thm quyn
cung cp v vn lp t v phi hp
vi cc thit b iu khin v bo v do
h cung cp.
2 QUALITY 2 CHT LNG
2.1 SUBMISSIONS 2.1 TRNH DUYT
General
Submit product data for components.
Tng qut
trnh cc thng s sn phm cho cc
cu kin.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 3 of 27 of C.05 19 September 2007
3 MATERIALS 3 VT T
General
All circuit breakers which are larger than
350A must have extension handles for
easy operation.
Tng qut
Tt c cc cu dao t ng ln hn
350A phi c cn thao tc ni di d
dng ng ct.
3.1 PROTECTIVE AND
CONTROL DEVICES
3.1 DNG C IU KHIN V
BO V
Coordination
Provide protective devices which grade
and coordinate for short circuit current,
overcurrent, let through energy, and
earth faults.
S phi hp
Cung cp cc dng c bo v c
phn cp v kt hp cho dng ngn
mch, qu dng, nng lng pht sinh
v dng chm t.
3.2 AUTO-TRANSFER
SWITCHES
3.2 B CHUYN I T NG
Standard
To AS 3947.6.1.
Tiu chun
Theo AS 3947.6.1.
Type
4 pole automatic type with supervisory
circuits which initiate and restore the
changeover transfer operation. Transfer
switches shall generally be Air or
molded case circuit breaker type.
Loi
Loi 4 cc t ng vi mch gim st,
mch ny kch hot v hon tr hot
ng chuyn i ngun. B chuyn
mch c th l kiu my ct khng kh
hoc MCCB.
Controls
ATS controls are to be either a
proprietory purpose built microprocessor
control such as Merlin Gerin UA or UG
controller or provide controller
constructed from discrete timers and
relays. Do not provide PLC based
controllers.
Provide solid state phase failure relays to
monitor both normal and replacement
supplies.
The operation of the ATS logic shall be
that on the loss of the normal supply the
generator shall be started after a preset
time delay. Where the normal source
has returned before the generator is
available for operatiuon then the system
shall not transfer to the generator source
but shall remain on normal supply.
An early transfer to generator shall be
possible innitiated on partial voltage
build-up or a delayed transfer may be set
on an adjustable time delay.

Provide an adjustable time delay
between disconnecting from the normal
supply and closing on the generator and
similarly when retransferring back from
generator to the normal supply.

Provide the following ATS controller
functions:
Time delay on generator call, Adjustable
0.2sec to 5min
iu khin
iu khin ATS l loi sn xut
nguyn b s dng vi iu khin nh l
Merlin Gerin UA hay l b iu khin
UG hay cung cp b iu khin cu to
t cc b nh thi ri rc v rle.
Khng cung cp cc b iu khin da
trn PLC.
Cung cp rle gi trng thi khi c li
pha theo di c ngun in bnh
thng v ngun thay th.
Hot ng ca lgic b ATS sao cho
khi b mt ngun cp in bnh thng
my pht s khi ng sau mt khong
thi gian ch n nh trc. Khi ngun
in bnh thng c tr li trc khi
my pht sn sng hot ng th h
thng s khng chuyn qua ngun my
pht m s gi ngun in thng.
Vic chuyn qua my pht sm s c
th c kch hot bng in p bn
phn hay vic hon chuyn ngun c
th iu chnh bng khong thi gian
ch.
Cung cp mt khong thi gian ch c
th chnh nh c gia vic ngt khi
ngun bnh thng v ng ngun ln
my pht v tng t nh vy khi
chuyn ngun ngc li t my pht
qua ngun bnh thng.
Cung cp b iu khin ATS c cc
chc nng sau:
Thi gian ch khi yu cu chy my
pht, chnh c t 0.2 giy n 5 pht

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 4 of 27 of C.05 19 September 2007
Voltage buildup monitoring 75% to
100%
Delay before transfer to replacement
source, adjustable 0.2sec to 2 min
Dwell before connection to replacement
source adjustable 0.2sec to 30 sec

Minimum run on replacement source
adjustable 1min to 30 minutes.
Dwell on retransfer to normal source
adjustable 0.2sec to 30 sec.
Theo di in p tng dn t 75% n
100%
Ch trc khi chuyn qua ngun thay
th, chnh c t 0.2 giy n 2 pht
Ngng trc khi kt ni vo ngun
thay th, chnh c t 0.2 giy n 2
pht
Thi gian ti thiu s dng ngun thay
th, chnh c t 1 pht n 30 pht
Ngng trc khi chuyn tr li ngun
bnh thng, chnh c t 0.2 giy
n 30 giy.
Classification
Contactors: PC.
Circuits: CB.
Phn lp
Cng tc t: PC
Mch: CB
Circuit breakers
Comply with Air circuit breakers, in the
Circuit breakers subsection. Provide
Trip units as required by drawings.
My ngt
Tun theo chng My ngt khng kh,
trong phn My ngt. Cung cp b iu
khin ct nh yu cu trn bn v.
Contactors
Comply with Contactors, in the
Controlgear subsection. Use only where
specifically required on drawings.
Cng tc t
Tun theo on Cng tc t, trong phn
thit b iu khin. Ch s dng
nhng v tr c yu cu trn bn v.
Interlocks
Provide electrical and mechanical
interlocks.
Mechanical interlocks shall generally be
a proprietory cable interlock, walking
beam, or castle key system where
manual transfer is required.
Kho lin ng
Cung cp cc kho lin ng c kh v
in.
Kha lin ng c kh l loi lin ng
cp, then cht hoc h thng cha kha
ti nhng ch yu cu chuyn mch
bng tay.
Mechanically held
All auto-transfer switches to be
mechanically held.
Gi bng c kh
Tt c cc b chuyn i t ng c
gi bng c kh.
3.3 AIR CIRCUIT BREAKERS 3.3 MY NGT KHNG KH
Standard
To AS 3947.2.or IEC 947-2
Tiu chun
Theo AS 3947.2. hay IEC 947-2.
Type
Open construction, withdrawable 4
poles, back connected, trip free.
Loi
Cu trc m, 4 cc c th ko ra c,
u ni ngc, nh t do.
Rated duty
Based on uninterrupted duty in a non-
ventilated enclosure.
Loi chu ti nh mc
Da trn cng sut lin tc trong v t
khng thng gi.
Utilisation category
Type B for partial and full
discrimination.
Loi s dng
Loi B cho phn loi tng phn v ton
phn.
Rated service short-circuit breaking
capacity
At least the fault level at incoming
terminals of the assembly. The I
CS
must
be equal to I
CU
(I
CS =
I
CU
).
nh mc cng sut ct ngn mch.

Ti thiu bng mc ngn mch ti u
vo t. Dng I
CS
phi tng ng
dng I
CU
(I
CS =
I
CU
).
Closing operation
Provide trip free closing mechanisms for
operation, with positive mechanically
operated ON/OFF indications.

Hot ng ng
Cung cp cc c cu vn hnh ng
khng ngt, vi cc ch th r rng v tr
NG/M.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 5 of 27 of C.05 19 September 2007
Opening operation
Provide mechanically operated release
for opening.
Hot ng nh
Cung cp cc c cu vn hnh nh
ngt mch.
Auxiliary switch contacts
Provide contacts with minimum rated
operational current of 6 A at 240 V,
50 Hz. Provide at least one spare
normally-open and one spare normally-
closed contact. Provide shunt trip release
coil circuits with an early-make/late-
break series connected auxiliary contact.
Tip im ng ngt ph
Cung cp cc tip im c dng hot
ng nh mc ti thiu 6 A, 240 V, 50
Hz. Cung cp d phng t nht mt tip
im thng m v mt tip im
thng ng. Cung cp cun nh vi
chui ng-sm/ nh tr kt ni vo
tip im ph.
The auxiliary supply voltage shall be 110
V DC with a permissible variation range
of -15% to +10%
The control power for breaker closing,
tripping and spring charging shall be DC
110 V. All control circuits of each
Circuit Breaker shall be separately
protected by means of MCBs. The close
and trip circuits shall be separately
protected.
The Protection and Control units shall be
operational by auxiliary power supply
voltage: 110 V DC, and current sensors:
1 A - CT, and voltage sensors: 110 V -
VT.
in p cho cc thit b ph 110 VDC
vi phm v bin i chp nhn c -
15% n +10%
Ngun iu khin cho my ngt ng,
ngt v np in cho ci nhy l ngun
DC 110V. Tt c cc mch iu khin
cho mi my ngt c bo v ring
bit bng cc MCB. Cc mch ng,
ngt s c bo v ring bit.

Cc b phn iu khin v bo v s
c vn hnh bi ngun in ph:
in p mt chiu 110V, v cc bin
dng: dng nh mc l 1A; cc bin
p: in p nh mc l 110 V.
Protection system
Integral to the circuit breaker,
incorporating a solid state protection
relay.
H thng bo v
Tch hp vi my ngt, kt hp vi r
le bo v bn dn.
Compartment
House each circuit breaker in a separated
self-contained enclosed subsection
module within the assembly.
Ngn cha
Cha mi my ngt trong mt tiu khu
ring bit bn trong t in.
Locking
Provide for circuit breakers to be
padlocked in the open position.
Kha
Cung cp cc mc kha cho my ngt
v tr m.
Interlocking
Electrical: Interlock control circuitry of
functional units with normally-opened
and normally-closed auxiliary contacts.
Mechanical: Required.
- Coded key: Captive type with squared
face key with alphabetical or
numerical coded operating face.
Kha lin ng
V in: Mch iu khin kha lin
ng ca cc thit b chc nng bng
cc tip im ph thng ng v m.
C kh: Yu cu.
- Kha mt m: Loi gi cht vi b
mt hnh vung trn c cc ch v
m s hot ng.
Door interlock
Except for compartment doors serving
only as covers, provide interlocks
preventing compartment doors being
open while circuit breakers are closed.
Kho lin ng ca
Ngoi tr cc ca ca cc ngn ch l
cc np che, cung cp cc kho lin
ng ngn nga cc ca m ra trong
khi my ngt ng in.
Abnormal operations
Provide breakers which cannot be used
in the following operations:
- Slow closing or opening of contacts.
- Manual independent hand closure, if
springs fail.
- Release of charged springs while
contacts are closed.
Vn hnh khc thng
Cc my ngt khng c s dng
trong cc hot ng di y:
- Cc tip im ng hay m chm.
- Vn hnh ng bng tay c lp, nu
l xo b hng.
- Nh l xo np trong khi tip im
c ng.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 6 of 27 of C.05 19 September 2007
Withdrawable type
Mounting: Mount circuit breaker on a
withdrawable carriage with racking gear
for racking in or withdrawing, and for
positively fixing the unit into any of the
3 following positions:
- Connected.
- Test/isolated.
- Disconnected.
Auxiliary contacts: Provide contacts
which remain connected in the
test/isolated position.
Interlocking: Provide interlocking which
prevents circuit breaker being racked in
or withdrawn unless it is in a tripped
condition and prevents the circuit
breaker being closed unless located in
either the connected or test/isolated
position. Provide stored energy devices
which are automatically discharged by
any racking operation.
Shutters: Provide automatic shutters,
which can be padlocked, covering busbar
and incoming/outgoing circuit
connections and labelled BUSBARS
and CIRCUIT respectively.

Earthing: Provide earthing connection
between withdrawable carriage and
assembly earth busbar which makes
before, and breaks after, other contacts
on the circuit breaker carriage.
Loi ko ra c
Gn: Gn my ngt trn khung ko ra
c vi c cu bnh rng iu khin
gn vo hay tho ra, v gn chc
chn thit b bt k 3 v tr no sau
y:
- u ni.
- Ngt/kim tra.
- tho ri
Tip im ph: Cung cp cc tip im
ph cn gi kt ni v tr tho/kim
tra.
Kha lin ng: Cung cp cc kha ci
vo nhau ngn nga my ngt b ko
ra hay hay lp vo ngoi tr n iu
kin ngt v ngn nga my ngt ng
li khi n mt trong hai v tr ni
hoc ngt/ kim tra. Cung cp mt
dng c lu tr nng lng, dng c
ny c t ng x bi bt k mt
hat ng quay bnh rng no.
L chn: Cung cp nhng l chn t
ng, nhng l chn ny c kha
bng kha mc, che thanh ci v che
cc u ni mch vo/ra, cc nhn ny
cn c dn nhn THANH CI v
MCH ring bit.
Tip t: Cung cp cc kt ni tip t
gia khung sn ko ra c v thanh
tip t ni trc , v ngt sau ,
cc tip im khc trn sn my ngt.
Maintenance
Provide for slow closing of the circuit
breaker and for adjustment when
disconnected.
Bo tr
Cung cp ng chm cho cc my ngt
v cn chnh khi tho ri.
3.4 MOULDED CASE AND
MINIATURE CIRCUIT
BREAKERS
3.4 CU DAO T NG NH
(MCB) V LN (MCCB)
Type
Fault capacity 10 kA: To AS 3947.2 or
IEC 947-2.
Fault capacity < 10 kA: Miniature
overcurrent circuit breakers.
I
CS
= 75% of I
CU
.
Loi
Cng sut ngn mch 10 kA: Theo
AS 3947.2 hay IEC 947-2.
Cng sut ngn mch < 10 kA cho
MCB qu dng.
Dng I
CS
= 75% dng I
CU

Mounting
Mount circuit breakers so that the
ON/OFF and current rating indications
are clearly visible with covers or
escutcheons in position. Align operating
toggles of each circuit breaker in the
same plane.
Gn
Gn my ngt sao cho hin th nh
mc dng v trng thi NG/M
r rng nhn thy c khi np ca hay
tm che bn trong c lp vo. Chnh
cc n tay vn hnh ca my ct trn
cng mt phng.
Utilisation category
Non-discrimination: Type A. Final
distribution circuits only.
Partial or full discrimination: Type B.
All main LV switchboard circuits, and
otherwise all above final distribution
Phn loi s dng
Khng phn loi: Loi A. Ch cho
mch phn phi sau cng.
Xp loi mt phn hay ton phn: Loi
B. Cho tt c cc mch ca t H p
chnh, v nu khng th cho tt c pha

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 7 of 27 of C.05 19 September 2007
circuits. trn ca mch cui cng.
Adjustable current settings
General: If trip current adjustment
control is exposed with covers in
position, provide for sealing to prevent
tampering.
Labels: Provide labels indicating trip
settings.
Ci t dng chnh
Tng qut: Nu c phn iu chnh
dng ngt c nhn thy khi np t
ang ng, th ti phi nim phong
li ngn nga thao tc nhm ln.
Dn nhn: Cung cp cc nhn th hin
gi tr ci t dng ngt.
Trip settings
Adjustable short circuit trip settings: Set
to the low position.
Ci t ngt
Ci t dng ngt ngn mch chnh
c: Ci t ti v tr thp.
Trip units
Circuit breakers with interchangeable
and integrally fused trip units: Connect
so that trip units are not live when circuit
breaker contacts are open.
Thit b ngt
My ngt vi cc cu kin ngt c tch
hp cu ch v c th hon i ln nhau
c: u ni sao cho cc cu kin
ngt khng c in khi my ngt v
tr m.
Locking
Provide for locking circuit breakers in
the open position.
Kha
Cung cp cc kha my ngt v tr
m.
Clip tray chassis
For miniature overcurrent circuit
breakers provide clip tray assemblies
capable of accepting single, double, or
triple circuit breakers, and related
busbars. Provide moulded clip-on pole
fillers for unused portions.
Thanh kp
Cho nhng MCB qu dng cung cp
cc thanh kp c kh nng gn cc
MCB n, i, hay ba, v thanh ci lin
i. Cung cp cc ming nha lp vo
nhng phn cha s dng.
Accessories
Rotary handle: Provide ON/OFF
indication, and override release to open
door padlocking facility.
Motor operators: Provide selector
switches, controls and indicators.
Auxiliary contacts: Minimum rating 5 A.
Ph kin
Tay xoay: Cung cp biu th
NG/M, v cn nh u tin
m cc tin ch mc kha ca.
B vn hnh ng c: Cung cp cc
cng tc xoay, iu khin v ch th.
Tip im ph: nh mc ti thiu 5A.
3.5 CURRENT TRANSFORMERS
(METERING)
3.5 BIN DNG (O LNG)
Standard
Measurement current transformers: To
AS 1675
Tiu chun.
My bin dng o lng: Theo AS
1675.
Test links
Provide test links for connection of
calibration instruments and meters and
for shorting of current transformer
secondaries. Provide energy meters,
maximum demand meters, ammeters and
protection relays, with sets of rail-
mounted links consisting of screw-
clamped slide links and an earth link.
Thanh lin kt cho kim tra
Cung cp cc thanh kt ni cho kim
tra ni cc dng c hiu chun v
ng h o v ni tt th cp my bin
dng. Cung cp ng h, ng h o
yu cu ln nht, ng h o dng v
cc rle bo v, vi b thanh ray c gn
cc lin kt c sn nh vt-lin k kp
trt v lin kt tip t.
Test studs
For energy and demand meters provide
rail-mounted potential test studs or plug
connections next to associated current
transformer links. Provide at least one
set of test studs for each compartment.
u ni kim tra
i vi cc ng h o lng v o
nng lng, cung cp u ni kim tra
in p lp ray hay cc cm ni gn
k bin dng tng ng. Cung cp t
nht mt u ni kim tra cho mi
ngn.
Accuracy classification
Energy measurements: Class 0.5M.
Cp chnh xc
o lng nng lng: Lp 0.5M

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 8 of 27 of C.05 19 September 2007
Indicating instruments: Class 2M. Kh c ch th: Lp 2M.
Ratings
Rated short time current: At least the
short time withstand current equivalent
of the circuit in which the transformer is
installed.
Rated primary current: At least equal to
the current rating of the functional unit.
Secondary windings: Rated at 5 A,
burden of 0.4 (10 VA) with star point
earthed.
nh mc
Dng ngn mch nh mc: t nht
tng ng dng chu thi gian ngn
mch trn bin dng c mc vo.
Dng s cp: t nht tng ng dng
nh mc ca thit b chc nng.
Cun dy s cp: nh mc 5 A, in
tr 0.4 (10 VA) vi im sao ni t.
Type
If practicable, cast resin encapsulated
window-type with busbar clamping
devices. Otherwise wound-primary type
with mounting feet.
Loi
Nu c th thc hin c, l loi v
c dng ca s vi dng c kp vo
thanh ci. Hay cch khc l loi qun
dy s cp vi chn gn.
Installation
General: Install transformers to permit
easy removal.
Removable links: Provide removable
links of minimum lengths for
transformers fitted on busbar systems.
Lp t
Tng qut: Lp t bin dng nhm
cho php tho ra d dng.
Lin kt c th tho ri c: Cung cp
cc lin kt c th tho ri c vi
chiu di ngn nht gn bin dng
vo h thng thanh ci.
3.6 INSTRUMENTS AND
METERS
3.6 DNG C V NG H O
Electricity meters
Energy demand type induction watthour
meters: To AS 1284.3.
General purpose electronic induction
watthour meters: To AS 1284.5.
General purpose induction watthour
meters: To AS 1284.1.
Socket mounting system: To AS 1284.4.

ng h in
ng h in loi cm ng loi o
cng sut tiu th in: Theo AS
1284.5.
ng h cm ng in mc ch chung
theo AS 1284.5
ng h in cm ng mc ch
chung: Theo AS 1284.1.
H thng gn cm: Theo AS 1284.4.
Construction
Indicating and recording instruments:
Provide damped movements and impact
resistant glass cover. Provide for external
adjustment of the zero. Support moving
elements of indicating instruments
between shock resistant jewel bearings.
Transducers: Totally enclose in flame-
retardant, rail-mounted moulded cases.
- Minimum degree of protection: IP52.
Cu trc
Dng c o lng v ch th: Cung cp
loi dch chuyn chm u v np knh
chu va chm. Cung cp u chnh v tr
khng. Gia c cc phn t chuyn ng
ca cc dng c ch th gia cc vng
m chng rung.
B bin i tn hiu: V ngoi c kn
gn trn thanh ray, bng vt liu ngn
chy.
- Cp bo v nh nht: IP52.
Meter scales
Direct reading analogue type with black
lettering on white background with black
pointer, capable of indicating the
maximum value of the measured
variable.
Thang o
Loi tn hiu analogue c trc tip c
ch en, kim en trn nn trng, c kh
nng ch gi tr ln nht cc thang o.
Transducers
If necessary for transducer operation,
provide auxiliary supply. Connect
outputs to dedicated rail-mounted
isolating type terminals.

B bin i tn hiu
Nu cn thit cho vn hnh b bin i
tn hiu, cung cp ngun ph. Kt ni
u ra n u ni loi cch ly lp ray
ring.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 9 of 27 of C.05 19 September 2007
Accuracy
Indicating instruments and accessories:
Accuracy class 1.5 or lower class index
number except Class 3 for thermal
maximum demand indicators.

Electricity meters: Class 0.5.
Power factor meters, phase angle meters
and synchroscopes: 2 electrical degrees
maximum error.
Transducers: Class 0.5.
Cp chnh xc.
Dng c ch th v ph kin: Cp chnh
xc lp 1.5 hay cp chnh xc thp hn
ngoi tr Phn lp 3 cho dng c ch
th cng sut tiu th dng nhit ln
nht.
ng h in: Phn lp 0.5.
ng h o h s cng sut, ng h
o gc pha v o s ng b: Sai s ln
nht 2 cp in.
My bin i tn hiu: Lp 0.5.
Accessories
General: Mount next to associated
instruments, inside cabinets.
Power distribution assemblies: Provide
meters of the same style and size, with
bezel minimum 96 x 96 mm and 90
o

quadrant scale.
Motor control assemblies: On motor
starter modules, provide bezel 72 x
72 mm with 90
o
quadrant scale.
Ph kin
Tng qut: Gn gn vi thit b i km,
bn trong t in.
T phn phi in: Cung cp cc ng
h o cng loi v cng kch c, c g
vt vi mt ng h nh nht 96 x 96
mm v thang o gc mt phn t 90
o
.
Cu kin iu khin ng c: Gn trn
t khi ng ng c, cung cp cc mt
ng h 72 x 72 mm c g vt vi
thang o gc mt phn t 90
o
.
Mounting
Flush mount meters on hinged panels.
Wire with multi stranded flexible cables
Gn
Gn ng h phng mt trn ca bn l.
Vi dy ni mm nhiu li.
Protection devices
Meter potential protection devices:
Group together behind associated meter
cover or hinged door, preferably next to
current transformer test links.
Dng c bo v
Dng c bo v in th ng h: Gn
nhm pha sau vch cc dng c o lin
kt vi nhau hay trn ca cnh m, tt
nht l gn cc lin kt kim tra ca
bin dng.
Labels
If associated exclusively with one phase,
label meters RED, YELLOW, or
BLUE as applicable.
Dn nhn
Nu phi gn dng c o ch trn mt
pha, th phi dn nhn dng c o
, VNG, hay XANH.
Ammeters
Type: Moving iron type oil dampened
for motor starter circuits.
Overscale: For ammeters subject to
motor starting currents, overscale to at
least 5 x full load current.
Selector switches: 4-position type with
positions designated R/W/B/OFF.
Mount under or next to relevant
ammeters.
ng h o dng in
Loi: Loi st cm ng tm du cho
mch khi ng ng c.
Thang o ngoi: Cho nhng b o dng
cho mch khi ng ng c, thang o
ngoi t nht bng 5 ln dng y ti.
Cng tc v tr: Loi 4-v tr vi cc v
tr c thit k /Trng/Xanh/Tt.
Gn pha di g vi cc b o dng
lin quan.
Maximum demand indicators
General: Provide a meter in each phase
with 15 minute response time. Provide
for sealing the reset mechanism. Provide
a combination 3 point indicator
consisting of an instantaneous red
ammeter pointer, a red maximum
demand slave pointer with external reset
facility, and a white maximum demand
pointer.
Instantaneous type: Combined type with
bi-metal maximum demand ammeter
element and moving iron instantaneous
ammeter element.
Ch th yu cu ln nht.
Tng qut: Cung cp mi ng h o
trn mi pha vi thi gian p ng 15
pht. Cung cp phn che chn cho c
cu chnh. Cung cp mt b ch th kt
hp 3 kim gm c kim ch dng tc
thi mu , mt kim ch dng ph
mu ch yu cu ln nht vi nt
chnh li, v mt kim ch dng yu cu
ln nht mu trng.
Loi tc thi: Loi kt hp nguyn t
o dng ln nht lng kim v nguyn
t o dng tc thi st cm ng.
Loi nhit: Loi kt hp vi nguyn t

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 10 of 27 of C.05 19 September 2007
Thermal type: Combined type with bi-
metal maximum demand ammeter
element.
o dng yu cu ln nht lng kim.
Accuracy class
Instantaneous: Class 1.5.
Maximum demand: Class 3.
Cp chnh xc
Tc thi: Lp 1.5.
Yu cu ln nht: Lp 3.
Voltmeters
Type: Moving iron.
Selector switches: 7-position voltage
transfer type for measurement of phase-
to-phase and phase-to-neutral voltages
with off. Mount under or next to relevant
voltmeters.
ng h o in p
Loi: St cm ng
Cng tc v tr: Loi 7-v tr chuyn i
in p pha-vi-pha v pha-vi-trung
tnh v v tr tt. Gn di gn k b o
in p lin quan.
Wattmeters and varmeters
Suitable for balanced 3 phase, 4 wire
loads. Connect to measurement
transducers.
o cng sut v o h s cng sut
Ph hp cho ti cn bng 3 pha, 4 dy.
Kt ni vi b bin i tn hiu.
Hours-run meters
Synchronous motor driven with 6 figure
(minimum) cyclometer dial with last
digit read-out in 0.1 hour increments.
ng h o thi gian tng gi
ng c ko ng b vi mt ng h
o c 6 s (t nht) vi s cui c gia s
0.1 gi.
Scale
Horizontal linear digits.
Multifunction meters
Multifunction meters, unless otherwise
specified, shall be provided with the
following functions: 3 phase monitoring
of volts, amps, power factor, kVA
killowatts and resettable maximum
demand indicator. Meters shall be
provided with backlight LCD displays
and pushbutton mode selection.
Thang o
Ch s nm ngang.
ng h vn nng.
Cc ng h vn nng, ngoi tr c
nhng yu cu khc, s c cung cp
vi cc chc nng nh sau: o in p
ba pha, dng, h s cng sut, cng
sut biu kin, cng sut hu ch v ti
tiu th cc i (c th chnh li v
zero). Cc ng h s c cung cp
vi mn hnh tinh th lng c n nn
v nt nhn chn ch .
Watthour meters
Type: Rotating element induction disc
type or electronic type.
Time of use type to be provided for
commercial applications as required by
EVN tariff schedule.
3 phase metering: Polyphase meters
suitable for balanced 3 phase, 4 wire
loads.
1 or 2 phase metering: Single phase
meters.
Current rating: To suit load and overload
conditions. Provide direct connect
meters suitable for current range of 15 -
100 A and meters with current
transformers suitable to 5 A secondary.
Register: Provide a direct reading
register of the large figure type. Mark on
the scale the metering transformer ratios
and the multiplying factor applied to the
meter constant.
Covers: Seal main covers.
ng h o cng sut
Loi: Loi a cm ng xoay hay loi
in t.
Loi ng h o thi gian s dng
c cung cp cho ng dng thng
mi nh yu cu biu cc ph EVN
(in lc)
o lng 3 pha: ng h o nhiu pha
thch hp cho ti cn bng 3 pha, 4 dy.
o 1 hay 2 pha: ng h o n pha.

Dng nh mc: ph hp vi ti v
iu kin qu ti. Cung cp cc ng
h o kt ni trc tip cho di dng 15
100 A c bin dng 5 A dng th
cp.
My ghi: cung cp cc my ghi c
trc tip kiu s ln. nh du trn
thang o t s my bin dng v h s
nhn ng dng cho hng s ng h.
Np: nim phong cc np chnh.
Frequency meters
Type: Either an analogue type, or
vibrating reed type with 7 reeds.
ng h o tn s.
Loi: Mt trong hai loi tn hiu
analogue, hay loi l rung vi 7 l.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 11 of 27 of C.05 19 September 2007
Analogue type: Graduated in 0.1 Hz
increments.
Scales:
- Analogue: Graduated 45/65 Hz.
- Vibrating reed: Horizontal reed bar
graduated 47/53 Hz.
Loi tn hiu analogue: c chia
0.1 Hz.
Thang o:
- Loi analogue: c chia 45/65
Hz.
- L rung: Thanh l ngang c chia
47/53 Hz.
Synchroscopes
General: Continuously rated, rotating
vane type movement, with spring loaded
bearings and silicon fluid dampening,
positive and negative arrows, black
pointer and 12 oclock marking.
Scales: 360
o
.
ng h ng b
Tng qut: Chuyn ng loi chong
chng quay, cp hot ng lin tc, vi
l xo chu ti v nhng trong silicon,
cc mi tn ch khong m v dng,
kim mu en v nh du v tr 12 gi.
Thang o: 360
o
.
Phase angle meters
General: Provide for 3 phase, 4 wire
balanced loads.
Scales: 0.5 leading to 0.5 lagging.
ng h o gc pha
Tng qut: Cung cp cho ti cn bng 3
pha, 4 dy.
Thang o: Trc 0.5 chm sau 0.5.
3.7 INDICATOR LIGHTS 3.7 N CH TH
General
Colour: Provide ON (green) and FAULT
(red) pilot lights on the fascia of the
control panel for all motors.
Tng qut
Mu: n ch th v tr NG (mu
xanh) v LI (mu ) cho tt c cc
mt t iu khin ng c.
Standard
To AS 3947.5.1.
Tiu chun
Theo AS 3947.5.1.
Degree of protection
At least that of the assembly/operating
face.
Cp bo v
Ti thiu theo b mt lp t/ vn hnh.
Incandescent indicators
Type: Incandescent oil tight type
minimum 22 mm diameter or 22 x
22 mm.
Lamps: Changeable from front of panel
without removing the holder.
Lamp rating: 1.2 - 5 W.
n ch th bng nung sng
Loi: Loi bng nung sng khng thm
du ng knh ti thiu 22 mm hay
kch thc ti thiu 22 x 22 mm.
Bng n: C th thay th c t pha
trc mt t m khng phi tho ri
n.
Cng sut n: 1.2 5 W.
Neon indicators
240 V, 12 mm diameter with in-built
resistor.
n n-ng
240V, ng knh 12 mm c gn in
tr bn trong.
LED indicators
12 or 24 V as necessary, in corrosion-
resistant bezel, nominal 5 mm diameter.
n it pht quang LED
12 hay 24V khi cn thit, trong khung
khng n mn, ng knh 5 mm.
Press-to-test
Compartments/subsections with < 5
indicating lights: Provide each indicating
light with a fitted integral press-to-test
lamp actuator.
Compartments/subsections with 5
indicating lights: Provide a common
press-to-test lamp push-button.




Nt nhn kim tra.
Cc tiu khu/ngn c s n ch th < 5:
Cung cp mi n mt nt nhn gn
bn trong nhn kim tra n.
Cc tiu khu/ngn c s n ch th 5:
Cung cp mt nt nhn chung nhn
kim tra n.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 12 of 27 of C.05 19 September 2007
3.8 CIRCUIT BREAKER
INTEGRAL PROTECTIVE
RELAYS
3.8 R LE BO V TCH HP
VI MY NGT
General
Provide integral protective relays which
provide for tripping in the event of relay
operation, and for manually resetting.
Provide operation indicators with a set of
change over voltage free alarm contacts,
for connection to an alarm circuit.
Tng qut
Cung cp r le bo v tch hp c chc
nng ngt khi r le hot ng, v cho
reset bng tay. Cung cp cc n ch th
hot ng c b tip im chuyn i
bo ng khng ph thuc in p do,
kt ni vo mch bo ng.
Mounting
Integral type: Readily accessible for
viewing and adjustment with doors and
covers in position.
External type: Flush.
Gn
Kiu kt hp chung: D dng tip cn
quan st v cn chnh vi khi cc
ca v np ang ng.
Loi bn ngoi: Gn phng mt.
3.9 CURRENT TRANSFORMERS
(PROTECTION)
3.9 MY BIN DNG (BO V)
Standard
To AS 1675.
Tiu chun
Theo AS 1675.
Type
Cast resin encapsulated window type
with busbar clamping devices
Loi
L loi ca s c kn vi dng c kp
thanh ci.
Rated short time current
At least the short time current equivalent
to the assembly fault level.
Dng ngn mch nh mc
Ti thiu dng ngn mch tng ng
vi mc ngn mch ca t.
Rated short-time
At least the maximum time setting of the
related protective relay. Minimum 1 s.
Thi gian ngn mch nh mc
Ti thiu ci t thi gian ln nht cho
cc r le bo v lin quan. Nh nht 1s.
Rated primary current
Equal to assigned current rating of the
associated functional unit.
Dng nh mc s cp
Tng ng vi nh mc dng n
nh ca cc cu kin chc nng kt
hp.
Rated secondary current
5 A. Connect star point to earth.
nh mc dng th cp
5A Ni im sao vo t.
Interposing transformers
As recommended by the protective relay
manufacturer.
Bin dng t vo gia
Theo yu cu ca nh sn xut r le
bo v.
Characteristics
As recommended by the protective relay
manufacturer.
c tnh
Theo yu cu ca nh sn xut r le
bo v.
Test links
Provide test terminals and current
transformer secondary shorting links in
accessible positions within instrument
panels. Provide a set of DIN-type rail
mounted test links, consisting of screw
clamped slide links and earth links, for
each current transformer group.
Lin kt cho th nghim
Cung cp cc u ni th nghim v
lin kt ni tt th cp ca bin dng
v tr c th tip cn c bn trong t
thit b. Cung cp lin kt kim tra loi
lp ray DIN, bao gm lin kt trt kp
vt v lin kt tip t, cho mi nhm
bin dng.
Installation
General: Install transformers to permit
easy removal.
Removable links: Provide removable
links of minimum lengths for
transformers fitted on busbar systems.
Markings: Mount transformers in the
Lp t
Tng qut: Lp t my bin dng sao
cho d dng cho php tho ri.
Lin kt c th tho ri: Cung cp
nhng lin kt c th tho ri c vi
chiu di ngn nht gn vo h
thng thanh ci.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 13 of 27 of C.05 19 September 2007
assembly enclosure, so that polarity
markings and nameplate details are
readily viewed right side up without
removing the transformers.
nh du: Gn bin dng trn v t,
sao cho chi tit nhn v nh du cc
c d dng nhn thy t pha trn m
khng phi lt bin dng.
3.10 RESIDUAL CURRENT
DEVICES/ EARTH LEAKAGE
CIRCUIT BREAKERS
3.10 MY CT DNG CHM T/
DNG R
Integral type
General: Incorporate earth leakage in
circuit breaker protection operation.
Mounting: Comply with Moulded case
and miniature circuit breakers, in the
Circuit breakers subsection.
Loi kt hp chung
Tng qut: Bo v dng chm t phi
hp chung vi hot ng bo v ca
my ngt t ng.
Gn: Tun theo tiu chun cho MCB v
MCCB trong chng my ngt in t
ng.
Tripping
Residual current classification: Type II.
Maximum tripping current: 30 mA.
Marking
Each RCD and any associated circuit-
breaker and Isolating switch shall be
marked in accordance with non metallic
engraved or silk screened legend to
indicate the points that it controls.
Where an RCD-protected supply is
connected only to permanently wired
equipment, access to the load circuit for
testing the operation of the RCD shall be
provided. A socket-outlet may be used,
where access to the socket-outlet is by
means of a tool.
Each item of permanently wired
equipment supplied by a leakage-
protected circuit shall be provided with
an individual isolating switch that shall
operate in all live conductors.
Ngt
Phn loi dng r: Loi II.
Dng ngt ln nht: 30 mA.
nh du
Mi RCD v cc my ngt hay cu dao
kt hp c nh du bng cc nhn
khng kim loi hay bng cc tm la
ghi ch cc im iu khin ca n.
Ti nhng ni cung cp b bo v RCD
c ni vo thit b ni dy thng
trc, th cung cp li tip cn mch ti
th nghim s vn hnh ca RCD.
C th s dng cm, nhng ni m
tip cn vo cm phi s dng dng
c cm tay cm vo.
Mi hng mc thit b ni dy thng
trc cp ngun bi mch bo v chng
chm t th s c cung cp thm
mt cu dao ring lp trn tt c dy
dn c in.
3.11 FUSES WITH ENCLOSED
FUSE LINKS
3.11 CU CH VI LIN KT CU
CH C V KN
Standards
Fuse with fuse links with blade contacts:
To AS 2005.21.1.
Fuse with fuse links for bolted
connections: To AS 2005.21.2.
Fuse with fuse links for the protection of
semiconductor devices: To
AS/NZS 60269.4.0.
Tiu chun
Cu ch c cc ni ch bng cc l tip
im: Theo AS 2005.21.1.
Cu ch c cc ni ch bng bulng:
Theo AS 2005.21.2.
Cu ch c cc lin kt ch bo v
cc dng c bn dn: theo
AS/NZS 60269.4.0.
General
General: Provide fuses suitable for the
fault level at the assembly, and which
discriminate with other protective
equipment.
Let-through energy and peak cut-off
current: To suit protected equipment.
Tng qut
Tng qut: Cung cp cu ch theo mc
ngn mch ca t, v phn bit vi
cc thit b bo v khc.
Dng ct nh v nng lng pht sinh:
Ph hp vi thit b c bo v.
Utilisation category
Motor circuits: gG, gM or aM.
Back-up protection: gG.
Distribution/general purpose: gG.
Phn loi s dng
Mch ng c: gG, gM hay aM.
Bo v d phng: gG.
Mc ch chung/phn phi: gG.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 14 of 27 of C.05 19 September 2007
Fuse-holders
Mount fuse-holders so that fuse carriers
may be withdrawn directly towards the
operator and away from live parts.
Provide fixed insulation which shrouds
live metal when the fuse carrier is
withdrawn.
Chn cu ch
Gn chn cu ch thn cu ch c
th ko trc tip v pha ngi vn
hnh v trnh xa cc cu kin mang
in khc. Gn cch in c nh
che cc phn kim loi c in khi thn
cu ch c tho ra.
Unenclosed fuses
Provide barriers on both sides of each
fuse link, preventing inadvertent
electrical contact between phases by the
insertion of screwdriver.
Cu ch khng kn
Cung cp cc ming chn hai bn ca
cu ch, ngn nga nhng tip xc
v gia cc pha do u tua vt a
vo.
Fuse links
Type: Enclosed, high rupturing capacity
type mounted in a fuse carrier. If
necessary for safe removal and insertion
of the fuse carrier, provide extraction
handles. Mount on clips within the
spares cabinet.
Identification: Clearly indicate
Australian manufacturer or distributor.
Cu ch
Loi: Loi kn, dng ngt cao gn trn
thn cu ch. Nu cn thit cho vic
tho v lp thn cu ch an ton, cung
cp nhng tay cm nh cu ch. Gn
trn kp gi ca t ph tng d tr.
Nhn dng: Ch ra r rng nh phn
phi hay nh sn xut ca c.
Busbar mounted fuse holders
Provide fuse carriers with retaining clips,
minimum fuse holder 32 A.
Chn cu ch gn trn thanh ci
Cung cp cc thn cu ch vi cc kp
gi, chn cu ch ti thiu l 32A
Spares
Provide 3 spare fuse links for each rating
of fuse link on each assembly. Mount
spares on clips within the spares cabinet.
D phng
Cung cp 3 cu ch d phng cho mi
nh mc cu ch ca thit b. Gn cc
cu ch d phng trn kp gi ca t
ph tng d tr.
3.12 CONTACTORS 3.12 CNG TC T
Standard
A.c. and d.c. contactors: To AS 3947.4.1
Tiu chun
Cng tc t A.C v D.C: Theo AS
3947.4.1
Type
Block type, air break, electro-magnetic.
Loi
Loi khi, ngt khng kh, t - in.
Poles
Number: 3.
Cc
S cc: 3.
Minimum rated values
Rated operational current: Full load
current of the load controlled.
Rated duty:
- Motors: Intermittent class 0.1.
- Heater banks: Intermittent class 1.
Rating: 16 A.
Mechanical endurance: 10.
Utilisation category:
- Motors: AC-3 or DC-3.
- Heater banks: AC-1 or DC-1.
Contacts life: 1 million operations at
AC-3 or DC-3.
Gi tr nh mc nh nht
Dng hot ng nh mc: Dng y
ti ca ti c iu khin.
Mc chu ti nh mc
- ng c: lp khng lin tc 0.1.
- Ti nhit: lp khng lin tc 1.
nh mc 16A.
bn c hc: 10.
Phn loi s dng:
- ng c: AC-3 hay DC-3.
- Ti nhit: AC-1 hay DC-1.
Tui th tip im: 1 triu ln hot
ng ti mc AC-3 hay DC-3.
Auxiliary contacts
General: Provide auxiliary contacts with
at least one normally-open and one
normally-closed separate contacts with
rating of 6 A at 240 V a.c.
Tip im ph
Tng qut: Cung cp cc tip im ph
c t nht mt tip im thng m v
mt tip im thng ng ring bit
vi nh mc 6 A, 240V ac.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 15 of 27 of C.05 19 September 2007
Utilisation category: AC-1.
Slave relay: If the number of auxiliary
contacts exceeds the number which can
be accommodated, provide a separate
slave relay.
Loi s dng: AC-1.
R le ph: Nu s tip im ph vt
qu s tip im c trong cng tc t,
th cung cc r le ph ring.
Mounting
Mount with sufficient clearance to allow
full access for maintenance, removal and
replacement of coils and contacts,
without the need to disconnect wiring or
remove other equipment.
Gn
Gn vi khong khng y nhm
cho php d dng tip cn bo tr,
tho ra v thay th cc cun dy v tip
im m khng cn phi tho dy hay
di di thit b.
Interconnection
Do not connect contactors in series or
parallel to achieve ratings.
Ni lin kt ln nhau
Khng c mc ni tip hay song
song cc cng tc t t c cng
sut mong mun.
3.13 CONTROL AND TEST
SWITCHES
3.13 CNG TC KIM TRA V
IU KHIN.
Standards
To AS/NZS 3947.1 and
AS/NZS 3947.5.1.
Switching elements:
- Electrical emergency stop device with
mechanical latching function: To
AS/NZS 3947.5.4.
- Electromechanical control circuit
devices: To AS/NZS 3947.5.1.
- Proximity switches: To
AS/NZS 3947.5.2.
Tiu chun.
Theo AS/NZS 3947.1 v
AS/NZS 3947.5.1.
Phn t ng ngt:
- Nhng dng c ngt mch in khn
cp vi chc nng ci c kh: Theo
AS/NZS 3947.5.4.
- Dng c mch iu khin c-in:
Theo AS/NZS 3947.5.1.
- Cng tc khng tip xc: Theo
AS/NZS 3947.5.2.
Rated operational current
Utilisation category: AC-22 to
AS 3947.1.
Dng hot ng nh mc
Loi s dng: Theo AC-22 n
AS 3947.1.
Degree of protection
At least the degree of protection for the
assembly.
Cp bo v
Ti thiu theo cp bo v cho t.
Push-buttons
Type: Oil-tight, minimum 22 mm
diameter, or 22 x 22 mm.
Rated operational current: At least 4 A at
240 V a.c.
Marking: Identify functions of each
push-button. For latched STOP or
EMERGENCY STOP push-buttons,
state instructions for releasing latches.
Illuminated push-buttons: Comply with
Indicator lights, in the Measurement
accessories subsection.
Nt nhn
Loi: Khng lt du, ng knh ti
thiu 22 mm, hay 22 x 22 mm.
Dng hot ng nh mc: t nht 4 A,
240V ac.
nh du: nhn bit chc nng ca mi
nt-nhn. Cho cc nt-nhn DNG
KHN CP hay DNG b gi, ch
ra cch nh trng thi gi.
Nt nhn c n sng: Tun theo tiu
chn phn Ph kin o lng v n
ch th.
Rotary switches
Provision: Provide rotary action AUTO-
OFF-MANUAL switch for each item of
equipment. Mount on the fascia of the
control panel underneath the relevant
pilot lights.
Type: Cam operated type with switch
positions arranged with displacement of
60.
Off position: Locate at the 12 oclock
position. Test positions must spring
Cng tc xoay
Cung cp: Cung cp cc cng tc xoay
cc v tr T NG-NGT-BNG
TAY cho mi hng mc thit b. Gn
trn mt t pha di n ch th lin
quan.
Loi: Loi vn hnh cam vi v tr cng
tc c b tr gc quay 60.

V tr ngt: t ti v tr 12 gi. V tr
th nghim bt buc phi quay v v tr

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 16 of 27 of C.05 19 September 2007
return to off position.
Rated operational current: At least 6 A at
230 V a.c.
Escutcheon plates: Provide rectangular
plates securely fixed to the assembly
panel. Identify switch position and
function.
ngt bng l xo.
Dng hot ng nh mc: Ti thiu 6
A, 230V ac.
Np che: Cung cp cc bng hnh ch
nht c gn chc chn vo t in,
Ghi r v tr ng ngt v chc nng.
Time switches - dial type
Operation: 7 day with synchronous
motor or electronically controlled drive
from 240 V 50 Hz supply. Provide day
omit and manual override facilities.
Mains failure operation: Either by
- 24 hour spring; or
- battery with 100 hour minimum
operating capacity and guaranteed 10
year minimum life.

Contact rating: 16 A at 240 V a.c.
Construction: Provide readily accessible
means of adjustment. Provide
operational settings which are clearly
visible when switch cover is fitted.
Dial: Either analogue with 2 hands, or
digital with hour and minute display.
Cng tc thi gian - loi mt s.
Hot ng: Trong 7 ngy vi ng c
hot ng ng b hoc iu khin
in t t ngun 240 V, 50 Hz. Cung
cp nhng ngy b b qua v tin ch
ghi chng bng tay.
Vn hnh khi mt ngun chnh: Bng
mt trong hai cch
- L xo 24 gi; hay
- C c quy vn hnh t nht 100 gi
v bo hnh ti thiu 10 nm.
nh mc cng tc: 16A 240Vac
Cu trc: Cung cp tin ch iu
chnh d dng tip cn. Gi tr ci t
c nhn thy r rng khi np t c
gn.
Mt s: Mt trong hai: tn hiu
analogue bng 2 kim, hay tn hiu s
vi hin th gi v pht.
Proximity switches
To AS/NZS 3947.5.2.
Cng tc khng tip xc
Theo AS/NZS 3947.5.2.
3.14 CONTROL RELAYS 3.14 R LE IU KHIN
Standard
To AS/NZS 3947.5.1.
Tiu chun
Theo AS/NZS 3947.5.1.
Operation
Suitable for continuous operation. Select
relays in compliance with the Control
relay section table.
Vn hnh
Ph hp vi iu kin vn hnh lin
tc. La chn r le theo bng r le iu
khin.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 17 of 27 of C.05 19 September 2007
Control relay selection table
Bng role iu khin
Relay type
Loi r le
Min. mech.
Life (million
operations)
Tui th c
nh nht
(Triu ln vn
hnh)
Base
Chn
Min. contact
rating
nh mc tip
im nh
nht.
Inter-
changeable
C th hon
i c
Min. no. of
contact
elements
S cc tip
im ca phn
t
1 5 Plug-in
Gn vo
1.25I
L
Yes
C
2
2 10 Plug-in
Gn vo
5 A at/
240 V
Yes
C
2
3 10 Fixed
mounting
Gn c nh
5 A at/
240 V
Yes
C
4

Construction
Latch plug-in types to receptacle bases
with captive clips which can be applied
and released without using tools.
Cu trc
Loi gn c cht gi vo chn c th
thay th c bng cc kp gi m
khng cn dng c khi gn vo v tho
ra.
Contact elements
Type: Electrically separate, double
break, silver alloy, non-welding contacts.
Utilization category:
- Alternating current: AC-15.
- Direct current: DC-13.
Configuration: For standard relays,
provide assemblies with at least 2 sets of
contacts and expandable to 8 sets of
contacts in the same assembly. Provide
at least one normally-open and one
normally-closed contact.
On site conversion: Provide contact
blocks readily convertible to either
normally-open or normally-closed
contacts.
Phn tip im
Loi: Tip im khng hn, hp kim
bc, ngt kp, tch ring v in.
Phn loi s dng:
- Dng xoay chiu: AC-15.
- Dng mt chiu: DC-13.
Cu trc: i vi r le tiu chun, cung
cp cu kin vi t nht 2 cp tip im
v c th m rng n 8 cp tip im
trn cng mt cu kin. Cung cp t
nht mt tip im thng m, mt tip
im thng ng.
Chuyn i ti cng trng. Cung cp
nhng khi c th chuyn i nhanh ti
cng trng sang tip im thng m
hay tip im thng ng.
Time delay relays
Adjustable over the full timing range
with timing repeatability within 12.5%
of nominal setting.
R le thi gian tr
C th chnh c trn ton b di thi
gian, vi chia thi gian trong
khong 12.5% ca ci t nh nht.
Electronic relays
Incorporate light emitting diodes
indicating energisation states of relays.
R le in t
Kt hp vi n iot pht sng ch
trng thi hot ng ca r le.
Pneumatic relays
Provide sealed chamber type with
internal circulating air with linear
calibrated time adjustment.
R le chy bng kh
Cung cp cc r le loi bung kn vi
s tun hon kh bn trong v cn chnh
thi gian tuyn tnh.
Synchronous relays
Provide synchronous motor drive type
relay fitted with anti-stalling device
which protects gearing during normal
operation.
R le ng b
Cung cp cc r le loi truyn ng
ng c ng b vi dng c chng
kt, dng c ny s bo v cc bnh
rng trong thi gian vn hnh bnh
thng.
Earth fault relay
Provide earth fault relay and associated
R le chng chm t
Cung cp r le chng chm t v cc

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 18 of 27 of C.05 19 September 2007
current measuring devices which trip the
mains power supply when an earth
leakage exceeds a set value. Adjustable
setting from .1A to 3 A, initially set at
0.5A.
dng c o lng kt hp ngt ngun
in chnh khi dng chm t vt qu
gi tr ci t iu chnh c t 0.1A
n 3A, ci t ban u 0.5A.
Undervoltage/Overvoltage relay
Provide OV/UV relay set to trip at +/-
10% of the voltage.
R le qu in p/ di in p
Cung cp r le Qu in p/ Di in
p ci t mc ngt ti +/-10% in p.
Phase failure relays
General: Provide separate solid-state
phase failure relays which release at
- 85% of normal voltage;
- single phase failure; or
- Reverse phase sequence after an
appropriate time delay.
Sensing circuit: Rejects induced voltage
spikes, and disturbances with
frequencies other than 50 Hz.
Back-up protection: Provide high
rupturing capacity fuses to each phase.
R le mt pha
Tng qut: Cung cp cc r le mt pha
bn dn, nh ti:
- 85% in p bnh thng;
- mt mt pha, hay
- i th t pha sau mt thi gian ch
tng ng.
Dng cm ng: khng nhn cc xung
in p cm ng vo, v s nhiu sng
vi cc tn s khc 50Hz.
Cung cp cc bo v d phng: Cung
cp cc cu ch dng ngt cao cho mi
pha.
3.15 INDICATING COUNTERS 3.15 B O M
General
Provide the following:
- At least 6 digits.
- Digits at least 3.5 mm high.
- Continuous duty rated.
- Non-reset type.
- 500 V surge diverters.
Tng qut
Cung cp nh sau:
- t nht 6 ch s.
- Chiu cao ch t nht 3.5mm.
- Mc chu ti lin tc.
- Loi khng reset.
- C b x xung in p 500 V.
3.16 EXTRA-LOW VOLTAGE
TRANSFORMERS
3.16 MY BIN IN P THP
C BIT
General
Provide the following:
- Centre tap on secondary winding.
- Primary and secondary windings
wired out on opposite sides of
transformer case.

- Primary and secondary windings
separated by means of an earthed
screen wired out to an insulated
terminal.
- Output loading 80% of transformer
continuous rating, taking account of
degree of ventilation and ambient
temperature within assembly, and
supplied load.
Tng qut
Cung cp nh sau:
- u chnh in p gia cun dy
th cp.
- Ni u dy cun th cp v cun s
cp trn v tr i nhau ca v my
bin p.
- Cun dy s cp v cun dy th cp
c tch ring bit bng mt mng
tip t ni ra n mt u cch in.

- Ti u ra 80% ca nh mc lin
tc ca my bin p, c tnh n cp
thng gi v nhit mi trng
bn trong thit b, v ti ngun.
3.17 SEMICONDUCTOR
CONTROLLERS AND
CONTACTORS
3.17 CNG TC T V B IU
KHIN BNG BN DN.
General
General: Provide semiconductor
controllers and contactors rated for the
characteristics of the controlled load.
Tng qut
Tng qut: Cung cp b iu khin
bng bn dn v cng tc t c nh
mc theo c tnh ca ti cn iu

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 19 of 27 of C.05 19 September 2007
Standard: To AS/NZS 3947.4.3. khin.
Tiu chun: Theo AS/NZS 3947.4.3.
3.18 CONTROLLER DEVICE
INTERFACES
3.18 GIAO DIN GIA CC DNG
C IU KHIN.
General
Provide interfaces between equipment
and control systems including the
following:
- Programmable logic controllers.
- Metering systems.
- Building management systems.
Standard: To AS/NZS 62026.1,
AS/NZS 62026.2, AS/NZS 62026.3 and
AS/NZS 62026.5.
Actuator sensor interface: To
AS/NZS 62026.2.
Provide control system components with
an actuator sensor interface: The actuator
sensor interface may be integrated into
field devices, or be used in separate
modules.
Devicenet: Provide control system
components with a devicenet connection
based controller-device interface,
suitable for use on a Controller Area
Network to AS/NZS 62026.3.


Smart distributed system (SDS): Provide
control system components with a SDS
controller-device interface, suitable for
use on a Controller Area Network to
AS/NZS 62026.5.

Seriplex: Provide a Seriplex interface
and communications system between
single or multiple controllers and control
circuit devices or switching elements.
Tng qut
Cung cp cc giao din gia cc thit b
v h thng iu khin bao gm cc
mc sau:
- Cc b PLC.
- H thng o lng.
- H thng qun l to nh.
Tiu chun: Theo AS/NZS 62026.1,
AS/NZS 62026.2, AS/NZS 62026.3 v
AS/NZS 62026.5.
Giao din cm bin tc ng: Theo
AS/NZS 62026.2.
Cung cp cc phn iu khin h thng
vi cc giao din cm bin tc ng:
Cc giao din cm bin tc ng c
kt hp thnh mt th thng nht trong
cc dng c lp ti ch, hay c s
dng trong cc modun ring.
Mng cp thp ni cc thit b: Cung
cp cc cu kin iu khin h thng
vi giao din gia cc b iu khin
dng c da trn kt ni mng cp
thp, thch hp s dng cho Mng iu
khin Khu vc theo AS/NZS 62026.5.
H thng phn phi thng minh (SDS):
Cung cp cc cu kin h thng iu
khin vi giao din gia dng c - phn
iu khin SDS, thch hp s dng cho
Mng iu khin Khu vc theo
AS/NZS 62026.5.
ng dn Seriplex: Cung cp mt
giao din Seriplex v h thng lin lc
gia iu khin n, a v dng c
mch iu khin hay cc nguyn t
ng ngt.
3.19 ALARM ANNUNCIATORS 3.19 BNG BO NG
General
Provide the following:
- Labelled annunciator illuminated
windows, to indicate status and alarm
conditions.
- Lamp test acknowledge-mute and
reset individual push-buttons.
- Audible alarm and associated logic
circuitry.
Tng qut
Cung cp nh sau:
- Cc ca s pht sng bng thng bo
c ghi nhn, ch tnh trng v iu
kin bo ng.
- n kim tra thng bo-cm v nt
nhn ring tr li trng thi c.
- Bo ng c th nghe thy c v
mch lgic kt hp.
Mode of operation
General: Provide the following
functions:
- Fault conditions: To initiate flashing
of appropriate annunciator lamps and
sounding of audible alarms.
- Operation of acknowledge mute
buttons: To silence audible alarms and
Phng thc vn hnh
Tng qut: Cung cp cc chc nng
nh sau:
- iu kin ngn mch: Bt u chp
n ca cc n thng bo tng ng
v pht ra bo ng c th nghe thy
c.
- Hot ng ca cc nt nhn thng

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 20 of 27 of C.05 19 September 2007
change annunciator lamps to the
steady state on condition.
- Window: To extinguish only when
fault condition has been cleared and
alarm reset push-button has been
activated.
- Subsequent alarms on other inputs: To
reactivate the audible alarm and flash
the appropriate annunciator lamp.
- Resetting: After correction of the fault
condition, provide on-site choice of
either automatic resetting or manual
resetting at the annunciator panel.
bo cm: tt cc m thanh bo
ng v chuyn n thng bo sang
iu kin n nh.
- Ca s: Ch tt i khi iu kin ngn
mch ht v nt nhn reset bo
ng c bm.
- Bo ng tip theo n cc u vo
khc: khi phc li m thanh bo
ng v lm chp cc n bo ng
tng ng.
- Ci t li: Sau khi chnh sa cc
iu kin ngn mch, cung cp s la
chn ti ch mt trong hai: t ng
ci t li hay ci t li bng tay ti
bng bo ng.
Type
Extra-low voltage, solid state, flush
mounted, window type.
Loi
Loi ca s, gn phng, bn dn, in
p thp-c bit.
Lamps
General: Provide annunciators with 2
extra-low voltage lamps per window.

Rated voltage of lamps: 5% greater than
annunciator system voltage.
Replacing: Changeable from front of
panel without affecting condition of
annunciator.
Vibration: Provide lamps which do not
disconnect due to vibration.
n
Tng qut: Cung cp cc bng bo
ng vi hai n in p thp c bit
cho mi ca s.
nh mc in p ca n: Ln hn
5% in p h thng bng thng bo.
Thay th: D dng thay th n t trc
mt t m khng nh hng n bng
bo ng.
Rung ng: s dng n khng b ngt
do rung ng
Extra-low voltage power supply
Provide an extra-low voltage power
supply for the alarm annunciator.
Ngun in p thp-c bit
Cung cp ngun in p thp-c bit
cho cc b thng bo bo ng.
Windows
Nominal size: 15 x 35 mm.
Engraving: Filled in black.
- Background colours: White for status
monitoring, red for alarms and
shutdown functions.
Ca s
Kch thc danh nh: 15 x 35 mm.
Chm khc: Sn en
- Mu nn: Mu trng cho trng thi
gim st, cho bo ng v chc
nng tt my.
3.20 AUDIBLE ALARM DEVICES 3.20 DNG C BO NG M
THANH
Sound level
At least 65 dB (A) at 1 m and at least
15 dB (A) above ambient sound levels in
designated areas.
Mc m thanh
Ti thiu 65 dB(A) khong cch 1 m
v v ti thiu 15 dB(A) cao trn mc
m thanh xung quanh trong khu vc ch
th.
3.21 BATTERIES AND
CHARGERS
3.21 C QUY V B SC
Standards
Valve regulated sealed lead-acid
batteries: To AS 4029.2.
Vented nickel-cadmium batteries: To
AS 3731.1.
Chargers: To AS 4044 Type 2.
Tiu chun
c qui axt-ch kn bn trong mt
chiu: Theo AS 4029.2.
c qui niken cadmium h: Theo AS
3731.1.
B np: Theo AS 4044 Loi 2.
General
Provide a battery and charger system for
Tng qut
Cung cp c quy v h thng np cho

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 21 of 27 of C.05 19 September 2007
circuit breaker tripping, closing and
automatic changeover switch operation.
Locate within the switchroom.
cc hot ng ngt my ngt, ng v
t ng chuyn i ngun. c t
trong phng t in.
Circuit breaker operation
Provide a d.c. supply for circuit breaker
operation from battery system and
charger.
Hot ng my ngt
Cung cp mt b cp ngun mt chiu
d.c cho hot ng my ngt t ngun c
qui v h thng np.
Performance
General: Capable of 10 consecutive air-
circuit breaker or moulded case circuit
breaker operations for the designated
quantity of circuit breakers. Each
operation consists of open-close of main
contacts for 0.5 s duration, with 1 s
intervals between operations, and
minimum discharge current of 4 A, with
batteries in 50% discharge condition.
Maintain a minimum terminal voltage of
80% of rated voltage at the completion
of the 10 operations.
System voltage: 110 V d.c.
c tnh
Tng qut: C kh nng thc hin 10
hot ng lin tip ca my ngt hay
cc MCCB theo s lng my ngt
thit k. Mi hot ng bao gm cng
tc ng m cc tip im chnh cho
khong thi gian 0.5 giy, vi khong
ngh 1s gia cc hot ng, v dng x
nh nht 4A, vi c qui iu kin cn
50% ngun. Duy tr in p c quy nh
nht bng 80% in p nh mc sau
khi hon thnh 10 ln vn hnh.
H thng in p: 110 V mt chiu d.c.
Safety signs and labels
Standard: To AS 2676.1.
Safety signs: Provide cautionary,
regulatory and emergency safety signs to
charger enclosure and switchroom.
Dn nhn v du hiu an ton
Tiu chun: Theo AS 2676.1.
Du hiu an ton: Cung cp bin cnh
bo, quy nh v an ton khn cp n
v t b np in v phng t in.
3.22 TRANSIENT PROTECTION 3.22 BO V S C BIN I
IN LN
Standards
Main assemblies connected to the MEN
earthing system: To AS 4070 Category
II.
Main assemblies not connected to the
MEN earthing system: To AS/NZS 1768
Category C.
Distribution boards: To AS/NZS 1768
Category B.
Tiu chun
Cc thit b chnh c kt ni vo h
thng tip t MEN: Theo AS 4070
loi II.
Nhng thit b chnh khng kt ni n
h thng tip t MEN: Theo
AS/NZS 1768 Loi C.
T phn phi in: Theo AS/NZS 1768
Loi B.
Primary protection
Provide shunt connected metal oxide
varistors at assembly incoming supply
terminals, on the line side of incoming
functional units.
Bo v s cp
Cung cp in tr shunt mc r vo
bin tr oxide kim loi ti u vo cp
ngun chnh, trn ng dy ca thit
b chc nng vo.
Secondary protection
Provide metal oxide varistors or zener
diode surge protection to assembly in-
built equipment and semi-conductor
components which are not able to
withstand transient overvoltages
exceeding primary protection let-through
residual levels.
Bo v th cp
Cung cp bin tr oxt kim loi hay bo
v dit zener cho cc cu kin bn
trong thit b v cc cu kin trong bn-
dn, m cc cu kin trong bn dn ny
khng th chu c xung in p bin
i in ln, in p nay vt qu bo
v phn s cp mc in p r
xuyn qua.
Components
Short-circuit protective devices and
isolators: Back-up each arrestor active
supply with a live side 32 A totally
enclosed fault current limiting fuse.
Provide 32 A multi-pole automatic
miniature circuit breaker on load side of
Cu kin
Dng c bo v ngn mch v cu dao
cch ly: D phng mt b thu st cho
pha ngun bao gm cu ch gii hn
dng ngn mch chnh kn hon ton
vi cng sut 32A. Cung cp mt MCB
32A nhiu cc sau u ti ca cu ch,

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 22 of 27 of C.05 19 September 2007
fuses, as an arrestor isolator.
Cables:
- Maximum length between main circuit
supply active and associated fuse,
isolator, arrestor, neutral and earth
conductor connections including MEN
link: 1 m.
- Maximum length between earth
conductor and earth grid/electrode
system: 5 m.
- Installation: Keep cables as short and
straight as practicable with line and
load side separately bunched 300 mm
apart.
Minimum cable size: 6 mm
2
copper.

Surge arrestor enclosures: Totally
ventilated sheet metal wall boxes with
hinged covers, mounted within or on the
wall next to designated assemblies,
containing grouped surge arrestors.
Marking: Label each group of primary
arrestors, stating their purpose and the
necessary characteristics.
nh l mt cu dao cch b ly st.
Dy cp:
- Chiu di ln nht gia mch cp
ngun chnh n cu ch, cu dao, b
thu st, cc kt ni dy trung tnh v
tip t bao gm c lin kt MEN:
1m.
- Chiu di ln nht gia dy t v h
thng li/cc tip t: 5m.

- Lp t: Gi cc cp ny ngn v
thng nht c th c vi cch
khong t pha ti v pha ngun b
ring l cch nhau 300mm.
Kch thc cp nh nht: Bng ng
6mm2.
V b thu xung st: Dng hp bng tn
kim loi gn trn tng c thng gi,
ca bn l, gn trn tng gn hay bn
trong thit b c ch nh, chamt
nhm cc b thu xung st.
nh du: Dn nhn mi nhm cc b
thu xung st phn s cp, ghi ra cc
mc ch ca chng v cc c tnh cn
thit.
3.23 POWER FACTOR
CORRECTION
3.23 IU CHNH H S CNG
SUT
Condensers
Provide condensers in compliance with
IEC standards.
Capacitors shall be three phase, indoor,
self-healing dry/dielectric oil insulation
(non-PCB) type, with internal fuse/
protective device and external discharge
resistor. Provide illuminated indicator
for each condenser step.
T in
Cung cp cc t in ph hp vi tiu
chun IEC.
T in loi 3 pha, trong nh, t xy-
kh/cch in bng du in mi
(khng s dng PCB), vi dng c bo
v/cu ch bn trong v in tr x
ngoi. Cung cp ch th pht sng cho
mi bc ng t in.
Control
Provide control via a digital power factor
controller, with a touch panel for
automatic operation and manual
override, and readout of phase angle or
power factor, volts, amps, kW, kVAR,
kVA.
Power factor can be set adjustable from
0.8 to 1
iu khin
Cung cp phn iu khin qua b iu
khin h s cng sut k thut s, vi
bn phm bm trn t cho hot ng t
ng, iu chnh bng tay u tin, v
th hin gc pha hay h s cng sut,
in p, dng in, kW, kVAR, KVA.
H s cng sut c th ci t iu
chnh c t 0.8 n 1.
Installation
Condensers are to be earthed.
Circuit protection is to be provided for
individual condensers.
A single switch or circuit breaker is to be
provided to disconnect all condensers.
A means of condenser discharge via an
appropriately sized dissipation resistor is
to be installed, which is connected in
series when now power is available.
Lp t
T in c tip t.
Mch bo v c cung cp cho mi t
ring bit.
Mt cu dao hay mt my ngt c
cung cp ngt tt c cc t in.
Mt tin ch x t ngang qua mt in
tr tiu hao cng sut tng ng
c lp t, cc in tr ny c
mc ni tip khi ngun c th c.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 23 of 27 of C.05 19 September 2007
3.24 MOTOR ISOLATING
SWITCHES
3.24 DAO CT NG NGT
NG C
General
Motor isolators: Provide an isolating
switch for each motor to break all active
conductors. Mount either adjacent to the
motor or, provided the switchboard is
within sight of the motor, located in the
control switchboard.
Operation: Select from the following:
- Operating through the motor control
circuit.
- Operating in all active conductors and
rated so as to be capable of making
and breaking the full load current of
the motor.
- Where isolator is for a fire and life
safety purpose ie stair case
pressurisation, smoke exhaust fan, fire
pump etc, provide switch position
contacts and fire rated wiring to the
fire indication panel or fire fan control
panel as appropriate.
Tng qut
Dao ct ng c: Cung cp cng tc
ng ngt cho mi mt ng c ngt
tt c cc dy pha. Gn mt trong hai
cch gn ng c hay t t in trong
tm nhn ca ng c, t trong t in
iu khin.
Vn hnh: La chn nh sau:
- Vn hnh thng qua mch iu khin
ng c
- Vn hnh trn tt c cc dy pha v
c nh mc sao cho c kh nng
ng ngt dng y ti ng c.
- Ti nhng ni m dao ct nhm mc
ch ngt khi chy v cc mc ch
an ton tnh mnh nh qut ht khi,
qut tng p cu thang, bm cha
chy v.v.., cung cp nhng tip im
v tr cng tc ng ngt v i cp
chng chy n t bo chy hay t
iu khin qut khi chy cho ph
hp.
4 EXECUTION 4 THI CNG
4.1 MARKING AND LABELLING 4.1 NH DU V DN NHN
General
Provide labels including control and
circuit equipment ratings, functional
units, notices for operational and
maintenance personnel, incoming and
outgoing circuit rating, sizes and origin
of supply and kW ratings of motor
starters.
Tng qut
Cung cp nhn bao gm nh mc cho
thit b iu khin v mch in, thit
b chc nng, cc ghi ch cho nhn
vin vn hnh v bo tr, nh mc
dng in vo v dng in ra, kch c
v ngun cp, v nh mc kW cho b
khi ng ng c.
Identifying labels
Provide labels fixed to access panels,
doors, covers and escutcheon panels and
internal equipment, indicating the
relevant worksection and component.
Nhn nhn dng
Cung cp nhn gn trn li vo t, ca
t, np che, trn mt t in v cc thit
b bn trong, ch ra cc cu kin trong
v cc cu kin lm vic.
Minimum lettering heights
Main assembly designation: 25 mm.
Distribution assembly designations:
15 mm.
Small proprietary distribution boards:
10 mm.
Main switches: 10 mm.
Outgoing functional units: 8 mm.
Identifying labels (on outside of cabinet
rear covers): 4 mm.
Danger, warning and caution notices:
10 mm for main heading, 5 mm for
remainder.
Other labels including equipment labels
within cabinets: 3 mm.

Chiu cao ch nh nht
Tn thit b chnh: 25 mm.
Tn thit b phn phi: 15 mm.
T phn phi nh sn xut c quyn:
10 mm.
Dao ct chnh: 10 mm.
Thit b chc nng u ra: 8 mm.
Dn nhn nhn dng (Bn ngoi mt
bn ca t): 4 mm.
Ghi ch nguy him, bo hiu v cnh
bo: 10 mm cho tiu , 5 mm cho
phn cn li.
Cc nhn khc bao gm nhn cho thit
b bn trong t in: 3 mm.

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 24 of 27 of C.05 19 September 2007
Label colours
Generally: Black lettering on white
background.
Main switch and caution labels: Red
lettering on white background.
Danger, warning labels: White lettering
on red background.
Mu nhn
Tng qut: Ch en trn nn trng.
Nhn ghi ch v dao ct chnh: Ch
trn nn trng.
Nhn cnh bo, nguy him: Ch trng
trn nn .
Fixing
General: Fix labels securely.
Method: Select from the following:
- Screws and double-sided adhesive.
- Fixed in extruded aluminium sections
fixed to panels with rivets or
countersunk screws.
Aluminium labels: Aluminium or monel
rivets.
Restrictions: Do not provide self-tapping
or thread-cutting screws.
Gn nhn
Tng qut: Gn nhn chc chn.
Phng php: La chn sau y:
- Bt vt v dn dnh hai mt
- Gn trn ming nhm bt vo t in
bng inh vt hay vt chm.
Nhn bng nhm: inh tn bng hp
kim monel hay nhm.
Gii hn: Khng c dng bng ko-
dn hay vt ct ren vo t.
Set-out
Align horizontally and vertically with
adjacent labels.
Sp t
Cn chnh nhn ngay ngn theo hng
ngang v dc.
Labels on assembly exteriors
Manufacturers name: Required.
Assemblies: Label with essential
markings.

Designation labels: For other than main
assemblies, provide designation label
stating source of electrical supply.
Identify separate sections of enclosures.
Assembly controls: Label controls and
fault current limiters, including the
following:
- Circuit designation for main switches,
main controls and submains controls.
- Details of consumers mains and
submains.
- Incoming busbar or cable rating to
first tee-off.
- Fuse link size.
Dn nhn cho bn ngoi t.
Tn nh sn xut: Yu cu
T: Dn nhn vi cc nh du chnh.
Nhn t tn: Cho cc thit b chnh
khc, cung cp nhn t tn ch ra
ngun cung cp chnh. Dn nhn tn
cc ngn ring ca v t.
T iu khin : Dn nhn cho b gii
hn dng ngn mch v iu khin, bao
gm nh sau:
- Tn mch cho dao ngt chnh, mch
iu khin chnh v mch iu khin
ph.
- Chi tit ngun ti v ngun ph.
- nh mc dy cp hay thanh ci vo
n b chia ngun u tin.
- Kch c dy cu ch.
Labels on assembly interiors
General: Provide labels for equipment
within assemblies. Locate so that it is
clear which equipment is referred to, and
lettering is not obscured by equipment or
wiring.
Moulded case circuit breakers: If circuit
breaker manufacturers markings are
obscured by operating handle
mechanisms or motor operators, provide
additional markings open to view on or
next to the circuit breaker.
Dn nhn cho cc cu kin bn trong
Tng qut: Cung cp cc nhn cho cc
thit b bn trong cu kin lp rp. Lp
t bn trong thit b c ni n, v
ch th khng c che khut bi thit
b hay dy dn.
My ngt MCCB: Nu nhn ca nh
sn xut my ngt b che khut bi c
cu tay cm vn hnh hay ngi vn
hnh ng c, th cung cp nhn ph
m ra n tm nhn trn my ngt k
cnh.
Danger, warning and caution notices
Busbars: If polymer membrane coating
is used without further insulation,
provide warning notices on the front
cover near the main switch or local main
switch, and on rear covers, indicating
Thng bo nhc nh, cnh bo v
nguy him
Thanh ci: Nu thanh ci c ph lp
plime m khng dng thm cch in,
th cung cp cc nhn cnh bo trn
mt trc gn dao ct chnh hay dao ct

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 25 of 27 of C.05 19 September 2007
that busbars are not insulated.

Fault current limiters: In assembly
sections containing fault current limiter
fuses provide caution notices fixed next
to the fault current limiters, stating that
replacement fuse links are to match as-
installed fuse link ratings, make and
characteristics. Provide separate label
stating fault current limiting fuse ratings.

Externally controlled equipment: To
prevent accidental contact with live
parts, provide warning notices for
equipment on assemblies not isolated by
main switch or local main switch.

Stand-by power: Provide warning
notices stating that assemblies may be
energised from the stand-by supply at
any time.
Anti-condensation heaters: To prevent
accidental switching off, provide caution
notices for anti-condensation heaters.

Custom-built assemblies: For insulation
or shrouding requiring removal during
normal assembly maintenance, provide
danger notices with appropriate wording
for replacement of insulation shrouding
before re-energising assemblies.

Positioning: Locate notices so that they
can be readily seen, next to or, if
impracticable, on busbar chamber covers
of functional units, and behind the front
cover of functional units. Provide circuit
identification labels in the cabling
chamber of each functional unit, located
next to external terminations.
cc b, v trn mt sau ch ra rng
thanh ci khng c cch in.
B gii hn dng ngn mch ln nht:
Trn cu kin lp rp c cha cu ch
gii hn dng ngn mch cung cp
nhng thng bo nhc nh cho b gii
hn dng ngn mch, ghi ra rng vic
thay th cu ch phi tng ng vi
nh mc v c tnh cu ch c
lp t. Cung cp cc nhn ring ch ra
nh mc cu ch ca b gii hn dng
ngn mch.
Thit b iu khin ngoi: ngn
nga cc tip xc nguy him vi cc
phn t c in, cung cp cc nhn
cnh bo cho cc thit b trong t
khng c cch ly bi dao ct chnh
hay bi dao ct cc b.
Cng sut d phng: Cung cp nhn
cnh bo r trn cc cu kin c th c
in vo t t ngun d phng ti bt
k lc no.
B sy chng ngng t: Nhm ngn
nga ri ro tt ngun cp, cung cp
nhn cnh bo cho b sy chng ngng
t.
Cc thit b lp rp theo s t hng
ring: i vi cch in hay s bao bc
c yu cu tho ra trong khi bo tr
thng thng, cung cp cc bng cnh
bo nguy him vi cc t ng din t
ph hp ch ra rng phi thay th cch
in trc khi ng in tr li cc cu
kin.
V tr: t cc cnh bo sao cho chng
d dng c nhn thy, gn vi hay l,
nu khng th thi hnh c, trn np
bung thanh ci ca cc thit b chc
nng, v pha sau np y pha trc
ca cc thit b chc nng. Cung cp
nhn ng du tn mch trn bung i
cp ca mi thit b chc nng, t gn
u cp bn ngoi.
Signage
Allow for co-ordination with the
Architect & Interior Designer for the
following signage:
- "DANGER" notice, to be positioned
on the Main LV switchboards.
- "NO ADMITTANCE" notice, to be
positioned on the outside face of the
door to the switchrooms and electrical
risers.
Provide 1 no., Shock Treatment Card, to
be hung in prominent position on the
wall of the switchrooms.
Bin tn hiu
Cho php phi hp vi Kin trc s &
Nh thu trang tr ni tht cho cc bin
tn hiu sau:
- Ghi ch "NGUY HIM", oc gn
trn t in tng.
- Ghi ch KHNG UC VO,
c gn trn mt ngoi ca vo
phng t in hay trc in thng
tng.
Cung cp mt Bng X L in Git
c treo v tr d thy trn tng ca
phng t in.
Schedule cards
General: For general light and power
distribution boards, provide schedule
cards of minimum size 200 x 150 mm,
with typewritten text showing the
following as-installed information:
Bng s mch
Tng qut: Cho tt c t phn phi
ng lc v t chiu sng, cung cp
bng s kch c 200 x 150 mm, vi
ch nh my ch ra cc thng tin c
lp t nh sau:

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 26 of 27 of C.05 19 September 2007
- Submain designation, rating and short-
circuit protective device.
- Light and power circuit numbers and
current ratings, cable sizes and type
and areas supplied.
Mounting: Mount schedule cards in a
holder fixed to the inside of the assembly
or cupboard door, next to the distribution
circuit switches. Protect with hard plastic
transparent covers.
- Tn, nh mc v dng c bo v
ngn-mch mch nhnh, .
- nh mc dng v s th t mch
ng lc v chiu sng, loi v kch
c dy cp v khu vc c cung
cp.
Gn: Gn bn s mch trn gi gi
s mch c gn bn trong cc cu
kin hay ca t tng, gn vi dao ct
ca t phn phi. Bo v trong v nha
do cng trong sut.
Single-line diagrams
Custom-built assemblies: Provide single-
line diagrams.
Format: Non-fading print, at least A3
size, showing the as-installed situation.
Mounting: Enclose in a non-reflective
glazed metal frame and wall mount close
to assembly.
S n tuyn
Cc cu kin lp rp theo n t hng
ring: Cung cp cc s n tuyn.
nh dng: Ch in khng b m, ti
thiu kh A3, ch ra tnh trng c
lp t.
Gn: Gn trn khung kim loi khng b
chi v c gn trn tng gn v tr
thit b.
Marking cables
Identify the origin of all wiring by means
of legible indelible marking.
Identification labels: Provide durable
labels fitted to each core and sheath,
permanently marked with numbers,
letters or both to suit the connection
diagrams.
Multicore cables and trefoil groups:
Identify multicore cables and trefoil
groups at each end with durable non-
ferrous tags clipped around each cable or
trefoil group.
nh du cp
nh du ngun gc ca tt c cc dy
dn bng ch r rng khng ty xa.
Nhn t tn: Cung cp cc nhn lu
bn gn vo mi li v v dy dn vi
ch, s hay c ch s ph hp vi s
ni dy.

Cp nhiu li v nhm cp tre-foil:
nh du cp nhiu li hay nhm cp
tre-foil ti mi u bng nhn khng-
kim loi kp xung quanh mi li dy
cp hay nhm cp tre-foil.
5 COMPLETION 5 HON TT
5.1 TRAINING 5.1 O TO
Programmable logic controllers
Make available one programmer and
submit associated instruction manual 5
days before start of operator training.
iu khin logic c th lp trnh
c PLC
Chun b sn mt thit b lp trnh v
cung cp cng vi s tay hng dn 5
ngy trc khi bt u chng trnh
hun luyn.
5.2 COMPLETION TESTS 5.2 TH NGHIM HON TT
General
Carry out the following tests:
- Electrical operation.
- Dielectric.
Tng qut
Thc hin cc th nghim sau:
- Hot ng in.
- Cht cch in.
5.3 MAINTENANCE 5.3 BO TR
General
General: Carry out the following:
- Monthly inspections and maintenance
work to maintain the assembly,
including battery systems.
- Rectify faults, make adjustments, and
replace consumable and faulty
Tng qut
Tng qut: Thc hin nh sau:
- Thc hin bo tr v kim tra hng
thng duy tr tt cc thit b, bao
gm c h thng c quy.
- Sa cha cc li, thc hin iu
chnh v thay th nhng vt liu b li

SWITCHBOARD COMPONENTS
The English language version prevails. u tin phn Anh ng khi c tranh chp.
Centrepoint Page 27 of 27 of C.05 19 September 2007
materials and equipment within 24
hours of notification.
Standard: To AS 2467.
hay ht hn s dng trong vng 24
gi khi nhn thng bo.
Tiu chun: Theo AS 2467.