Professional Documents
Culture Documents
EHYHBH-AV32, EHYHBX-AV3 - Installation Manual - 4PEN349587-1G - English
EHYHBH-AV32, EHYHBX-AV3 - Installation Manual - 4PEN349587-1G - English
EHYHBH05AF
EHYHBH08AF Installation manual
English
EHYHBX08AF Daikin Altherma hybrid heat pump – heat pump module
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions: 08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de 16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß acordo com as nossas instruções: 17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami:
unseren Anweisungen eingesetzt werden: 09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям: 18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: 10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser: instrucţiunile noastre:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze 11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att 19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
instructies: användning sker i överensstämmelse med våra instruktioner: 20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras 12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i 21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции:
instrucciones: henhold til våre instrukser: 22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni: 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: 23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
07 είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται 14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům: 24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade s našim
σύμφωνα με τις οδηγίες μας: 15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: návodom:
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01 following the provisions of: 10 under iagttagelse af bestemmelserne i: 19 ob upoštevanju določb: 01 Directives, as amended. 10 Direktiver, med senere ændringer. 18 Directivelor, cu amendamentele respective.
02 gemäß den Vorschriften der: 11 enligt villkoren i: 20 vastavalt nõuetele: 02 Direktiven, gemäß Änderung. 11 Direktiv, med företagna ändringar. 19 Direktive z vsemi spremembami.
03 conformément aux stipulations des: 12 gitt i henhold til bestemmelsene i: 21 следвайки клаузите на: 03 Directives, telles que modifiées. 12 Direktiver, med foretatte endringer. 20 Direktiivid koos muudatustega.
04 overeenkomstig de bepalingen van: 13 noudattaen määräyksiä: 22 laikantis nuostatų, pateikiamų: Low Voltage 2014/35/EU 04 Richtlijnen, zoals geamendeerd. 13 Direktiivejä, sellaisina kuin ne ovat muutettuina. 21 Директиви, с техните изменения.
05 siguiendo las disposiciones de: 14 za dodržení ustanovení předpisu: 23 ievērojot prasības, kas noteiktas: 05 Directivas, según lo enmendado. 14 v platném znění. 22 Direktyvose su papildymais.
06 secondo le prescrizioni per: 15 prema odredbama: 24 održiavajúc ustanovenia: Electromagnetic Compatibility 2014/30/EU * 06 Direttive, come da modifica. 15 Smjernice, kako je izmijenjeno. 23 Direktīvās un to papildinājumos.
07 με τήρηση των διατάξεων των: 16 követi a(z): 25 bunun koşullarına uygun olarak: 07 Οδηγιών, όπως έχουν τροποποιηθεί. 16 irányelv(ek) és módosításaik rendelkezéseit. 24 Smernice, v platnom znení.
08 de acordo com o previsto em: 17 zgodnie z postanowieniami Dyrektyw: 08 Directivas, conforme alteração em. 17 z późniejszymi poprawkami. 25 Değiştirilmiş halleriyle Yönetmelikler.
09 в соответствии с положениями: 18 în urma prevederilor: 09 Директив со всеми поправками.
01 Note* as set out in <A> and judged positively by <B> 06 Nota* delineato nel <A> e giudicato positivamente da <B> 11 Information* enligt <A> och godkänts av <B> enligt 16 Megjegyzés* a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z) 21 Забележка* както е изложено в <A> и оценено положително от <B>
according to the Certificate <C>. secondo il Certificato <C>. Certifikatet <C>. <C> tanúsítvány szerint. съгласно Сертификата <C>.
02 Hinweis* wie in <A> aufgeführt und von <B> positiv 07 Σημείωση* όπως καθορίζεται στο <A> και κρίνεται θετικά 12 Merk* som det fremkommer i <A> og gjennom positiv 17 Uwaga* zgodnie z dokumentacją <A>, pozytywną 22 Pastaba* kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal
beurteilt gemäß Zertifikat <C>. από το <B> σύμφωνα με το Πιστοποιητικό <C>. bedømmelse av <B> ifølge Sertifikat <C>. opinią <B> i Świadectwem <C>. Sertifikatą <C>.
03 Remarque* tel que défini dans <A> et évalué positivement par <B> 08 Nota* tal como estabelecido em <A> e com o parecer positivo 13 Huom* jotka on esitetty asiakirjassa <A> ja jotka <B> 18 Notă* aşa cum este stabilit în <A> şi apreciat pozitiv de <B> 23 Piezīmes* kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam <A> DAIKIN.TCF.025J07/10-2020
conformément au Certificat <C>. de <B> de acordo com o Certificado <C>. on hyväksynyt Sertifikaatin <C> mukaisesti. în conformitate cu Certificatul <C>. saskaņā ar sertifikātu <C>.
04 Bemerk* zoals vermeld in <A> en positief beoordeeld door <B> 09 Примечание* как указано в <A> и в соответствии с положительным 14 Poznámka* jak bylo uvedeno v <A> a pozitivně zjištěno 19 Opomba* kot je določeno v <A> in odobreno s strani <B> 24 Poznámka* ako bolo uvedené v <A> a pozitívne zistené <B> v súlade <B> DEKRA (NB0344)
overeenkomstig Certificaat <C>. решением <B> согласно Свидетельству <C>. <B> v souladu s osvědčením <C>. v skladu s certifikatom <C>. s osvedčením <C>.
05 Nota* como se establece en <A> y es valorado 10 Bemærk* som anført i <A> og positivt vurderet af <B> i henhold til 15 Napomena* kako je izloženo u <A> i pozitivno ocijenjeno od strane 20 Märkus* nagu on näidatud dokumendis <A> ja heaks kiidetud 25 Not* <A>’da belirtildiği gibi ve <C> Sertifikasına göre <B> <C> 2082543.0551-QUA/EMC
positivamente por <B> de acuerdo con el Certifikat <C>. <B> prema Certifikatu <C>. <B> järgi vastavalt sertifikaadile <C>. tarafından olumlu olarak değerlendirildiği gibi.
Certificado <C>.
Hiromitsu Iwasaki
Director
Ostend, 1st of February 2021
3P353176-5G
Table of contents
6 Commissioning 21
6.1 Checklist before commissioning................................................ 21
6.2 Checklist during commissioning ................................................ 21
6.2.1 To check the minimum flow rate ................................. 21
6.2.2 To perform an air purge .............................................. 22
6.2.3 To perform a test run .................................................. 22
6.2.4 To perform an actuator test run .................................. 22
6.2.5 To perform an underfloor heating screed dryout......... 22
f g
3 Preparation
a 3.1 Preparing the installation site
300
10 350 500
>500
(mm)
▪ The indoor unit is designed for indoor installation only and for
a Installation manual, operation manual, addendum book for ambient temperatures ranging 5~35°C in cooling mode and
optional equipment, quick installation guide, general safety 5~30°C in heating mode.
precautions, boiler communication cable, reducer
accessory set.
b Connection pieces for the gas boiler 3.2 Preparing water piping
INFORMATION NOTICE
Do NOT throw away the upper cardboard cover. On the In case of plastic pipes, make sure they are fully oxygen
outside of the cardboard cover, the installation pattern is diffusion tight according to DIN 4726. The diffusion of
printed. oxygen into the piping can lead to excessive corrosion.
3.2.1 To check the water volume and flow rate Item Description Wires Maximum
running
Minimum water volume current
Check that the total water volume in the installation is minimum 11 Outdoor ambient 2 (b)
13.5 litre, the internal water volume of the indoor unit NOT included. temperature sensor
(b)
INFORMATION 12 Indoor ambient 2
temperature sensor
In critical processes, or in rooms with a high heat load,
Field supplied components
extra water might be required.
13 Shut-off valve 2 100 mA(b)
NOTICE 14 Electricity meter 2 (b)
When circulation in each space heating/cooling loop is 15 Domestic hot water 2 (b)
NOTICE
3.3 Preparing electrical wiring More technical specifications of the different connections
are indicated on the inside of the indoor unit.
3.3.1 Overview of electrical connections for
external and internal actuators
Item Description Wires Maximum 4 Installation
running
current
Outdoor unit and indoor unit power supply 4.1 Opening the units
(a)
1 Power supply for 2+GND
outdoor unit 4.1.1 To open the switch box cover of the
2 Power supply and 3+GND (g) indoor unit
interconnection cable to 1 Remove the side panel at the right side of the indoor unit. The
indoor unit side panel is fixed at the bottom with 1 screw.
(c)
3 Power supply gas 2+GND
2 Remove the upper and lower screw on the side panel of the
boiler
switch box.
(e)
4 Preferential kWh rate 2
3 The right panel of the switch box will open.
power supply (voltage
free contact) 4 Remove the upper and lower screw on the front panel of the
5 Normal kWh rate power 2 6.3 A switch box.
supply 5 The front panel of the switch box will open.
User interface
(f)
6 User interface 2
Optional equipment
7 3‑way valve 3 100 mA(b)
(d)
8 Domestic hot water 2
tank thermistor
(b)
9 Power supply for drain 2
pan heater
10 Room thermostat/heat 3 or 4 100 mA(b)
pump convector
2×
1 2 3
4 2 Fix the wall bracket to the wall with 2 M8 bolts.
2×
2×
3
When the boiler is installed and access to the switch box is required,
please follow the steps below.
6 Remove the upper and lower screw on the side panel of the
switch box.
7 Remove the switch box from the unit.
8 Hook the switch box to the side of the unit with the hooks
foreseen on the switch box.
30kg
8
6
4 Tilt the top of the unit against the wall at the position of the wall
bracket.
4.2 Mounting the indoor unit 5 Slide the bracket on the back of the unit over the wall bracket.
Make sure the unit is fixed properly. You can additionally fix the
4.2.1 To install the indoor unit bottom side of the unit with 2 M8 bolts.
1 Put the installation pattern (see box) on the wall and follow the 6 The unit is mounted to the wall.
steps as shown below.
NOTICE
Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the
unit.
NOTICE
▪ It is recommended to install shut-off valves to space
heating in and space heating out connections. Shut-off
valves are field supplied. They allow service to the unit
without draining the whole system.
▪ Foresee a drain/fill point to drain or fill the space
heating circuit
4.3 Connecting refrigerant piping
NOTICE
See the installation manual of the outdoor unit for all guidelines,
specifications and installation instructions. Do NOT install valves to shut down the entire emitter
system (radiators, floor heating loops, fan coil units, ...)
instantly if this can result in an immediate short circuit of
4.3.1 To connect the refrigerant piping to the
the water flow between the outlet and the inlet of the unit
indoor unit (for example via a bypass valve). This may trigger an error.
1 Connect the liquid stop valve from the outdoor unit to the 1 Connect the water inlet connection (Ø22 mm).
refrigerant liquid connection of the indoor unit.
2 Connect the water outlet connection (Ø22 mm).
b a
a Water inlet
b Water outlet
3 In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.
NOTICE
Install air purge valves at all local high points.
NOTICE
In case an optional domestic hot water tank is installed: A
pressure relief valve (field supply) with an opening
pressure of maximum 10 bar (= 1 MPa) must be installed
a b
on the domestic cold water inlet connection in accordance
a Refrigerant liquid connection with the applicable legislation.
b Refrigerant gas connection
2 Connect the gas stop valve from the outdoor unit to the 4.4.2 To fill the space heating circuit
refrigerant gas connection of the indoor unit.
Before filling the space heating circuit, the gas boiler MUST be
installed.
1 Flush the installation thoroughly to clean the circuit.
2 Connect the water supply hose to the drain point (field supply).
INFORMATION
When installing field supply or option cables, foresee
sufficient cable length. This will make it possible to remove/
reposition the switch box and gain access to other
components during service.
0.0 mm
3 Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in
contact with the piping and sharp edges. 31
30
CAUTION
Do NOT push or place redundant cable length in the unit.
X2M
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit. 3
2 X1M
1
b a c
X2M
LN 123
LN 123 S1S
a Interconnection cable (=main power supply)
3
2 X1M b Normal kWh rate power supply
1 c Preferential power supply contact
2 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
X5M
If the system is connected to a preferential kWh rate power
supply, a separate normal kWh rate power supply is
required. Change connector X6Y according to the wiring
diagram on the inside of the indoor unit.
INFORMATION
The preferential kWh rate power supply contact is
a connected to the same terminals (X5M/3+4) as the safety
thermostat. It is only possible for the system to have
123
EITHER preferential kWh rate power supply OR a safety
123
thermostat.
Legend: see illustration below.
In case of preferential kWh rate power supply
4.5.3 To connect the user interface 4C From the top 4D From the top centre
▪ If you use 1 user interface, you can install it at the indoor unit (for a a
control close to the indoor unit), or in the room (when used as b b
room thermostat).
▪ If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface
in the room (used as room thermostat). PCB PCB
# Action
1 Connect the user interface cable to the indoor unit.
1× 1×
Fix the cable with cable ties to the cable tie mountings. b
b
X1M
a Notch this part for the wiring to pass through with nippers
etc.
b Secure the wiring to the front part of the casing using the
X5M wiring retainer and clamp.
2
1
4.5.4 To connect the shut-off valve
INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
1 Connect the valve control cable to the appropriate terminals as
b a shown in the illustration below.
7 X2M 7 X2M
6 6
5 5
3 Fix the wallplate of the user interface to the wall.
4 Connect as shown in 4A, 4B, 4C or 4D.
5 Reinstall the faceplate onto the wallplate. X1M X1M
Be careful NOT to pinch the wiring when attaching the
frontplate to the unit.
(a) The main user interface is required for operation, but has to
be ordered separately (mandatory option). X5M X5M
4A From the rear 4B From the left
PCB
PCB
1×
a 1×
b a
b M2S M2S
2 Fix the cable with cable ties to the cable tie mountings.
X1M X1M
8 X5M X5M
7
M2P
M
S2S 1~
2 Fix the cable with cable ties to the cable tie mountings. 2 Fix the cable with cable ties to the cable tie mountings.
4.5.6 To connect the gas meter 4.5.8 To connect the alarm output
1 Connect the alarm output cable to the appropriate terminals as
INFORMATION shown in the illustration below.
In case of a gas meter with transistor output, check the
polarity. The positive polarity MUST be connected to a
X5M/9; the negative polarity to X5M/10.
1 Connect the gas meter cable to the appropriate terminals as 28
A4P
10
9
X5M X1M
A8P
X5M
S3S
2 Fix the cable with cable ties to the cable tie mountings.
4.5.7 To connect the domestic hot water pump a Installation of EKRP1HBAA is required.
1 Connect the domestic hot water pump cable to the appropriate 2 Fix the cable with cable ties to the cable tie mountings.
terminals as shown in the illustration below.
4.5.9 To connect the space cooling/heating ON/
OFF output
1 Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
a
31
30
29
Y2
X2M X2M
A4P
X1M X1M
A8P
X5M
4
3 X5M
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/3+4) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
installation
a Installation of EKRP1AHTA is required.
2 Fix the cable with cable ties to the cable tie mountings. 4.6.1 To close the indoor unit
1 Close the switch box.
4.5.11 To connect the safety thermostat
2 Mount the side plate to the unit.
(normally closed contact)
3 Mount the top plate.
1 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below. NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
5 Configuration
Why 2
H JST
3
If you do NOT configure the system correctly, it might NOT work as 4
expected. The configuration influences the following: 5
Method Column in tables 1 Go to [6.4]: > Information > User permission level.
Accessing settings via the breadcrumb in the # 2 Press for more than 4 seconds.
menu structure. Result: Your user permission level is now Installer. The
For example:
[A.2.1.7] home pages display .
Accessing settings via the code in the Code INFORMATION
overview settings.
For example: [C-07] The Installer permission level switches automatically
back to End user in the following cases:
See also:
▪ If you press again for more than 4 seconds, or
▪ "To access the installer settings" [4 13]
▪ If you do NOT press any button for more than 1 hour
▪ "5.1.3 Menu structure: Overview installer settings" [4 20]
To set the user permission level to Advanced end user
To connect the PC cable to the switch box
1 Go to the main menu or any of its submenus: .
Prerequisite: The EKPCCAB4 kit is required.
2 Press for more than 4 seconds.
1 Connect the USB connector of the cable to your PC.
Result: Your user permission level is now Adv. end user. The
2 Connect the plug of the cable to X10A on A1P of the switch box user interface displays additional information and a "+" is added to
of the indoor unit. the menu title. The user permission level stays in Adv. end user
until manually set otherwise.
To set the user permission level to End user
1 Press for more than 4 seconds.
INFORMATION 2 Push for 4 seconds on the user interface on which you want
An additional 0-digit is added to the first part of the setting to proceed to the quick wizard.
when you access the codes in the overview settings. Result: This user interface is now the main user interface.
Example: [1‑01]: "1" will result in "01". INFORMATION
Overview settings While using the quick wizard on the main user interface,
01 the second user interface displays Busy and you cannot
00 00 01 15 02 00 03 00 interact with it.
04 05 06 07 3 On the display, check if there is a data difference between both
08 09 0a 0b user interfaces.
0c 0d 0e 0f
Confirm Adjust Scroll Result: For proper operation of the system, the local data on
both user interfaces must be the same. If they contain different
3 Go to the corresponding second part of the setting (in this data, both user interfaces will display:
example [1-01]) by using the and button.
Synchronization
Overview settings Data difference detected.
Please select action:
01
00 00 01 15 02 00 03 00
04 05 06 07 Send data
08 09 0a 0b
Confirm Adjust
0c 0d 0e 0f
Confirm Adjust Scroll
4 To make the data equal on both user interfaces, select the
Result: The value to be modified is now highlighted. required action:
4 Modify the value by using the and button. ▪ Send data: the user interface you are operating contains
the correct data. Copy this data to the other user interface.
Overview settings ▪ Receive data: the user interface you are operating does
01 NOT contain the correct data. Copy the data of the other
00 00 01 20 02 00 03 00 user interface to this user interface.
04 05 06 07
5 Confirm to proceed.
08 09 0a 0b
0c 0d 0e 0f Start copy
Confirm Adjust Scroll
Are you sure you want to
start the copy operation?
5 Repeat previous steps if you have to modify other settings.
6 Push to confirm the modification of the parameter.
OK Cancel
7 At installer settings menu, press to confirm the settings.
Confirm Adjust
Installer settings
The system will restart. 6 Push to confirm the displayed selection of data.
Result: All data (languages, schedules etc.) will be copied from the
selected source user interface to the other one. When done, the
system is ready to be operated via both user interfaces.
OK Cancel
Confirm Adjust INFORMATION
▪ As long as data is being copied, you cannot operate
Result: The system will restart. the user interfaces.
To copy the system settings from the first to the ▪ Copying data can take up to 90 minutes.
second user interface ▪ It is recommended to change installer settings, or the
configuration of the unit, on the main user interface. If
If a second user interface is connected, the installer must first not, it can take up to 5 minutes before these changes
proceed below instructions for the proper configuration of the 2 user are visible in the menu structure of the main user
interfaces. interface.
This procedure offers you also the possibility to copy the language
set from one user interface to the other one: e.g. from EKRUCBL2 to To copy the language set from the first to the
EKRUCBL1. second user interface
1 Turn on the unit. See "To copy the system settings from the first to the second user
interface" [4 14].
Quick wizard: Set the system layout after first 5.1.2 Basic configuration
power ON
Quick wizard: Language / time and date
After first power ON of the system, a quick wizard guides you
through the initial configuration of the following system settings: # Code Description
▪ language [A.1] N/A Language
▪ date [1] N/A Time and date
▪ time
Quick wizard: Standard
▪ system layout
Space heating/cooling settings
After you confirmed the system layout, you can proceed with the
installation and commissioning of the system. # Code Description
1 At power ON and as long as the system layout was not [A.2.1.7] [C-07] Unit temperature control:
confirmed yet, select your preferred language. ▪ 0 (LWT control): Unit operation is
decided based on the leaving water
Language temperature.
Select the desired language
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat.
▪ 2 (RT control): Unit operation is
decided based on the ambient
Confirm Adjust temperature of the user interface.
[A.2.1.B] N/A Only if there are 2 user interfaces:
2 Set the current date and time.
User interface location:
Date
▪ At unit
What is the date today?
▪ In room
[A.2.1.8] [7-02] Number of water temperature zones:
Tue 1 Jan 2013
▪ 0 (1 LWT zone): Main
Confirm Adjust Scroll
▪ 1 (2 LWT zones): Main + additional
[A.2.1.9] [F-0D] Pump operation:
Time
What is the current time? ▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition.
00 : 00 ▪ 1 (Sample): When thermo OFF
condition occurs, the pump runs every
Confirm Adjust Scroll 5 minutes and the water temperature
is checked. If the water temperature is
3 Set the system layout settings: Standard, Options, below target, unit operation can start.
Capacities. For more details, see "5.1.2 Basic
▪ 2 (Request): Pump operation based
configuration" [4 15].
on request. Example: Using a room
A.2 System layout 1 thermostat and thermostat creates
Standard thermo ON/OFF condition.
Options
Capacities Quick wizard: Options
Confirm layout
Domestic hot water settings
Select Scroll # Code Description
[A.2.2.1] [E‑05] Domestic hot water preparation:
4 After configuration, select Confirm layout and press .
▪ 0 (No): NOT possible
Confirm layout
▪ 1 (Yes)(default): Possible
Please confirm the system
layout. The system will [A.2.2.2] [E‑06] Domestic hot water production:
restart and will be ready for
first startup. ▪ 0 (Type 1): by boiler
OK Cancel ▪ 1 (Type 2): by tank
Confirm Adjust Note: For Switzerland, setting MUST be
"1".
Result: The user interface reinitializes.
[A.2.2.3] [E‑07] Domestic hot water tank:
5 Proceed with the configuration of the system. When done,
▪ 4 (Type 5). EKHWP.
confirm the configuration settings.
▪ 6 (Type 7) Third-party tank.
Result: The screen shortly turns OFF and Busy is displayed for
several seconds. Range: 0~6.
[0-00]
This is the value by which the desired
leaving water temperature is increased
or lowered.
▪ Tt: Target leaving water temperature When leaving water temperature modulation is enabled,
(additional) the weather‑dependent curve needs to be set to a higher
position than [8-06] plus the minimum leaving water
▪ Ta: Outdoor temperature temperature setpoint required to reach a stable condition
[7.7.2.2] [0‑04] Only for EHYHBX08. Weather- on the comfort setpoint for the room. To increase
dependent curve (cooling): efficiency, modulation can lower the leaving water setpoint.
[0‑05]
Tt By setting the weather‑dependent curve to a higher
[0‑06] position, it cannot drop below the minimum setpoint. See
[0‑07] the illustration below.
[0-05]
Tt
[0-04] +[8-06]
−[8-06]
[0-07] [0-06] Ta
a
▪ Tt: Target leaving water temperature b
(additional)
Ta
▪ Ta: Outdoor temperature
a Weather-dependent curve
Pump control: Flow target b Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
# Code Description room.
N/A [8‑0B] Target flow rate during heat pump Leaving water temperature: Emitter type
operation.
# Code Description
N/A [8‑0C] Target flow rate during hybrid
operation. [A.3.1.1.7] [9‑0B] Emitter type:
N/A [8‑0D] Target flow rate during boiler operation. Reaction time of the system:
▪ 0: (Quick)
INFORMATION
Example: Small water volume and
Changing these settings can result in discomfort. Refer to
fan coils.
the installer reference guide for more information.
▪ 1: (Slow)
Example: Large water volume, floor
heating loops.
Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.
[A.2.2] Options
DHW operation
DHW tank
DHW tank type
Contact type main
Contact type add.
Digital I/O PCB [A.2.2.6] Digital I/O PCB
Demand PCB
External kWh meter Solar kit
DHW pump Alarm output
External sensor
Gas meter
[A.3] Space operation LAN adapter
LWT settings [A.3.1] Leaving water
Room thermostat
Main [A.3.1.1] Main
Operation range
Additional
LWT setpoint mode
Temperature range
[A.3.2] Room thermostat
Modulated LWT
Room temp. range Shut-off valve
Room temp. offset Emitter type
Ext. room sensor offset
Room temp. step [A.3.1.2] Additional
LWT setpoint mode
[A.4] Domestic hot water [A.3.3] Operation range Temperature range
Space heating OFF temp
Type
Space cooling On temp
Disinfection
Maximum setpoint [A.4.4] Disinfection
SP mode Disinfection
Weather-dependent curve Operation day
Start time
Temperature target
Duration
[A.5] Heat sources
Boiler [A.5.2] Boiler
Equilibrium temp.
[A.6] System operation
Auto restart
Preferential kWh rate [A.6.2] Prefer. kWh rate PS
Pwr consumpt. control
Averaging time Forced pump OFF
Ext amb. sensor offset
Forced defrost [A.6.3] Pwr consmp ctrl
Savings mode
Calorific value Mode
Emergency Type
Amp. value
kW value
[A.7] Commissioning Amp. limits for DI
kW limits for DI
Test run
UFH screed dryout
Air purge
Actuator test run
INFORMATION
Depending on the selected installer settings and unit type,
settings will be visible/invisible.
Prerequisite: Make sure that the leaving water temperature home ▪ Shut-off valve test
page, room temperature home page, and domestic hot water home ▪ 3-way valve test
page are turned OFF.
▪ Alarm output test
1 Go to [A.7.3]: > Installer settings > Commissioning >
Air purge. ▪ Cooling/heating signal test
Result: The air purge starts. It stops automatically when done. To ▪ Bypass valve test
stop it manually, press , select OK and press .
INFORMATION
6.2.3 To perform a test run The setpoint during a boiler test run is 40°C. Keep in mind
the 5°C overshoot that is possible during boiler operation,
Prerequisite: Make sure that the leaving water temperature home especially in combination with floor heating loops.
page, room temperature home page, and domestic hot water home
page are turned OFF.
6.2.5 To perform an underfloor heating screed
1 Set the user permission level to Installer. See "To set the user dryout
permission level to Installer" [4 13].
Prerequisite: Make sure there is only 1 user interface connected to
2 Go to [A.7.1]: > Installer settings > Commissioning >
your system to perform an underfloor heating screed dryout.
Test run.
Prerequisite: Make sure that the leaving water temperature home
3 Select a test and press . Example: Heating. page, room temperature home page, and domestic hot water home
4 Select OK and press . page are turned OFF.
Result: The test run starts. It stops automatically when done 1 Go to [A.7.2]: > Installer settings > Commissioning >
(±30 min). To stop it manually, press , select OK and press . UFH screed dryout.
2 Set a dryout program.
INFORMATION
3 Select Start dryout and press .
If 2 user interfaces are present, you can start a test run
from both user interfaces. 4 Select OK and press .
▪ The user interface used to start the test run displays a Result: The underfloor heating screed dryout starts. It stops
status screen. automatically when done. To stop it manually, press , select OK
and press .
▪ The other user interface displays a "busy" screen. You
cannot use the user interface as long as the "busy" INFORMATION
screen is shown.
In case no outdoor unit is installed, the user interface will
ask if the gas boiler can take over the entire load. After
6.2.4 To perform an actuator test run allowing this, restart the screed dryout program to make
sure all actuators are operating.
Perform an actuator test run to confirm the operation of the different
actuators. For example, when you select Pump, a test run of the NOTICE
pump will start.
To perform an underfloor heating screed dryout, room frost
Prerequisite: Make sure that the leaving water temperature home protection needs to be disabled ([2‑06]=0). By default, it is
page, room temperature home page, and domestic hot water home
enabled ([2‑06]=1). However, due to the "installer-on-site"
page are turned OFF.
mode (see "Commissioning"), room frost protection will be
1 Set the user permission level to Installer. See "To set the user automatically disabled for 36 hours after the first power-on.
permission level to Installer" [4 13].
If the screed dryout still needs to be performed after the
2 Make sure the room temperature control, the leaving water first 36 hours of power-on, manually disable room frost
temperature control and the domestic hot water control are protection by setting [2‑06] to "0", and KEEP it disabled
turned OFF via the user interface. until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.
8 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin Business Portal (authentication required).
12
13
14
15
9 8
11
16
17
1
10
3 20
7
4
6
5 19 18
2
3D082238-1B
A Water side
B Refrigerant side
1 Space heating/cooling water IN
2 Space heating/cooling water OUT
3 Shut‑off valve with drain/fill valve
4 Expansion vessel
5 Filter
6 Pump
7 Plate heat exchanger
8 Air purge
9 Flow sensor
Outdoor unit Outdoor unit Only for demand PCB option Only for demand PCB option
Use normal kWh rate power Use normal kWh rate power Only for solar pump station Only for solar pump station
supply for indoor unit supply for indoor unit Options: solar pump connection, Options: solar pump connection,
(2) Gas boiler interconnection (2) Gas boiler interconnection alarm output, On/OFF output alarm output, On/OFF output
Gas boiler Gas boiler Refer to operation manual Refer to operation manual
(3) User interface (3) User interface Solar pump connection Solar pump connection
Only for remote user interface Only for remote user interface Switch box Switch box
option option Thermo On/OFF output Thermo On/OFF output
(4) Domestic hot water tank (4) Domestic hot water tank (7) External room thermostats (7) External room thermostats
3 wire type SPDT 3 wire type SPDT and heat pump convector and heat pump convector
3 wire type SPST 3 wire type SPST Additional LWT zone Additional leaving water
temperature zone
(5) Options (5) Options
Main LWT zone Main leaving water temperature
230 V AC supplied by PCB 230 V AC supplied by PCB zone
5 V DC pulse detection (voltage 5 V DC pulse detection (voltage Only for external sensor (floor/ Only for external sensor (floor or
supplied by PCB) supplied by PCB) ambient) ambient)
Continuous Continuous current Only for heat pump convector Only for heat pump convector
DHW pump output Domestic hot water pump output Only for wired thermostat Only for wired thermostat
DHW pump Domestic hot water pump Only for wireless thermostat Only for wireless thermostat
2 core
2x0.75
3 Preferential kWh rate power supply contact X1M: 1-2-3
+ earth
Field supply
3 Safety thermostat
4 core
Field supply
Indoor unit
Only for *KRP1HB*
X1M: 1-2-3
+ earth A4P: Y1 2 core
X2M: 30-31 X2M: 28 alarm indication
Alarm output 230 V
X5M: 3-4 Only for *KSRPS3 option
A4P: Y3 2 core
X2M: 29 BSK: 1-2 solar interlock
Solar input 230 V
A4P: Y2 2 core
Optional parts (*KHWP*) X2M: 29
Cooling/heating
On/OFF output
Cooling/heating 230 V
On/OFF output
A1P: X39A
X5M: 1-2
X5
Gas boiler
3D082242-1A
4P349587-1G 2020.10
Verantwortung für Energie und Umwelt