You are on page 1of 40

Installation and operation

manual

Packaged air-cooled water chiller

EWAQ016CAW
EWAQ021CAW
EWAQ025CAW
EWAQ032CAW
EWAQ040CAW
EWAQ050CAW
EWAQ064CAW

EWYQ016CAW
EWYQ021CAW
EWYQ025CAW
EWYQ032CAW
EWYQ040CAW
EWYQ050CAW Installation and operation manual
English
EWYQ064CAW Packaged air-cooled water chiller
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI

Daikin Europe N.V.


01 declares under its sole responsibility that the air conditioning models to which this declaration relates: 09 заявляет, исключительно под свою ответственность, что модели кондиционеров воздуха, к которым относится настоящее заявление: 17 deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów, których dotyczy niniejsza deklaracja:
02 erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist: 10 erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører: 18 declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
03 déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration: 11 deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att: 19 z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaša:
04 verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft: 12 erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon, innebærer at: 20 kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
05 declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace referencia la declaración: 13 ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit: 21 декларира на своя отговорност, че моделите климатична инсталация, за които се отнася тази декларация:
06 dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione: 14 prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje: 22 visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
07 δηλώνει με αποκλειστική της ευθύνη ότι τα μοντέλα των κλιματιστικών συσκευών στα οποία αναφέρεται η παρούσα δήλωση: 15 izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi: 23 ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeļu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
08 declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere: 16 teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik: 24 vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie:
25 tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu klima modellerinin aşaǧıdaki gibi olduǧunu beyan eder:

EWAQ016CAW****, EWAQ021CAW****, EWAQ025CAW****, EWAQ032CAW****, EWAQ040CAW****, EWAQ050CAW****, EWAQ064CAW****,


EWYQ016CAW****, EWYQ021CAW****, EWYQ025CAW****, EWYQ032CAW****, EWYQ040CAW****, EWYQ050CAW****, EWYQ064CAW****,
* = , , -, 0, 1, 2, 3, ..., A, B, C, ..., Z

01 are in conformity with the following standard(s) or other normative 05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) 09 соответствуют следующим стандартам или другим нормативным 12 respektive utstyr er i overensstemmelse med følgende standard(er) eller 17 spełniają wymogi następujących norm i innych dokumentów 21 съответстват на следните стандарти или други нормативни
document(s), provided that these are used in accordance with our documento(s) normativo(s), siempre que sean utilizados de acuerdo con документам, при условии их использования согласно нашим andre normgivende dokument(er), under forutssetning av at disse brukes normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi документи, при условие, че се използват съгласно нашите
instructions: nuestras instrucciones: инструкциям: i henhold til våre instrukser: instrukcjami: инструкции:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder - 06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a 10 overholder følgende standard(er) eller andet/andre 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien 18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) 22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius
dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie carattere normativo, a patto che vengano usati in conformità alle nostre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: document(e) normativ(e), cu condiţia ca acestea să fie utilizate în dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
gemäß unseren Anweisungen eingesetzt werden: istruzioni: vore instrukser: 14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají conformitate cu instrucţiunile noastre: 23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), 07 είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) 11 respektive utrustning är utförd i överensstämmelse med och následujícím normám nebo normativním dokumentům: 19 skladni z naslednjimi standardi in drugimi normativi, pod standartiem un citiem normatīviem dokumentiem:
pour autant qu'ils soient utilisés conformément à nos instructions: κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται σύμφωνα με τις följer följande standard(er) eller andra normgivande dokument, under 15 u skladu sa slijedećim standardom(ima) ili drugim normativnim pogojem, da se uporabljajo v skladu z našimi navodili: 24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i)
04 conform de volgende norm(en) of één of meer andere bindende οδηγίες μας: förutsättning att användning sker i överensstämmelse med våra dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: 20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v
documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig 08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) instruktioner: 16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentidega, kui neid kasutatakse vastavalt meie juhenditele: súlade s našim návodom:
onze instructies: documento(s) normativo(s), desde que estes sejam utilizados de acordo dokumentum(ok)nak, ha azokat előírás szerint használják: 25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar
com as nossas instruções: ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01 following the provisions of: 10 under iagttagelse af bestemmelserne i: 19 ob upoštevanju določb: 01 Directives, as amended. 10 Direktiver, med senere ændringer. 18 Directivelor, cu amendamentele respective.
02 gemäß den Vorschriften der: 11 enligt villkoren i: 20 vastavalt nõuetele: 02 Direktiven, gemäß Änderung. 11 Direktiv, med företagna ändringar. 19 Direktive z vsemi spremembami.
03 conformément aux stipulations des: 12 gitt i henhold til bestemmelsene i: 21 следвайки клаузите на: 03 Directives, telles que modifiées. 12 Direktiver, med foretatte endringer. 20 Direktiivid koos muudatustega.
04 overeenkomstig de bepalingen van: 13 noudattaen määräyksiä: 22 laikantis nuostatų, pateikiamų: Machinery 2006/42/EC *** 04 Richtlijnen, zoals geamendeerd. 13 Direktiivejä, sellaisina kuin ne ovat muutettuina. 21 Директиви, с техните изменения.
05 siguiendo las disposiciones de: 14 za dodržení ustanovení předpisu: 23 ievērojot prasības, kas noteiktas: Electromagnetic Compatibility 2014/30/EU * 05 Directivas, según lo enmendado. 14 v platném znění. 22 Direktyvose su papildymais.
06 secondo le prescrizioni per: 15 prema odredbama: 24 održiavajúc ustanovenia: 06 Direttive, come da modifica. 15 Smjernice, kako je izmijenjeno. 23 Direktīvās un to papildinājumos.
07 με τήρηση των διατάξεων των: 16 követi a(z): 25 bunun koşullarına uygun olarak: Pressure Equipment 2014/68/EU ** 07 Οδηγιών, όπως έχουν τροποποιηθεί. 16 irányelv(ek) és módosításaik rendelkezéseit. 24 Smernice, v platnom znení.
08 de acordo com o previsto em: 17 zgodnie z postanowieniami Dyrektyw: 08 Directivas, conforme alteração em. 17 z późniejszymi poprawkami. 25 Değiştirilmiş halleriyle Yönetmelikler.
09 в соответствии с положениями: 18 în urma prevederilor: 09 Директив со всеми поправками.
01 * as set out in <A> and judged positively by <B> according to the 05 * como se establece en <A> y es valorado positivamente por <B> 09 * как указано в <A> и в соответствии с положительным решением <B> 14 * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v souladu 19 * kot je določeno v <A> in odobreno s strani <B> v skladu 24 * ako bolo uvedené v <A> a pozitívne zistené <B> v súlade
Certificate <C>. de acuerdo con el Certificado <C>. согласно Свидетельству <C>. s osvědčením <C>. s certifikatom <C>. s osvedčením <C>.
** as set out in the Technical Construction File <D> and judged positively by ** tal como se expone en el Archivo de Construcción Técnica <D> ** как указано в Досье технического топкования <D> и в соответствии ** jak bylo uvedeno v souboru technické konstrukce <D> a pozitivně ** kot je določeno v tehnični mapi <D> in odobreno s strani <E> (Uporabljen ** ako je to stanovené v Súbore technickej konštrukcie <D> a kladne
<E> (Applied module <F>) according to the Certificate <G>. Risk y juzgado positivamento por <E> (Modulo aplicado <F>) según el с положительным решением <E> zjištěno <E> (použitý modul <F>) v souladu s osvědčením <G>. modul <F>) v skladu s certifikatom <G>. Kategorija tveganja <H>. posúdené <E> (Aplikovaný modul <F>) podľa Certifikátu <G>. Kategória
category <H>. Also refer to next page. Certificado <G>. Categoría de riesgo <H>. Consulte también la siguiente (Прикладной модуль <F>) согласно Свидетельству <G>. Категория Kategorie rizik <H>. Viz také následující strana. Glejte tudi na naslednji strani. nebezpečia <H>. Viď tiež nasledovnú stranu.
02 * wie in <A> aufgeführt und von <B> positiv beurteilt gemäß página. риска <H>. Также смотрите следующую страницу. 15 * kako je izloženo u <A> i pozitivno ocijenjeno od strane <B> prema 20 * nagu on näidatud dokumendis <A> ja heaks kiidetud <B> järgi vastavalt 25 * <A>’da belirtildiği gibi ve <C> Sertifikasına göre <B> tarafından olumlu
Zertifikat <C>. 06 * delineato nel <A> e giudicato positivamente da <B> secondo 10 * som anført i <A> og positivt vurderet af <B> i henhold til Certifikat <C>. Certifikatu <C>. sertifikaadile <C>. olarak değerlendirildiği gibi.
** wie in der Technischen Konstruktionsakte <D> aufgeführt und von <E> il Certificato <C>. ** som anført i den Tekniske Konstruktionsfil <D> og positivt vurderet af ** kako je izloženo u Datoteci o tehničkoj konstrukciji <D> i pozitivno ** nagu on näidatud tehnilises dokumentatsioonis <D> ja heaks kiidetud ** <D> Teknik Yapı Dosyasında belirtildiği gibi ve <G> Sertifikasına göre
(Angewandtes Modul <F>) positiv ausgezeichnet positiv ausgezeichnet ** delineato nel File Tecnico di Costruzione <D> e giudicato positivamente <E> (Anvendt modul <F>) i henhold til Certifikat <G>. Risikoklasse <H>. ocijenjeno od strane <E> (Primijenjen modul <F>) prema Certifikatu <E> järgi (lisamoodul <F>) vastavalt sertifikaadile <G>. Riskikategooria <E> tarafından olumlu olarak (Uygulanan modül <F>) değerlendirilmiştir.
gemäß Zertifikat <G>. Risikoart <H>. Siehe auch nächste Seite. da <E> (Modulo <F> applicato) secondo il Certificato <G>. Categoria Se også næste side. <G>. Kategorija opasnosti <H>. Također pogledajte na slijedećoj stranici. <H>. Vaadake ka järgmist lehekülge. Risk kategorisi <H>. Ayrıca bir sonraki sayfaya bakın.
03 * tel que défini dans <A> et évalué positivement par <B> conformément au di rischio <H>. Fare riferimento anche alla pagina successiva. 11 * enligt <A> och godkänts av <B> enligt Certifikatet <C>. 16 * a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z) <C> tanúsítvány 21 * както е изложено в <A> и оценено положително от <B> съгласно
Certificat <C>. 07 * όπως καθορίζεται στο <A> και κρίνεται θετικά από το <B> σύμφωνα με ** i enlighet med den Tekniska Konstruktionsfilen <D> som positivt intygats szerint. Сертификата <C>. <A> Daikin.TCF.029C3/07-2017
** tel que stipulé dans le Fichier de Construction Technique <D> et jugé το Πιστοποιητικό <C>. av <E> (Fastsatt modul <F>) vilket också framgår av Certifikat <G>. ** a(z) <D> műszaki konstrukciós dokumentáció alapján, a(z) <E> igazolta ** както е заложено в Акта за техническа конструкция <D> и оценено
positivement par <E> (Module appliqué <F>) conformément au Certificat ** όπως προσδιορίζεται στο Αρχείο Τεχνικής Κατασκευής <D> και κρίνεται Riskkategori <H>. Se även nästa sida. a megfelelést (alkalmazott modul: <F>), a(z) <G> tanúsítvány szerint. положително от <E> (Приложен модул <F>) съгласно Сертификат <B> TÜV (NB1856)
<G>. Catégorie de risque <H>. Se reporter également à la page θετικά από το <E> (Χρησιμοποιούμενη υπομονάδα <F>) σύμφωνα με το 12 * som det fremkommer i <A> og gjennom positiv bedømmelse av <B> Veszélyességi kategória <H>. Lásd még a következő oldalon. <G>. Категория риск <H>. Вижте също на следващата страница.
suivante. Πιστοποιητικό <G>. Κατηγορία επικινδυνότητας <H>. Ανατρέξτε επίσης ifølge Sertifikat <C>. 17 * zgodnie z dokumentacją <A>, pozytywną opinią <B> i 22 * kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal <C> 10021804.29
04 * zoals vermeld in <A> en positief beoordeeld door <B> overeenkomstig στην επόμενη σελίδα. ** som det fremkommer i den Tekniske Konstruksjonsfilen <D> og gjennom Świadectwem <C>. Sertifikatą <C>.
Certificaat <C>. 08 * tal como estabelecido em <A> e com o parecer positivo de <B> positiv bedømmelse av <E> (Anvendt modul <F>) ifølge Sertifikat <G>. ** zgodnie z archiwalną dokumentacją konstrukcyjną <D> i pozytywną ** kaip nurodyta Techninėje konstrukcijos byloje <D> ir patvirtinta <E> <D> Daikin.TCFP.006
** zoals vermeld in het Technisch Constructiedossier <D> en de acordo com o Certificado <C>. Risikokategori <H>. Se også neste side. opinią <E> (Zastosowany moduł <F>) zgodnie ze Świadectwem <G>. (taikomas modulis <F>) pagal pažymėjimą <G>. Rizikos kategorija <H>.
in orde bevonden door <E> (Toegepaste module <F>) overeenkomstig ** tal como estabelecido no Ficheiro Técnico de Construção <D> e com o 13 * jotka on esitetty asiakirjassa <A> ja jotka <B> on hyväksynyt Kategoria zagrożenia <H>. Patrz także następna strona. Taip pat žiūrėkite ir kitą puslapį. <E> Vinçotte nv (NB0026)
Certificaat <G>. Risicocategorie <H>. Zie ook de volgende pagina. parecer positivo de <E> (Módulo aplicado <F>) de acordo com o Sertifikaatin <C> mukaisesti. 18 * aşa cum este stabilit în <A> şi apreciat pozitiv de <B> în conformitate cu 23 * kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam saskaņā
Certificado <G>. Categoria de risco <H>. Consultar também a página ** jotka on esitetty Teknisessä Asiakirjassa <D> ja jotka <E> on hyväksynyt Certificatul <C>. ar sertifikātu <C>. <F> D1
seguinte. (Sovellettu moduli <F>) Sertifikaatin <G> mukaisesti. Vaaraluokka <H>. ** conform celor stabilite în Dosarul tehnic de construcţie <D> şi apreciate ** kā noteikts tehniskajā dokumentācijā <D>, atbilstoši <E> pozitīvajam
Katso myös seuraava sivu. pozitiv de <E> (Modul aplicat <F>) în conformitate cu Certificatul <G>. lēmumam (piekritīgā sadaĮa: <F>), ko apliecina sertifikāts <G>. Riska <G> 52846/9042
Categorie de risc <H>. Consultaţi de asemenea pagina următoare. kategorija <H>. Skat. arī nākošo lappusi.
<H> II

01*** Daikin Europe N.V. is authorised to compile the Technical Construction File. 07*** Η Daikin Europe N.V. είναι εξουσιοδοτημένη να συντάξει τον Τεχνικό φάκελο κατασκευής. 13*** Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan. 19*** Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
02*** Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen. 08*** A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico. 14*** Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce. 20*** Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
03*** Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique. 09*** Компания Daikin Europe N.V. уполномочена составить Комплект технической документации. 15*** Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji. 21*** Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
04*** Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen. 10*** Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata. 16*** A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására. 22*** Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
05*** Daikin Europe N.V. está autorizado a compilar el Archivo de Construcción Técnica. 11*** Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen. 17*** Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej. 23*** Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
06*** Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruzione. 12*** Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen. 18*** Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie. 24*** Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
25*** Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir.

3PW70086-5F
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI

01 continuation of previous page: 05 continuación de la página anterior: 08 continuação da página anterior: 12 fortsettelse fra forrige side: 15 nastavak s prethodne stranice: 19 nadaljevanje s prejšnje strani: 22 ankstesnio puslapio tęsinys:
02 Fortsetzung der vorherigen Seite: 06 continua dalla pagina precedente: 09 продолжение предыдущей страницы: 13 jatkoa edelliseltä sivulta: 16 folytatás az előző oldalról: 20 eelmise lehekülje järg: 23 iepriekšējās lappuses turpinājums:
03 suite de la page précédente: 07 συνέχεια από την προηγούμενη σελίδα: 10 fortsat fra forrige side: 14 pokračování z předchozí strany: 17 ciąg dalszy z poprzedniej strony: 21 продължение от предходната страница: 24 pokračovanie z predchádzajúcej strany:
04 vervolg van vorige pagina: 11 fortsättning från föregående sida: 18 continuarea paginii anterioare: 25 önceki sayfadan devam:

01 Design Specifications of the models to which this declaration relates: 07 Προδιαγραφές Σχεδιασμού των μοντέλων με τα οποία σχετίζεται η δήλωση: 13 Tätä ilmoitusta koskevien mallien rakennemäärittely: 20 Deklaratsiooni alla kuuluvate mudelite disainispetsifikatsioonid:
02 Konstruktionsdaten der Modelle auf die sich diese Erklärung bezieht: 08 Especificações de projecto dos modelos a que se aplica esta declaração: 14 Specifikace designu modelů, ke kterým se vztahuje toto prohlášení: 21 Проектни спецификации на моделите, за които се отнася декларацията:
03 Spécifications de conception des modèles auxquels se rapporte cette déclaration: 09 Проектные характеристики моделей, к которым относится настоящее заявление: 15 Specifikacije dizajna za modele na koje se ova izjava odnosi: 22 Konstrukcinės specifikacijos modelių, kurie susiję su šia deklaracija:
04 Ontwerpspecificaties van de modellen waarop deze verklaring betrekking heeft: 10 Typespecifikationer for de modeller, som denne erklæring vedrører: 16 A jelen nyilatkozat tárgyát képező modellek tervezési jellemzői: 23 To modeļu dizaina specifikācijas, uz kurām attiecas šī deklarācija:
05 Especificaciones de diseño de los modelos a los cuales hace referencia esta declaración: 11 Designspecifikationer för de modeller som denna deklaration gäller: 17 Specyfikacje konstrukcyjne modeli, których dotyczy deklaracja: 24 Konštrukčné špecifikácie modelu, ktorého sa týka toto vyhlásenie:
06 Specifiche di progetto dei modelli cui fa riferimento la presente dichiarazione: 12 Konstruksjonsspesifikasjoner for de modeller som berøres av denne deklarasjonen: 18 Specificaţiile de proiectare ale modelelor la care se referă această declaraţie: 25 Bu bildirinin ilgili olduğu modellerin Tasarım Özellikleri:
19 Specifikacije tehničnega načrta za modele, na katere se nanaša ta deklaracija:

01 ∙ Maximum allowable pressure (PS): <K> (bar) 06 ∙ Pressione massima consentita (PS): <K> (bar) 10 ∙ Maks. tilladt tryk (PS): <K> (bar) 15 ∙ Najveći dopušten tlak (PS): <K> (bar) 19∙ Maksimalni dovoljeni tlak (PS): <K> (bar) 24 ∙ Maximálny povolený tlak (PS): <K> (bar)
∙ Minimum/maximum allowable temperature (TS*): ∙ Temperatura minima/massima consentita (TS*): ∙ Min./maks. tilladte temperatur (TS*): ∙ Najniža/najviša dopuštena temperatura (TS*): ∙ Minimalna/maksimalna dovoljena temperatura (TS*): ∙ Minimálna/maximálna povolená teplota (TS*):
* TSmin: Minimum temperature at low pressure side: <L> (°C) * TSmin: temperatura minima nel lato di bassa pressione: <L> (°C) * TSmin: Min. temperatur på lavtrykssiden: <L> (°C) * TSmin: Najniža temperatura u području niskog tlaka: <L> (°C) * TSmin: Minimalna temperatura na nizkotlačni strani: <L> (°C) * TSmin: Minimálna teplota na nízkotlakovej strane: <L> (°C)
* TSmax: Saturated temperature corresponding with the maximum * TSmax: temperatura satura corrispondente alla pressione massima * TSmax: Mættet temperatur svarende til maks. tilladte tryk (PS): <M> * TSmax: Standardna temperatura koja odgovara najvećem dopuštenom * TSmax: Nasičena temperatura, ki ustreza maksimalnemu dovoljenemu * TSmax: Nasýtená teplota korešpondujúca s maximálnym povoleným
allowable pressure (PS): <M> (°C) consentita (PS): <M> (°C) (°C) tlaku (PS): <M> (°C) tlaku (PS): <M> (°C) tlakom (PS): <M> (°C)
∙ Refrigerant: <N> ∙ Refrigerante: <N> ∙ Kølemiddel: <N> ∙ Rashladno sredstvo: <N> ∙ Hladivo: <N> ∙ Chladivo: <N>
∙ Setting of pressure safety device: <P> (bar) ∙ Impostazione del dispositivo di controllo della pressione: <P> (bar) ∙ Indstilling af tryksikringsudstyr: <P> (bar) ∙ Postavke sigurnosne naprave za tlak: <P> (bar) ∙ Nastavljanje varnostne naprave za tlak: <P> (bar) ∙ Nastavenie tlakového poistného zariadenia: <P> (bar)
∙ Manufacturing number and manufacturing year: refer to model nameplate ∙ Numero di serie e anno di produzione: fare riferimento alla targhetta del ∙ Produktionsnummer og fremstillingsår: se modellens fabriksskilt ∙ Proizvodni broj i godina proizvodnje: pogledajte natpisnu pločicu modela ∙ Tovarniška številka in leto proizvodnje: glejte napisno ploščico ∙ Výrobné číslo a rok výroby: nájdete na výrobnom štítku modelu
02 ∙ Maximal zulässiger Druck (PS): <K> (Bar) modello 11 ∙ Maximalt tillåtet tryck (PS): <K> (bar) 16 ∙ Legnagyobb megengedhető nyomás (PS): <K> (bar) 20∙ Maksimaalne lubatud surve (PS): <K> (bar) 25 ∙ İzin verilen maksimum basınç (PS): <K> (bar)
∙ Minimal/maximal zulässige Temperatur (TS*): 07 ∙ Mέγιστη επιτρεπόμενη πίεση (PS): <K> (bar) ∙ Min/max tillåten temperatur (TS*): ∙ Legkisebb/legnagyobb megengedhető hőmérséklet (TS*): ∙ Minimaalne/maksimaalne lubatud temperatuur (TS*): ∙ İzin verilen minimum/maksimum sıcaklık (TS*):
* TSmin: Mindesttemperatur auf der Niederdruckseite: <L> (°C) ∙ Ελάχιστη/μέγιστη επιτρεπόμενη θερμοκρασία (TS*): * TSmin: Minimumtemperatur på lågtryckssidan: <L> (°C) * TSmin: Legkisebb megengedhető hőmérséklet a kis nyomású oldalon: * TSmin: Minimaalne temperatuur madalsurve küljel: <L> (°C) * TSmin: Düşük basınç tarafındaki minimum sıcaklık: <L> (°C)
* TSmax: Sättigungstemperatur die dem maximal zulässigen Druck (PS) * TSmin: Ελάχιστη θερμοκρασία για την πλευρά χαμηλής πίεσης: <L> * TSmax: Mättnadstemperatur som motsvarar maximalt tillåtet tryck (PS): <L> (°C) * TSmax: Maksimaalsele lubatud survele (PS) vastav küllastunud * TSmax: İzin verilen maksimum basınca (PS) karşı gelen doyma
entspricht: <M> (°C) (°C) <M> (°C) * TSmax: A legnagyobb megengedhető nyomásnak (PS) megfelelő temperatuur: <M> (°C) sıcaklığı: <M> (°C)
∙ Kältemittel: <N> * TSmax: Κορεσμένη θερμοκρασία που αντιστοιχεί με τη μέγιστη ∙ Köldmedel: <N> telítettségi hőmérséklet: <M> (°C) ∙ Jahutusaine: <N> ∙ Soğutucu: <N>
∙ Einstellung der Druck-Schutzvorrichtung: <P> (Bar) επιτρεπόμενη πίεση (PS): <M> (°C) ∙ Inställning för trycksäkerhetsenhet: <P> (bar) ∙ Hűtőközeg: <N> ∙ Surve turvaseadme seadistus: <P> (bar) ∙ Basınç emniyet düzeninin ayarı: <P> (bar)
∙ Herstellungsnummer und Herstellungsjahr: siehe Typenschild ∙ Ψυκτικό: <N> ∙ Tillverkningsnummer och tillverkningsår: se modellens namnplåt ∙ A túlnyomás-kapcsoló beállítása: <P> (bar) ∙ Tootmisnumber ja tootmisaasta: vaadake mudeli andmeplaati ∙ İmalat numarası ve imalat yılı: modelin ünite plakasına bakın
des Modells ∙ Ρύθμιση της διάταξης ασφάλειας πίεσης: <P> (bar) 12 ∙ Maksimalt tillatt trykk (PS): <K> (bar) ∙ Gyártási szám és gyártási év: lásd a berendezés adattábláján 21∙ Максимално допустимо налягане (PS): <K> (bar)
03 ∙ Pression maximale admise (PS): <K> (bar) ∙ Αριθμός κατασκευής και έτος κατασκευής: ανατρέξτε στην πινακίδα ∙ Minimalt/maksimalt tillatt temperatur (TS*): 17 ∙ Maksymalne dopuszczalne ciśnienie (PS): <K> (bar) ∙ Минимално/максимално допустима температура (TS*):
∙ Température minimum/maximum admise (TS*): αναγνώρισης του μοντέλου * TSmin: Minimumstemperatur på lavtrykkssiden: <L> (°C) ∙ Minimalna/maksymalna dopuszczalna temperatura (TS*): * TSmin: Минимална температура от страната на ниското налягане:
* TSmin: température minimum côté basse pression: <L> (°C) 08 ∙ Pressão máxima permitida (PS): <K> (bar) * TSmax: Metningstemperatur i samsvar med maksimalt tillatt trykk (PS): * TSmin: Minimalna temperatura po stronie niskociśnieniowej: <L> (°C) <L> (°C)
* TSmax: température saturée correspondant à la pression maximale ∙ Temperaturas mínima e máxima permitidas (TS*): <M> (°C) * TSmax: Temperatura nasycenia odpowiadająca maksymalnemu * TSmax: Температура на насищане, съответстваща на максимално
admise (PS): <M> (°C) * TSmin: Temperatura mínima em baixa pressão: <L> (°C) ∙ Kjølemedium: <N> dopuszczalnemu ciśnieniu (PS): <M> (°C) допустимото налягане (PS): <M> (°C)
∙ Réfrigérant: <N> * TSmax: Temperatura de saturação correspondente à pressão máxima ∙ Innstilling av sikkerhetsanordning for trykk: <P> (bar) ∙ Czynnik chłodniczy: <N> ∙ Охладител: <N>
∙ Réglage du dispositif de sécurité de pression: <P> (bar) permitida (PS): <M> (°C) ∙ Produksjonsnummer og produksjonsår: se modellens merkeplate ∙ Nastawa ciśnieniowego urządzenia bezpieczeństwa: <P> (bar) ∙ Настройка на предпазното устройство за налягане: <P> (bar)
∙ Numéro de fabrication et année de fabrication: se reporter à la plaquette ∙ Refrigerante: <N> 13 ∙ Suurin sallittu paine (PS): <K> (bar) ∙ Numer fabryczny oraz rok produkcji: patrz tabliczka znamionowa modelu ∙ Фабричен номер и година на производство: вижте табелката
signalétique du modèle ∙ Regulação do dispositivo de segurança da pressão: <P> (bar) ∙ Pienin/suurin sallittu lämpötila (TS*): 18 ∙ Presiune maximă admisibilă (PS): <K> (bar) на модела
04 ∙ Maximaal toelaatbare druk (PS): <K> (bar) ∙ Número e ano de fabrico: consultar a placa de especificações * TSmin: Alhaisin matalapainepuolen lämpötila: <L> (°C) ∙ Temperatură minimă/maximă admisibilă (TS*): 22∙ Maksimalus leistinas slėgis (PS): <K> (bar)
∙ Minimaal/maximaal toelaatbare temperatuur (TS*): da unidade * TSmax: Suurinta sallittua painetta (PS) vastaava kyllästyslämpötila: * TSmin: Temperatură minimă pe partea de presiune joasă: <L> (°C) ∙ Minimali/maksimali leistina temperatūra (TS*):
* TSmin: Minimumtemperatuur aan lagedrukzijde: <L> (°C) 09 ∙ Максимально допустимое давление (PS): <K> (бар) <M> (°C) * TSmax: Temperatură de saturaţie corespunzând presiunii maxime * TSmin: Minimali temperatūra žemo slėgio pusėje: <L> (°C)
* TSmax: Verzadigde temperatuur die overeenstemt met de maximaal ∙ Минимально/Максимально допустимая температура (TS*): ∙ Kylmäaine: <N> admisibile (PS): <M> (°C) * TSmax: Prisotinta temperatūra, atitinkamti maksimalų leistiną slėgį
toelaatbare druk (PS): <M> (°C) * TSmin: Минимальная температура на стороне низкого давления: ∙ Varmuuspainelaitteen asetus: <P> (bar) ∙ Agent frigorific: <N> (PS): <M> (°C)
∙ Koelmiddel: <N> <L> (°C) ∙ Valmistusnumero ja valmistusvuosi: katso mallin nimikilpi ∙ Reglarea dispozitivului de siguranţă pentru presiune: <P> (bar) ∙ Šaldymo skystis: <N>
∙ Instelling van drukbeveiliging: <P> (bar) * TSmax: Температура кипения, соответствующая максимально 14 ∙ Maximální přípustný tlak (PS): <K> (bar) ∙ Numărul de fabricaţie şi anul de fabricaţie: consultaţi placa de identificare ∙ Apsauginio slėgio prietaiso nustatymas: <P> (bar)
∙ Fabricagenummer en fabricagejaar: zie naamplaat model допустимому давлению (PS): <M> (°C) ∙ Minimální/maximální přípustná teplota (TS*): a modelului ∙ Gaminio numeris ir pagaminimo metai: žiūrėkite modelio pavadinimo
05 ∙ Presión máxima admisible (PS): <K> (bar) ∙ Хладагент: <N> * TSmin: Minimální teplota na nízkotlaké straně: <L> (°C) plokštelę <K> PS 40 bar
∙ Temperatura mínima/máxima admisible (TS*): ∙ Настройка устройства защиты по давлению: <P> (бар) * TSmax: Saturovaná teplota odpovídající maximálnímu přípustnému 23 ∙ Maksimālais pieļaujamais spiediens (PS): <K> (bar)
* TSmin: Temperatura mínima en el lado de baja presión: <L> (°C) ∙ Заводской номер и год изготовления: смотрите паспортную табличку tlaku (PS): <M> (°C) ∙ Minimālā/maksimālā pieļaujamā temperatūra (TS*): <L> TSmin –30 °C
* TSmax: Temperatura saturada correspondiente a la presión máxima модели ∙ Chladivo: <N> * TSmin: Minimālā temperatūra zemā spiediena pusē: <L> (°C)
admisible (PS): <M> (°C) ∙ Nastavení bezpečnostního tlakového zařízení: <P> (bar) * TSmax: Piesātinātā temperatūra saskaņā ar maksimālo pieļaujamo <M> TSmax 63 °C
∙ Refrigerante: <N> ∙ Výrobní číslo a rok výroby: viz typový štítek modelu spiedienu (PS): <M> (°C)
∙ Ajuste del presostato de seguridad: <P> (bar) ∙ Dzesinātājs: <N> <N> R410A
∙ Número de fabricación y año de fabricación: consulte la placa ∙ Spiediena drošības ierīces iestatīšana: <P> (bar)
de especificaciones técnicas del modelo ∙ Izgatavošanas numurs un izgatavošanas gads: skat. modeļa <P> 40 bar
izgatavotājuzņēmuma plāksnītie

01 Name and address of the Notified body that judged positively 06 Nome e indirizzo dell’Ente riconosciuto che ha riscontrato la conformità 10 Navn og adresse på bemyndiget organ, der har foretaget en positiv 14 Název a adresa informovaného orgánu, který vydal pozitivní posouzení 19 Ime in naslov organa za ugotavljanje skladnosti, ki je pozitivno ocenil 24 Názov a adresa certifikačného úradu, ktorý kladne posúdil zhodu so
on compliance with the Pressure Equipment Directive: <Q> alla Direttiva sulle apparecchiature a pressione: <Q> bedømmelse af, at udstyret lever op til kravene i PED (Direktiv for shody se směrnicí o tlakových zařízeních: <Q> združljivost z Direktivo o tlačni opremi: <Q> smernicou pre tlakové zariadenia: <Q>
02 Name und Adresse der benannten Stelle, die positiv unter Einhaltung der 07 Όνομα και διεύθυνση του Κοινοποιημένου οργανισμού που απεφάνθη Trykbærende Udstyr): <Q> 15 Naziv i adresa prijavljenog tijela koje je donijelo pozitivnu prosudbu o 20 Teavitatud organi, mis hindas Surveseadmete Direktiiviga ühilduvust 25 Basınçlı Teçhizat Direktifine uygunluk hususunda olumlu olarak
Druckanlagen-Richtlinie urteilte: <Q> θετικά για τη συμμόρφωση προς την Οδηγία Εξοπλισμών υπό Πίεση: 11 Namn och adress för det anmälda organ som godkänt uppfyllandet av usklađenosti sa Smjernicom za tlačnu opremu: <Q> positiivselt, nimi ja aadress: <Q> değerlendirilen Onaylanmış kuruluşun adı ve adresi: <Q>
03 Nom et adresse de l’organisme notifié qui a évalué positivement la <Q> tryckutrustningsdirektivet: <Q> 16 A nyomástartó berendezésekre vonatkozó irányelvnek való 21 Наименование и адрес на упълномощения орган, който
conformité à la directive sur l’équipement de pression: <Q> 08 Nome e morada do organismo notificado, que avaliou favoravelmente a 12 Navn på og adresse til det autoriserte organet som positivt bedømte megfelelőséget igazoló bejelentett szervezet neve és címe: <Q> се е произнесъл положително относно съвместимостта
04 Naam en adres van de aangemelde instantie die positief geoordeeld conformidade com a directiva sobre equipamentos pressurizados: <Q> samsvar med direktivet for trykkutstyr (Pressure Equipment Directive): 17 Nazwa i adres Jednostki notyfikowanej, która wydała pozytywną opinię с Директивата за оборудване под налягане: <Q>
heeft over de conformiteit met de Richtlijn Drukapparatuur: <Q> 09 Название и адрес органа технической экспертизы, принявшего <Q> dotyczącą spełnienia wymogów Dyrektywy dot. Urządzeń Ciśnieniowych: 22 Atsakingos institucijos, kuri davė teigiamą sprendimą pagal slėginės <Q> VINÇOTTE nv
05 Nombre y dirección del Organismo Notificado que juzgó positivamente el положительное решение о соответствии Директиве об оборудовании 13 Sen ilmoitetun elimen nimi ja osoite, joka teki myönteisen päätöksen <Q> įrangos direktyvą pavadinimas ir adresas: <Q> Jan Olieslagerslaan 35
cumplimiento con la Directiva en materia de Equipos de Presión: <Q> под давлением: <Q> painelaitedirektiivin noudattamisesta: <Q> 18 Denumirea şi adresa organismului notificat care a apreciat pozitiv 23 Sertifikācijas institūcijas, kura ir devusi pozitīvu slēdzienu par atbilstību 1800 Vilvoorde, Belgium
conformarea cu Directiva privind echipamentele sub Spiediena lekārtu Direktīvai, nosaukums un
presiune: <Q> adrese: <Q>

Shigeki Morita
Director
Ostend, 1st of September 2017

3PW70086-5F
Table of contents
8 Troubleshooting 22
Table of contents 8.1 Error codes: Overview................................................................ 22

9 Technical data 23
9.1 Service space: Outdoor unit ....................................................... 23
1 About the documentation 4 9.2 Piping diagram: Outdoor module................................................ 23
1.1 About this document.................................................................. 4
9.3 Wiring diagram: Outdoor unit ..................................................... 25

For the installer 5 For the user 26


2 About the box 5 10 About the system 26
2.1 Outdoor unit............................................................................... 5
10.1 System layout............................................................................. 26
2.1.1 To remove the accessories from the outdoor unit....... 5
11 User interface 26
3 About the units and options 5
3.1 About the outdoor unit ............................................................... 5 12 Operation 27
3.2 System layout............................................................................ 5 12.1 Operation range ......................................................................... 27
12.2 Quick start-up ............................................................................. 27
4 Preparation 5 12.3 Operating the system ................................................................. 28
4.1 Preparing installation site .......................................................... 5
12.3.1 About the clock ............................................................ 28
4.1.1 Installation site requirements of the outdoor unit ........ 5
12.3.2 About operating the system ......................................... 29
4.2 Preparing water piping .............................................................. 6
12.3.3 Space cooling operation .............................................. 29
4.2.1 Water circuit requirements .......................................... 6
12.3.4 Space heating operation .............................................. 29
4.2.2 Formula to calculate the expansion vessel pre-
12.3.5 Other operation modes ................................................ 30
pressure ...................................................................... 7
12.3.6 Schedule timer ............................................................. 30
4.2.3 To check the water volume and expansion vessel
pre-pressure................................................................ 7 12.3.7 Operating the optional demand PCB ........................... 34
4.2.4 Changing the pre-pressure of the expansion vessel... 8 12.3.8 Operating the optional external control adapter........... 34
4.2.5 To check the water volume: Examples ....................... 8 12.3.9 Operating the optional remote controller...................... 35
4.3 Preparing electrical wiring ......................................................... 8 13 Maintenance and service 35
4.3.1 Safety device requirements ........................................ 8
13.1 About the refrigerant................................................................... 35
5 Installation 8 13.2 After-sales service and warranty ................................................ 35
5.1 Opening the units ...................................................................... 8 13.2.1 Warranty period ........................................................... 35
5.1.1 To open the outdoor unit............................................. 8 13.2.2 Recommended maintenance and inspection............... 35
5.1.2 To open the electrical component box of the outdoor 14 Troubleshooting 35
unit .............................................................................. 9
14.1 Error codes: Overview................................................................ 36
5.2 Mounting the outdoor unit.......................................................... 9
5.2.1 To provide the installation structure ............................ 9 15 Relocation 36
5.3 Connecting the water piping...................................................... 10
5.3.1 Precautions when connecting the water piping........... 10 16 Disposal 36
5.3.2 To fill the water circuit ................................................. 10
5.3.3 To protect the water circuit against freezing ............... 10

5.4
5.3.4 To insulate the water piping ........................................
Connecting the electrical wiring.................................................
11
11
1 About the documentation
5.4.1 Field wiring: Overview................................................. 11
5.4.2 To route and fix the power supply............................... 11 1.1 About this document
5.4.3 To install the main switch handle ................................ 11
5.4.4 To connect the power supply and transmission INFORMATION
cables.......................................................................... 12
Make sure that the user has the printed documentation and
5.4.5 To install the remote controller.................................... 12
ask him/her to keep it for future reference.
5.4.6 To install optional equipment ...................................... 13
Target audience
6 Configuration 13
6.1 Overview: Configuration ............................................................ 13 Authorised installers + end users
6.2 Making field settings.................................................................. 13
INFORMATION
6.2.1 About making field settings ......................................... 13
6.2.2 Field setting components ............................................ 14 This appliance is intended to be used by expert or trained
6.2.3 To access the field setting components...................... 14 users in shops, in light industry and on farms, or for
6.2.4 To access mode 1 or 2 ............................................... 14 commercial use by lay persons.
6.2.5 To use mode 1 ............................................................ 14
Documentation set
6.2.6 To use mode 2 ............................................................ 15
6.2.7 Mode 1: Monitoring settings........................................ 15 This document is part of a documentation set. The complete set
6.2.8 Mode 2: Field settings................................................. 15 consists of:
6.2.9 Field settings on the remote controller........................ 16 ▪ General safety precautions:
6.3 Switching between cooling and heating .................................... 20
▪ Safety instructions that you must read before installing
7 Commissioning 21 ▪ Format: Paper (in the box of the outdoor unit)
7.1 Precautions when commissioning ............................................. 21
7.2 Checklist before commissioning................................................ 21
7.3 Final check ................................................................................ 22

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
4 4P489435-1B – 2017.10
2 About the box
▪ Outdoor unit installation and operation manual: Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
▪ Installation and operation instructions
The original documentation is written in English. All other languages
▪ Format: Paper (in the box of the outdoor unit)
are translations.
▪ Installer and user reference guide:
Technical engineering data
▪ Preparation of the installation, reference data,…
▪ A subset of the latest technical data is available on the regional
▪ Detailed step-by-step instructions and background information Daikin website (publicly accessible).
for basic and advanced usage
▪ The full set of latest technical data is available on the Daikin
▪ Format: Digital files on http://www.daikineurope.com/support- extranet (authentication required).
and-manuals/product-information/

For the installer

▪ In cooling mode, the refrigerant transports the heat taken from the
2 About the box water heat exchanger to the air heat exchanger where the heat is
released to the air.
2.1 Outdoor unit ▪ In heating mode, the refrigerant transports the heat taken from the
air heat exchanger to the water heat exchanger where the heat is
released to the water.
2.1.1 To remove the accessories from the
outdoor unit
3.2 System layout
Make sure that all accessories are available in the unit.

a b c d e a b d c e
1× 1× 1× 1× 8× RC

g
i
FC1 FC2 FC3
f g h i
2× 1×/2× 1× 1× M1 M2 M3

RT1 RT2 RT3

e f f f
a Outdoor unit
a General safety precautions
b Plate heat exchanger
b Installation manual and operation manual (panel 3)
c Expansion vessel
c Remote controller (panel 3)
d Pump
d Main switch handle (panel 1)
e Shut-off valve
e Tie wraps (panel 3)
f Motorized valve
f Shut-off valves (panel 3)
g Bypass valve
g Threaded connection (panel 3) (1× for EWAQ
FC1…3 Fancoil unit (field supply)
+EWYQ016~032, 2× for EWAQ+EWYQ040~064) RC Remote controller
h Filter (panel 3) RT1…3 Room thermostat
i Elbow (panel 3)

3 About the units and options 4 Preparation

3.1 About the outdoor unit 4.1 Preparing installation site


This installation manual concerns the packaged air-cooled water 4.1.1 Installation site requirements of the
chiller. The unit is intended for outdoor installation and can be
outdoor unit
combined with fan coil units for air conditioning purposes, or it can
be used for supplying water for process cooling applications. Mind the spacing guidelines. See the "Technical data" chapter.
The units are available in 7 standard sizes with nominal capacities CAUTION
ranging from 16.8 to 63 kW. All sizes are available as cooling only
unit (EWAQ) and as heat pump unit (EWYQ: cooling/heating). Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
The unit is designed to work in heating mode at ambient
temperatures from –15°C to 35°C and in cooling mode at ambient This unit, both indoor and outdoor, is suitable for
temperatures from –15°C to 43°C. installation in a commercial and light industrial
environment.
The main components are the compressor, the air heat exchanger,
and the water heat exchanger.
The compressor circulates refrigerant into the heat exchangers.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 5
4 Preparation
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
a
This unit is suitable for installation in a commercial and b
light industrial environment.

a
4.2 Preparing water piping c

4.2.1 Water circuit requirements


NOTICE
d
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN 4726. The diffusion of
oxygen into the piping can lead to excessive corrosion. b
▪ Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in
the "Installation" chapter, respecting the water inlet and outlet. a Adapter piece (on the inlet only in case of EWAQ
+EWYQ040~064)
▪ Connecting piping – Force. Do NOT use excessive force when b Shut-off valve
connecting the piping. Deformation of the piping can cause c Bend
malfunctioning of the unit. d Filter

▪ Connecting piping – Tools. Only use appropriate tooling to NOTICE


handle brass, which is a soft material. If NOT, pipes will get
Before mounting the bend, attach the filter to it.
damaged.
▪ Connecting piping – Air, moisture, dust. If air, moisture or dust NOTICE
gets into the circuit, problems may occur. To prevent this: If the bend is not used during installation, replace it with an
▪ Only use clean pipes extension (5 cm long for a 1¼" filter, and 6 cm long for a
2" filter) to ensure proper cleaning operation of the filter.
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent NOTICE
dust and/or particles entering the pipe.
Be sure to install the filter properly. Failure to install or
▪ Use a decent thread sealant to seal connections. incorrect installation will damage the plate heat exchanger
permanently.
NOTICE
▪ Drain taps. Drain taps must be provided at all low points of the
If glycol is present in the system, make sure the thread
system to permit complete drainage of the circuit. A drain valve is
sealant used is resistant to glycol.
provided inside the unit.
▪ Closed circuit. Use the outdoor unit ONLY in a closed water ▪ Air vents. Provide air vents at all high points of the system, which
system. Using the system in an open water system will lead to must also be easily accessible for servicing. An automatic air
excessive corrosion. purge valve is provided inside the unit. Check that this air purge
▪ Water flow. You can find the minimum required water flow in the valve is NOT tightened too much, so that automatic release of air
following table. In all cases, this flow needs to be guaranteed. from the water circuit is possible. Refer to field setting [E‑04] in
When the flow is lower, operation will stop and error will be "6.2.9 Field settings on the remote controller" on page 16.
displayed.
WARNING
Capacity class Minimum required flow rate ▪ For correct operation of the system, a regulating valve
016+021+025 23 l/min must be installed in the water system. The regulating
032 36 l/min valve is to be used to regulate the water flow in the
system (field supply).
040+050 46 l/min
▪ Selecting a flow outside the curves can cause
064 72 l/min
malfunction or damage to the unit. Also refer to the
▪ Field supply components – Water pressure and temperature. Technical specifications.
Check that all components in the field piping can withstand the ▪ The maximum water piping temperature is 50°C according to
water pressure and water temperature. safety device setting.
▪ Drainage – Low points. Provide drain taps at all low points of the ▪ Always use materials which are compatible with the water used in
system in order to allow complete drainage of the water circuit. the system and with the materials used in the unit. (The unit piping
▪ Non-brass metallic piping. When using non-brass metallic fittings are made of brass, the plate heat exchangers are made of
piping, insulate the brass and non-brass properly so that they do stainless steel 316 plates brazed together with copper and the
NOT make contact with each other. This to prevent galvanic optional pump housing is made of cast iron.)
corrosion. ▪ Select the piping diameter in relation to the required water flow
▪ Shut-off valves. Two shut-off valves are delivered with the unit. and available external static pressure (ESP) of the pump. See the
Install them as shown in the following figure. following table for the recommended water piping diameter.

Capacity class Water piping diameter


016~032 1-1/4"

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
6 4P489435-1B – 2017.10
4 Preparation
Capacity class Water piping diameter Example:
040~064 2" To illustrate the impact on the system when modifying the setting
[F‑00], we will consider a unit with a minimum allowable water
NOTICE volume of 66 l. The unit is installed 5 m below the highest point in
It is strongly recommended to install an additional filter on the water circuit and is charged with 30% of ethylene glycol.
the water circuit. Especially to remove metallic particles Assuming that the setting [F‑00] is changed from 5°C (default value)
from the field water piping, it is advised to use a magnetic to 0°C. From the below table we see that 5°C corresponds to a
or cyclone filter which can remove small particles. Small temperature differential of 3.5 K and 0°C to 1 K, which is actually the
particles can damage the unit and will not be removed by lowest value we can set.
the standard filter of the unit.
[F‑00] value (°C) Temperature differential (K)
▪ Water pressure. Take care that the components installed in the
0 1
field piping can withstand the water pressure (maximum 3 bar +
static pressure of the pump). 1 1.5
2 2
4.2.2 Formula to calculate the expansion vessel 3 2.5
pre-pressure 4 3
The pre-pressure (Pg) of the vessel depends on the installation 5 3.5
height difference (H): 6 4
Pg=0.3+(H/10) (bar) 7 4.5
8 5
4.2.3 To check the water volume and expansion 9 5.5
vessel pre-pressure
10 6
The unit has an expansion vessel of 12 litre with a default pre- 11 6.5
pressure of 1 bar.
12 7
See the installer and user reference guide for more information.
13 7.5
To make sure that the unit operates properly: 14 8
▪ You must check the minimum and maximum water volume. 15 8.5
▪ You might need to adjust the pre-pressure of the expansion
The water volume correction factor according to the curve shown in
vessel.
the below graph is 3.5; this means that the minimum volume will be
Minimum water volume 3.5 times larger.

Cooling only model Minimum total water volume (l) Correction factor curve for minimum water volume
016~032 33 a
4.0
040~064 66
3.5

Heat pump model Minimum total water volume (l) 3.0

016~025 76 2.5

032 110 2.0

040+050 152 1.5

064 220 1.0

0.5
INFORMATION 0.0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9
In critical processes, or in rooms with a high heat load,
b
extra water might be required.
a Water volume correction factor
INFORMATION b Temperature differential (K)

The temperature step difference can be modified using When multiplying 64 l by the correction factor, we get 224 l, which
settings [A‑02] and [F‑00]. This has an impact on the will be the minimum water volume allowed in the installation if a
minimum water volume required when the unit operates in temperature differential of 1 K is used.
cooling. Now it is very important to check that for the height difference of the
By default, the unit is set to have a water temperature system, the volume in the system is less than the maximum allowed
difference of 3.5 K which allows it to operate with the value at that pre-pressure (Pg). If we take a look at the ethylene
minimum volume mentioned in the previous table. glycol concentration curve of 30%, for 1 bar of pre-pressure the
However, if a smaller temperature differential is set, as in maximum volume allowed is 240 l.
the case of process cooling applications where The total volume in the system will definitely be larger after adding
temperature fluctuations must be avoided, a larger the internal volume of the unit. In this case, some pre-pressure can
minimum water volume will be required. be applied or an additional expansion vessel or buffer tank must be
To ensure proper operation of the unit when changing the installed in the field piping.
values of setting [F‑00] (for cooling mode), the minimum Maximum water volume
water volume has to be corrected. If this volume exceeds
Use the following graph to determine the maximum water volume for
the range allowed in the unit, an additional expansion
the calculated pre-pressure.
vessel or a buffer tank must be installed in the field piping.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 7
5 Installation
a 3 Example 2
2,5 The unit is installed at the highest point in the water circuit. The total
water volume in the water circuit (no glycol used) is 420 l.
2
A Actions:
1,5
▪ Because the total water volume (420 l) is more than the default
1 F water volume (340 l), the pre-pressure must be decreased.
E B ▪ The required pre-pressure is:
0,5 C
D Pg=(0.3+(H/10)) bar=(0.3+(0/10)) bar=0.3 bar
0
0 33 50 100 150 200 250 300 350 400 450 500 550 600 ▪ The corresponding maximum water volume is approximately 490 l
b (see graph).
a Pre-pressure (bar) ▪ Because 420 l is lower than 490 l, the expansion vessel is
b Maximum water volume (l) (water or water + glycol) appropriate for the installation.
A System without glycol
B System with 30% ethylene glycol
C System with 40% ethylene glycol
D System with 30% propylene glycol
4.3 Preparing electrical wiring
E System with 40% propylene glycol
F Default
4.3.1 Safety device requirements
If the total water volume in the entire circuit exceeds the maximum
allowed water volume (see graph), an additional expansion vessel The power supply must be protected with the required safety
must be installed in the field piping. devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
The default value of pre-pressure (Pg) is for a height difference of
7 m. Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
If the height difference of the system is lower than 7 m AND the table below.
volume in the system is less than the maximum allowed value at that
pre-pressure (Pg) (see graph), then NO pre-pressure (Pg) Model Recommended fuses
adjustment is required. EWAQ/EWYQ016 25 A
EWAQ/EWYQ021 32 A
4.2.4 Changing the pre-pressure of the
EWAQ/EWYQ025 32 A
expansion vessel
EWAQ/EWYQ032 40 A
NOTICE EWAQ/EWYQ040 50 A
Only a licensed installer may adjust the pre-pressure of the EWAQ/EWYQ050 63 A
expansion vessel.
EWAQ/EWYQ064 80 A
When changing the default pre-pressure of the expansion vessel
(1 bar) is required, take following guidelines into account: NOTICE

▪ Only use dry nitrogen to set the expansion vessel pre-pressure. When using residual current operated circuit breakers, be
sure to use a high-speed type 300 mA rated residual
▪ Inappropriate setting of the expansion vessel pre-pressure will operating current.
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done
by releasing or increasing nitrogen pressure through the Schrader
valve of the expansion vessel. 5 Installation

5.1 Opening the units

5.1.1 To open the outdoor unit


DANGER: RISK OF ELECTROCUTION
a
DANGER: RISK OF BURNING

To gain access to the unit, front plates need to be opened as follows:

a Schrader valve

4.2.5 To check the water volume: Examples


Example 1
The unit is installed 5 m below the highest point in the water circuit.
The total water volume in the water circuit is 250 l.
No actions or adjustments are required.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
8 4P489435-1B – 2017.10
5 Installation
NOTICE
When the installation height of the unit needs to be
increased, do NOT use stands to only support the corners.

5
1
4
5 ≥100 ≥100
2 4
3

≥100 ≥100
Panel X Not allowed
1 Electrical parts of the hydro module O Allowed (* = preferred installation)

2 Hydro module (side panel) ▪ The height of the foundation must at least be 150 mm from the
floor. In heavy snowfall areas, this height should be increased,
3 Hydro module (front panel)
depending on the installation place and condition.
4 Outdoor module (left panel)
▪ The preferred installation is on a solid longitudinal foundation
5 Outdoor module (right panel) (steel beam frame or concrete). The foundation must be larger
Once the front plates open, the electrical component box can be than the grey marked area.
accessed. See "5.1.2 To open the electrical component box of the
outdoor unit" on page 9.
For service purposes, the pushbuttons on the main PCB need to be
accessed. To access these pushbuttons, the electrical component 440
box cover does not need to be opened. See "6.2.3 To access the
field setting components" on page 14.
B

5.1.2 To open the electrical component box of


the outdoor unit
440

C
A

NOTICE
f
Do NOT apply excessive force when opening the
electronic component box cover. Excessive force can
B
A
B

deform the cover, resulting in entering of water to cause f


equipment failure. c c

a a
631 b 631 b
729 c 729 c
765 d 765 d
765 e 765 e
Minimum foundation
a Hole for foundation bolt
b Base inner dimension
c Distance between foundation bolt holes
d Depth of unit
e Base outer dimension
f Longitudinal foundation dimension

kW A B C
16~25 1340 792 —
32 1650 1102 —
40+50 2320 792 192
64 2940 1102 192

▪ Fasten the unit in place using four foundation bolts M12. It is best
5.2 Mounting the outdoor unit to screw in the foundation bolts until their length remains 20 mm
above the foundation surface.
5.2.1 To provide the installation structure
20 mm

Make sure the unit is installed level on a sufficiently strong base to


prevent vibration and noise.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 9
5 Installation
NOTICE ▪ For correct operation of the system, a regulating valve must be
installed in the water system. The regulating valve is to be used to
▪ Prepare a water drainage channel around the
regulate the water flow in the system (field supply).
foundation to drain waste water from around the unit.
During heating operation and when the outdoor
temperatures are negative, the drained water from the 5.3.2 To fill the water circuit
outdoor unit will freeze up. If the water drainage is not 1 Connect the water supply to the drain and fill valve.
taken care of, the area around the unit might be very
slippery. 2 Make sure the automatic air purge valve is open (at least 2
turns).
▪ When installed in a corrosive environment, use a nut
with plastic washer (a) to protect the nut tightening part 3 Fill with water until the pressure gauge indicates a pressure of
from rust. approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves (refer to field setting [E‑04]
in "6.2.9 Field settings on the remote controller" on page 16).

NOTICE
▪ Air in the water circuit can cause malfunctioning. During
a filling, it may not be possible to remove all the air from
the circuit. Remaining air will be removed through the
automatic air purge valves during the initial operating
5.3 Connecting the water piping hours of the system. Additional filling with water
afterwards may be required.

5.3.1 Precautions when connecting the water ▪ To purge the system, use the special function as
piping described in "7 Commissioning" on page 21.

INFORMATION NOTICE

Also read the precautions and requirements in the The water pressure indicated on the manometer will vary
following chapters: depending on the water temperature (higher pressure at
higher water temperature).
▪ General safety precautions
However, at all times water pressure shall remain above
▪ Preparation 1 bar to avoid air entering the circuit.

To connect the water piping NOTICE

Water connections must be made in accordance with all applicable Make sure water quality complies with EU directive
legislations and the outlook drawing delivered with the unit, 98/83 EC.
respecting the water inlet and outlet.
INFORMATION
NOTICE The unit may dispose of some excessive water through the
Do NOT use excessive force when connecting the piping. pressure relief valve.
Deformation of the piping can cause malfunctioning of the
unit. NOTICE

If dirt gets in the water circuit, problems may occur. Therefore, In case of a power supply failure or pump failure, and NO
always take into account the following when connecting the water glycol was added to the system, drain the system. When
circuit: water is at standstill inside the system, the system is very
likely to freeze and get damaged.
▪ Use clean pipes only.
▪ Hold the pipe end downwards when removing burrs. 5.3.3 To protect the water circuit against
▪ Cover the pipe end when inserting it through a wall so that no dust freezing
and dirt enter.
Frost can damage the system. For this reason, if negative ambient
▪ Use a good thread sealant for the sealing of the connections. The temperatures are expected, make sure the water circuit is sufficiently
sealing must be able to withstand the pressures and temperatures protected against freezing.
of the system; it must also be resistant to the used glycol in the
water. Heater tape (optional)

▪ When using non-brass metallic piping, make sure to insulate both A heater tape is wound around the piping to protect vital parts of the
materials from each other to prevent galvanic corrosion. hydraulic system inside the unit.

▪ Make sure to provide a proper drain for the pressure relief valve. This heater tape will only protect internal parts of the unit. It can not
protect field installed parts outside the unit.
▪ Because brass is a soft material, use appropriate tooling for
connecting the water circuit. Inappropriate tooling will cause Field heater tapes must be provided by the installer.
damage to the pipes.
NOTICE
In case of a power failure or if the power supply is
disconnected during winter, the optional heater tape
cannot protect the unit from freezing. If a power failure can
happen at times the unit is unattended, if the power supply
is disconnected during winter, or if you did not select this
option, it is recommended to add glycol to the water
system.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
10 4P489435-1B – 2017.10
5 Installation
Glycol 5.3.4 To insulate the water piping
Refer to field setting [8‑04] in "6.2.9 Field settings on the remote
The complete water circuit, inclusive all piping, must be insulated to
controller" on page 16.
prevent condensation during cooling operation and reduction of the
INFORMATION heating and cooling capacity as well as prevention of freezing of the
outside water piping during winter time. The thickness of the
The concentrations mentioned in the table below will
insulation materials must be at least 13 mm with λ=0.039 W/mK in
prevent the piping from bursting, but will not prevent the
order to prevent freezing of the outside water piping at ambient
liquid in the piping from freezing.
temperature of –15°C.
Depending on the expected lowest outdoor temperature, make sure If the temperature is higher than 30°C and the humidity is higher
the water system is filled with a weight concentration of glycol as than RH 80%, the thickness of the insulation materials should be at
mentioned in the following table. least 20 mm to prevent condensation on the surface of the
insulation.
Minimum outdoor Ethylene glycol Propylene glycol
temperature
–5°C 10% 15% 5.4 Connecting the electrical wiring
–10°C 15% 20%
–15°C 20% 35% 5.4.1 Field wiring: Overview
Field wiring consists of power supply (always including earth) and
WARNING
indoor-outdoor communication (= transmission) wiring.
Ethylene glycol is toxic.
▪ Most field wiring on the unit is to be made on the terminal blocks
NOTICE inside the electrical component boxes. To gain access to the
terminal blocks, remove the electrical component box service
The above mentioned concentrations are applicable only panel. See "5.1 Opening the units" on page 8.
when the unit is at a standstill.
▪ Cable tie mountings are provided at the wiring entries of the
CAUTION electrical component box.
▪ In case of over-pressure when using glycol, be sure to The wiring diagram is delivered with the unit, located at the inside of
connect the safety valve to a drain pan in order to the switch box cover.
recover the glycol. Connecting a drain pipe is not
required if no glycol is used. The discharged water is 5.4.2 To route and fix the power supply
then drained via the bottom of the unit.
▪ Using more than 40% glycol will damage the unit.

WARNING
Due to presence of glycol, corrosion of the system is
possible. Uninhibited glycol will turn acidic under the
influence of oxygen. This process is accelerated by the
presence of copper and high temperatures. The acidic
LV HV PS
uninhibited glycol attacks metal surfaces and forms
galvanic corrosion cells that cause severe damage to the
system. Therefore it is important that:
▪ the water treatment is correctly executed by a qualified
water specialist,
▪ a glycol with corrosion inhibitors is selected to
counteract acids formed by the oxidation of glycols, LV
▪ no automotive glycol is used because their corrosion HV
inhibitors have a limited lifetime and contain silicates PS
which can foul or plug the system,
▪ galvanized pipes are NOT used in glycol systems since
the presence may lead to the precipitation of certain
components in the glycol's corrosion inhibitor.
PS Power supply
NOTICE HV High voltage
LV Low voltage
Glycol absorbs water from its environment. Therefore do
NOT add glycol that has been exposed to air. Leaving the
cap off the glycol container causes the concentration of 5.4.3 To install the main switch handle
water to increase. The glycol concentration is then lower Open panel 1 and mount the main switch handle parts. The handle
than assumed. As a result, the hydraulic components of the main switch is mounted on panel 1.
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air. EWAQ+EWYQ016~032

See also "7.3 Final check" on page 22.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 11
5 Installation
Wire specification Value
Maximum length 500 m

NOTICE
The wiring for connection is NOT included.

NOTICE
The accessory remote controller MUST be mounted
indoors.
EWAQ+EWYQ040~064
1 Insert a slotted screwdriver into the slots in the rear part of the
remote controller, and remove the front part of the remote
controller.
Ø5 8

N 1
ÿ 5 8

2 N
3
2
1

2 Fasten the remote controller on a flat surface.


2

1 N•m
0.7 N•m
5
N

2
1

NOTICE
4 6
Be careful NOT to distort the shape of the lower part of the
ON I remote controller by overtightening the mounting screws.
A
3 Connect the terminals of the remote controller and the terminals
inside the unit (P1 to P1, P2 to P2) as shown in the figure.
f
NOTICE
P1
P2

P1
P2

a a
When the main switch is the in OFF position, it is possible
to lock the main switch using a suitable padlock. See the
figure below.
Keep in mind that in this case the padlock needs to be b
opened and removed before it is possible to turn the main
switch to the ON position.

P2 P1 P2 P1
N

2
c
1

ON I

OFF
O

d e
a Unit
b Rear part of the remote controller
5.4.4 To connect the power supply and c Front part of the remote controller
transmission cables d Wired from the rear
e Wired from the top
1 Open the electrical component box cover. f Use nippers to notch the part for the wiring to pass through

2 Using the appropriate cable, connect the power supply and NOTICE
communication cable(s) to the appropriate terminals as shown
▪ When wiring, run the wiring away from the power
on the wiring diagram.
supply wiring in order to avoid receiving electric noise
3 Fix the cables with cable ties to the cable tie mountings to (external noise).
ensure strain relief and to make sure that they do not come in
▪ Peel the shield for the part that has to pass through the
contact with the piping and sharp edges. Never squeeze
inside of the remote controller case (L).
bundled cables.
4 Close the electrical component box cover.
L
5.4.5 To install the remote controller 4 Reattach the upper part of the remote controller, starting with
The unit comes with a remote controller offering a user-friendly way the clips at the bottom.
to set up, use and maintain the unit. Before operating the remote
controller, follow this installation procedure.
1
Wire specification Value
Type 2 wire
Section 0.75~1.25 mm2

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
12 4P489435-1B – 2017.10
6 Configuration
CAUTION INFORMATION
Do NOT pinch the wiring when attaching. It is important that all information in this chapter is read
sequentially by the installer and that the system is
If, in addition to the standard remote controller, an optional remote
configured as applicable.
controller (EKRUAHTB) is installed as well:
5 Connect the electrical wires of both remote controllers as DANGER: RISK OF ELECTROCUTION
described.
6 Select a master and a slave remote controller using the SS1
selector switch. 6.2 Making field settings

6.2.1 About making field settings


PCB
S INFORMATION
SS1
M
The LEDs and buttons are located in the outdoor module
S Slave (not in the hydro module).
M Master
Making settings is done via the master unit.
INFORMATION Next to making field settings it is also possible to confirm the current
Only the remote controller set as master can be used as a operation parameters of the unit.
room thermostat. Pushbuttons and DIP switches
INFORMATION Item Description
For multi unit control, connect the remote controller to the Pushbuttons By operating the pushbuttons it is possible to:
unit as instructed above. For all other units to be controlled
▪ Change the mode.
by this controller, connect P1 of the previous unit to P1 of
the next unit, P2 of the previous unit to P2 of the next unit, ▪ Perform field settings (demand operation,
etc. low noise, etc).
DIP switches ▪ DS1 (1): COOL/HEAT selector
P1 P2 P1 P2 P1 P2 ▪ DS1 (2~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
▪ DS2 (1~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.

See also:
P1 P2 ▪ "6.2.2 Field setting components" on page 14

This is limited to 16 PCBs, with EWAQ+EWYQ016~032 ▪ "6.2.3 To access the field setting components" on page 14
counting as 1 PCB, and EWAQ+EWYQ040~064 as 2 Mode 1 and 2
PCBs.
Mode Description
5.4.6 To install optional equipment Mode 1 Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
(monitoring
For the installation of optional equipment, refer to the installation contents can be monitored as well.
settings)
manual which is delivered with the optional equipment or the
addenda delivered with this unit. Mode 2 Mode 2 is used to change the field settings of
the system. Consulting the current field setting
(field settings)
value and changing the current field setting
value is possible.
6 Configuration In general, normal operation can be resumed
without special intervention after changing field
INFORMATION
settings.
It is important that all information in this chapter is read
Some field settings are used for special
sequentially by the installer and that the system is
operation (e.g., 1 time operation, recovery/
configured as applicable.
vacuuming setting, manual adding refrigerant
DANGER: RISK OF ELECTROCUTION setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
6.1 Overview: Configuration
See also:
This chapter describes what you have to do and know to configure
the system after it is installed. ▪ "6.2.4 To access mode 1 or 2" on page 14

It contains information about: ▪ "6.2.5 To use mode 1" on page 14

▪ Making field settings ▪ "6.2.6 To use mode 2" on page 15

▪ Switching between cooling and heating ▪ "6.2.7 Mode 1: Monitoring settings" on page 15
▪ "6.2.8 Mode 2: Field settings" on page 15

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 13
6 Configuration
To continue the configuration of the system, it is required to give
some input to the PCB of the unit. This chapter will describe how
manual input is possible by operating the pushbuttons/DIP switches
on the PCB and reading the feedback from the LEDs.
Make sure to re-attach the inspection cover into the electrical
INFORMATION component box cover after the job is finished.
If you get confused in the middle of the process, push BS1.
NOTICE
Then it returns to setting mode 1 (H1P is off).
Make sure that all outside panels, except for the service
cover on the electrical component box, are closed while
6.2.2 Field setting components working.
The components to make field settings are as follows: Close the lid of the electrical component box firmly before
TEST: C/H SELECT turning on the power.
MODE L.N.O.P. DEMAND MULTI
HWL: IND MASTER SLAVE

H1P H2P H3P H4P H5P H6P H7P H8P 6.2.4 To access mode 1 or 2
BS1 BS2 BS3 BS4 BS5 After the units are turned ON, the display goes to its default
MODE SET RETURN TEST RESET situation. From there, you can access mode 1 and mode 2.
BS1~BS5 Pushbuttons
H1P~H8P LEDs
Initialisation: default situation
ON ( ) OFF ( ) Flashing ( )
NOTICE
Pushbuttons Be sure to turn on the power 6 hours before operation in
Use the pushbuttons to make the field settings. order to have power running to the crankcase heater and
BS1 MODE: For changing the set mode to protect the compressor.
BS2 SET: For field setting
BS3 RETURN: For field setting Turn on the power supply of the outdoor unit, and turn on the
BS4 Not used external operation switch. After initialisation, the display indication
BS5 Not used
state will be as below (default situation when shipped from factory).
LEDs
The LEDs give feedback about the field settings, which are defined
as [Mode-Setting]=Value. Single unit
H1P Shows the mode Multi-unit Left unit (master)
H2P~H7P Shows the settings and values, represented in binary code
H8P NOT used for field settings, but used during initialisation Right unit (slave)
Example: If the default situation is not displayed after 10~12 minutes, check
[H1P - 32 + 16 + 8 + 4 + 2 + 1] the malfunction code. Solve the malfunction code accordingly.
Description
H1P H2P H3P H4P H5P H6P H7P The HAP LED flashes to indicate normal microcomputer operation.
Default situation Switching between modes
(H1P OFF) Use BS1 to switch between the default situation, mode 1 and
Mode 1 mode 2.
(H1P flashing)
a
Mode 2
S1

B
B

S1

(H1P ON)
S1
B
S1

[5
B

Setting 8
s]

0 + 0 + 8 + 0 + 0 + 0
(in mode 2) b c
(H2P~H7P = binary 8)
a Default situation (H1P OFF)
Value 4 b Mode 1 (H1P flashing)
0 + 0 + 0 + 4 + 0 + 0 c Mode 2 (H1P ON)
(in mode 2) BS1 Press BS1.
(H2P~H7P = binary 4) BS1 [5 s] Press BS1 for at least 5 s.

INFORMATION
6.2.3 To access the field setting components
If you get confused in the middle of the process, press BS1
Remove the inspection cover to carry out field settings. to return to the default situation.

a
6.2.5 To use mode 1
Mode 1 is used to monitor the status of the unit.
b
What How
Accessing monitoring Once mode 1 is selected (push BS1
mode 1 one time), you can select the wanted
setting. It is done by pushing BS2.
Operate the switches and pushbuttons with an insulated stick (such To quit and return to the Press BS1.
as a closed ball-point pen) to avoid touching of live parts. initial status

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
14 4P489435-1B – 2017.10
6 Configuration

6.2.6 To use mode 2 Value / Description


H6P Shows the status of low noise operation.
The master unit should be used to input field settings in
mode 2. OFF
Mode 2 is used to set field settings of the outdoor unit and system. Unit is currently not operating under low noise
restrictions.
What How
ON
Changing and accessing Once mode 2 is selected (push BS1 for
Unit is currently operating under low noise
the setting in mode 2 more than 5 seconds), you can select
restrictions.
the wanted setting. It is done by pushing
BS2. Low noise operation reduces the sound generated by the
unit compared to nominal operating conditions.
Accessing the selected setting's value is
done by pushing BS3 1 time. Low noise operation can be set in mode 2. There are two
methods to activate low noise operation of the compressor
To quit and return to the Press BS1.
unit and heat exchanger unit.
initial status
Changing the value of the ▪ Once mode 2 is selected (push BS1 ▪ The first method is to enable an automatic low noise
selected setting in mode 2 for more than 5 seconds) you can operation during night time by field setting. The unit will
select the wanted setting. It is done operate at the selected low noise level during the
by pushing BS2. selected time frames.

▪ Accessing the selected setting's value ▪ The second method is to enable low noise operation
is done by pushing BS3 1 time. based on an external input. For this operation an optional
accessory is required.
▪ Now BS2 is used to select the
H7P Shows the status of power consumption limitation operation.
required value of the selected setting.
OFF
▪ When the required value is selected,
you can define the change of value Unit is currently not operating under power
by pushing BS3 1 time. consumption limitations.
▪ Press BS3 again to start operation ON
according to the chosen value. Unit is currently operating under power
consumption limitation.
6.2.7 Mode 1: Monitoring settings Power consumption limitation reduces the power
consumption of the unit compared to nominal operating
In mode 1 (and in default situation) you can read out the following conditions.
information:
Power consumption limitation can be set in mode 2. There
Value / Description are two methods to activate power consumption limitation of
H2P Shows the present operation state. the compressor unit.
OFF ▪ The first method is to enable a forced power consumption
limitation by field setting. The unit will always operate at
Normal operation state.
the selected power consumption limitation.
ON
▪ The second method is to enable power consumption
Abnormal operation state. limitation based on an external input. For this operation
FLASHING an optional accessory is required.
Under preparation or under test preparation

6.2.8 Mode 2: Field settings


Press the BS2 button to make field settings to configure the system. The LEDs give a binary representation of the setting/value number.

Setting Value
(= binary) Description
Deactivated.
Fan high static pressure setting. (default)
In order to increase the static pressure the outdoor unit fan is Activated.
delivering, this setting should be activated.
Deactivated
Automatic low noise setting and level during night time. (default)
By changing this setting, you activate the automatic low noise Level 1 Level 3<Level 2<Level 1
operation function of the unit and define the level of operation. Level 2
Depending on the chosen level, the noise level will be lowered.
Level 3

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 15
6 Configuration
Setting Value
(= binary) Description
Level 1 Level 3<Level 2<Level 1
Low noise operation level via the external control adaptor. Level 2
If the system needs to be running under low noise operation (default)
conditions when an external signal is sent to the unit, this setting Level 3
defines the level of low noise that will be applied.
This setting will only be effective when the optional external control
adaptor (DTA104A62) is installed and setting [2‑12] was activated.
Level 1 Level 3<Level 2<Level 1
Power consumption limitation level via the external control adaptor Level 2
(DTA104A62) (default)
If the system needs to be running under power consumption Level 3
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied. The level is according to the table.
Deactivated.
Enable the low noise function and/or power consumption limitation (default)
via the external control adaptor (DTA104A62). Activated.
If the system needs to be running under low noise operation or
under power consumption limitation conditions when an external
signal is sent to the unit, this setting should be changed. This
setting will only be effective when the optional external control
adaptor (DTA104A62) is installed in the indoor unit.

6.2.9 Field settings on the remote controller 4 Press and to change the value of the selected
field setting.
The user can change the field settings using the remote controller.
5 Press to save the new value.
Each field setting is assigned a 3-digit number or code, e.g. [5-03],
6 Repeat the previous steps to change other field settings as
which is indicated on the remote controller display. The first digit [5]
required.
is the 'first code' or field setting group. The second and third digit [03]
together are the 'second code'. 7 When finished, press to exit the field setting mode.

INFORMATION
▪ Changes made to a specific field setting are only stored
when is pressed. Navigating to a new field setting
code or pressing will discard any changes.
▪ Field settings are grouped by their first code, e.g. field
b settings [0-00]; [0-01]; [0-02]; [0-03] are defined as
a
"Group 0". When different values are changed within
c
the same group, pressing will save all the values
changed within this group.

INFORMATION
▪ Before shipping, the set values have been set as
shown in "6.2.9 Field settings on the remote
controller" on page 16.
▪ When exiting the field setting mode, " " may be
displayed on the remote controller LCD while the unit
initializes itself.

[0] Remote control setup


1 Press for a minimum of 5 seconds to enter the field setting
mode. [0‑00] User permission level

Result: (c), the current selected field setting code The user permission level defines which buttons and functions are
(b) and the set value (a) are displayed. available for the user. By default no level is defined, so all buttons
and functions are operable.
2 Press to select the appropriate field setting first code.
3 Press to select the appropriate field setting second [0‑00] Description
code. 2 Permission level 2
3 Permission level 3

Master Slave Permission level 2 Permission level 3


Operation ON/OFF
Setting the leaving water temperature —

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
16 4P489435-1B – 2017.10
6 Configuration
Master Slave Permission level 2 Permission level 3
Setting the room temperature
Quiet mode ON/OFF — —
Weather dependent setpoint operation ON/OFF —
Setting the clock — —
Programming the schedule timer — — —
Schedule timer operation ON/OFF —
Field settings — — —
Error code display
Test operation — —

After entering the field setting, the selected permission level must be Space heating based on ON/OFF instruction
enabled by simultaneously pressing and , immediately
Press The schedule timer for space heating and the
followed by simultaneously pressing and . Keep all 4 buttons
quiet mode stops and will not start again.
pressed for at least 5 seconds. Note that no indication on the remote
controller is given. After the procedure the blocked buttons will not The schedule timer icon is not displayed any
be available anymore. more.
Deactivating the selected permission level is done in the same way. ▪ Operation example: Schedule timer based on ON/OFF instruction.
[0‑01] Room temperature compensation value When the setback function (see field setting [2]) is enabled, the
setback operation will have priority over the scheduled action in
If necessary, it is possible to adjust some thermistor value of the unit the schedule timer if ON instruction is active. If OFF instruction is
by a correction value. This can be used as countermeasure for active this will have priority over the setback function. At any time
thermistor tolerances or capacity shortage. the OFF instruction will have the highest priority.
The compensated temperature (= measured temperature plus ON OFF ON
compensation value) is then used to control the system and will be
B
displayed in the temperature read-out mode. See also field 22°C
setting [9] in this chapter for compensation values for leaving water 45°C 21°C
temperature. 1 44°C
19°C 19°C
[0-02] 42°C 42°C

This setting is not applicable. t


16:00 0:30 6:30 9:00
[0‑03] Status
Defines whether the ON/OFF instruction can be used in the
schedule timer for space heating.

[0‑03] Description
2 18°C
0 Space heating schedule timer based on ON/
40°C
OFF instruction. t
1 (default) Space heating schedule timer based on 23:00 5:00
temperature setpoint. A
B ON OFF ON
Space heating based on ON/OFF instruction
During operation When the schedule timer switches space 22°C
45°C 21°C
heating OFF, the controller will be switched off
(operation LED will stop working). 19°C 44°C 19°C
18°C
Press The schedule timer for space heating will stop 3 42°C 42°C
40°C
(when active at that moment) and will start t
again at the next scheduled ON function.
16:00 23:00 6:30 9:00
The "last" programmed command overrules the 1 Schedule timer
"preceding" programmed command and will 2 Setback function
remain active until the "next" programmed 3 Both setback function and schedule timer are enabled
A Setback function
command occurs.
B ON/OFF instruction
Example: imagine the actual time is 17:30 and t Time
T Temperature setpoint
actions are programmed at 13:00, 16:00 and
Room temperature
19:00. The "last" programmed command Leaving water temperature
(16:00) overruled the "previous" programmed
command (13:00) and will remain active until Space heating based on temperature setpoint(a)
the "next" programmed command (19:00) During operation During schedule timer operation the operation
occurs. LED is lit continuously.
So in order to know the actual setting, you Press The schedule timer for space heating stops
should consult the last programmed command and will not start again.
(this may date from the day before).
The controller is switched off (operation LED
The controller is switched off (operation LED off).
off), but the schedule timer icon remains on.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 17
6 Configuration
Space heating based on temperature setpoint(a) INFORMATION
Press The schedule timer for space heating and the ▪ The setback function is enabled by default.
quiet mode stops and will not start again.
▪ The setback function can be combined with the
The schedule timer icon is not displayed any automatic weather dependent setpoint operation.
more.
▪ Setback function is an automatic daily scheduled
(a) For leaving water temperature and/or room temperature function.
▪ Operation example: Schedule timer based on temperature
Setback configured for room temperature control
setpoint
When the setback function (see field setting [2]) is enabled, the
T
setback operation will have priority over the scheduled action in the A 21°C
schedule timer.
T B 18°C
22°C
45°C 21°C t
1 44°C 19°C [2-01] [2-02]
19°C 19°C
42°C 42°C 42°C A Normal room temperature setpoint
B Room setback temperature [5-03]
t Time
T Temperature
t
Setback configured for leaving water temperature control
16:00 0:30 6:30 9:00
T T
A 45°C
5°C [5-02]
2
18°C B 40°C
40°C
t
37°C t [2-01] [2-02]
23:00 5:00 A Normal leaving water temperature setpoint
A B Leaving water setback temperature [5-02]
T t Time
T Temperature
22°C
45°C 21°C See field setting [5] in this chapter for temperature setpoints.
3 19°C 19°C 44°C 19°C [2‑00] Status
42°C 18°C 42°C 42°C
40°C [2‑00] Description
0 The setback function is disabled.
37°C t 1 The setback function is enabled.
16:00 23:00 0:30 5:00 6:30 9:00
1 Schedule timer [2‑01] Start time
2 Setback function Time at which setback is started.
3 Both setback function and schedule timer are enabled
A Setback function [2‑02] Stop time
t Time
T Temperature setpoint Time at which setback is stopped.
Room temperature
Leaving water temperature [3] Weather dependent setpoint
[0‑04] Status INFORMATION
Defines whether the ON/OFF instruction can be used in the This function is available for heat pump units operating in
schedule timer for cooling. heating mode ONLY. It does NOT exist for cooling.
This is the same as for space heating [0‑03], but the setback When weather dependent operation is active, the leaving water
function is not available. temperature is determined automatically depending on the outdoor
[1] Settings are not applicable temperature: colder outdoor temperatures will result in warmer water
and vice versa. The unit has a floating setpoint. Activating this
[2] Automatic setback function operation will result in a lower power consumption than use with a
INFORMATION manually fixed leaving water setpoint.

This function is available for heat pump units operating in During weather dependent operation, the user has the possibility to
heating mode ONLY. It does NOT exist for cooling. shift up or down the target water temperature by a maximum of 5°C.
This "Shift value" is the temperature difference between the
The setback function provides the possibility to lower the room temperature setpoint calculated by the controller and the real
temperature. It can be activated e.g. during the night, because setpoint. E.g. a positive shift value means that the real temperature
temperature demands during night and day are not the same. setpoint will be higher than the calculated setpoint.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
18 4P489435-1B – 2017.10
6 Configuration
It is advised to use the weather dependent setpoint because it [6‑01] Description
adjusts the water temperature to the actual needs for space heating.
0 (default) External room thermostat not installed.
It will prevent the unit from switching too much between thermo ON
operation and thermo OFF operation when using the remote 1 External room thermostat input 1 = heating
controller room thermostat or external room thermostat. operation ON (1)/OFF (0).
Tt External room thermostat input 2 = cooling
operation ON (1)/OFF (0).
2 External room thermostat input 1 = operation
Lo_Ti ON (1)/OFF (0).
+ 05 External room thermostat input 2 = cooling (1)/
Hi_Ti 00 Shift value heating (0).
– 05 [7] Option setup
[7‑00] Forced pump operation

Lo_A Hi_A TA [7‑00] Description


Tt Target water temperature 0 The pump performs intermittent sampling
TA Ambient (outdoor) temperature during thermo off conditions. This setting is
Shift value Shift value
often used when the unit is controlled by a
[3‑00] Low ambient temperature (Lo_A) room thermostat.
Low outdoor temperature. 1 (default) The pump continues operation during thermo
off conditions.
[3‑01] High ambient temperature (Hi_A)
High outdoor temperature. [8] Option setup

[3‑02] Setpoint at low ambient temperature (Lo_Ti) [8‑00] Remote controller temperature control

The target outgoing water temperature when the outdoor [8‑00] Description
temperature equals or drops below the low ambient temperature 0 (default) The unit operates in leaving water temperature
(Lo_A). control.
Lo_Ti should be higher than Hi_Ti, as warmer water is required for 1 The unit operates in room temperature control.
colder outdoor temperatures. This means that the remote controller is used
as a room thermostat, so the remote controller
[3‑03] Setpoint at high ambient temperature (Hi_Ti)
can be placed in the living room to control the
The target outgoing water temperature when the outdoor room temperature.
temperature equals or rises above the high ambient temperature
(Hi_A). Note: When the unit is operated in room temperature control (by
remote controller or external room thermostat option), room
Hi_Ti should be lower than Lo_Ti, as less warm water suffices for
temperature has priority over leaving water setpoint.
warmer outdoor temperatures.
[8-01]
INFORMATION
This setting is not applicable.
If the value of [3‑03] is mistakenly set higher than the value
of [3‑02], the value of [3‑03] will always be used. [8-03]
This setting is not applicable.
[4] Settings are not applicable
[8‑04] Freeze-up prevention
[5] Automatic setback
Freeze-up prevention will be activated by starting up the pump to
[5-00] circulate the water, and if the leaving or return water temperature is
This setting is not applicable. <5°C for 5 minutes, the unit will start up in heating mode to prevent
too low temperatures.
[5-01]
The freeze-up prevention is only active when the unit is in thermo
This setting is not applicable.
OFF condition.
[5‑02] Leaving water setback temperature The option can be enabled when there is no optional heater tape or
[5‑03] Room setback temperature glycol in the system and when heat can be used from an application.

[5-04] [8‑04] Description


This setting is not applicable. 0 (default) No freeze-up prevention

[6] Option setup 1 Freeze-up prevention level 1 (outdoor


temperature <4°C and leaving or return water
[6‑01] External room thermostat option temperature <7°C)
If an optional external room thermostat is installed, its operation 2 Freeze-up prevention level 2 (outdoor
must be enabled by this field setting. temperature <4°C)
The external room thermostat only gives an ON/OFF signal to the [9] Automatic temperature compensation
heat pump based on the room temperature. Because it does not give
continuous feedback information to the heat pump, it is If necessary, it is possible to adjust some thermistor value of the unit
supplementary to the remote controller room thermostat function. To by a correction value. This can be used as countermeasure for
have a good control of the system and avoid frequent ON/OFF it is thermistor tolerances or capacity shortage.
advised to use the automatic weather dependent setpoint operation.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 19
6 Configuration
The compensated temperature (= measured temperature plus [C‑00] Maximum leaving water setpoint in heating operation
compensation value) is then used to control the system and will be
[C‑01] Minimum leaving water setpoint in heating operation
displayed in the temperature read-out mode.
[C‑02] Maximum leaving water setpoint in cooling operation
[9‑00] Leaving water temperature compensation value for
heating operation [C‑03] Minimum leaving water setpoint in cooling operation
[9‑01] Leaving water thermistor auto corrective function This depends on field setting [A‑04].
This function will take into account the outdoor ambient conditions [C-04]
and correct the measured value which will be used for the logic.
This setting is not applicable.
E.g. when the ambient temperature is high during cooling mode, the
[d] Settings are not applicable
logic will correct the measured value of the leaving water thermistor
to a lower value to take into account influence of high ambient [E] Service mode
temperatures in the measurement.
[E‑00]
[9-02]
This setting is not applicable.
This setting is not applicable.
[E‑01]
[9‑03] Leaving water temperature compensation value for
This setting is not applicable.
cooling operation
[E‑02]
[9-04]
This setting is not applicable.
This setting is not applicable.
[E‑03]
[A] Option setup
This setting is not applicable.
[A-00]
This setting is not applicable. [E‑04] Pump only operation (air purge function)
When installing and commissioning the unit it is very important to
[A-01]
remove all air from the water circuit.
This setting is not applicable.
This field setting operates the pump to improve air removal from the
[A‑02] Return water temperature undershoot value unit without actually operating the unit. The pump will run for
10 minutes, stop 2 minutes, etc.
This setting makes it possible to set the allowable undershoot when
operating the unit during heating THERMO ON/OFF condition. [E‑04] Description
The unit will go in THERMO ON only if the return water temperature 0 (default) Normal operation of the unit
(RWT) goes below the setpoint minus the differential temperature:
1 Automatic air purge operation during
Thermo ON: RWT<Setpoint–(([A‑02]/2)+1) 108 minutes
The setting [A‑02] has a variability range from 0 to 15 and the step is 2 Automatic air purge operation during
1 degree. The default value is 5, meaning that the differential 48 minutes
temperature default value is 3.5.
[F] Option setup
[A‑03] Leaving water temperature overshoot/undershoot value
[F‑00] Return water temperature overshoot value
This setting makes it possible to set the allowable overshoot
This setting makes it possible to set the allowable overshoot when
(heating)/undershoot (cooling) when operating the unit during
operating the unit during cooling THERMO ON/OFF condition.
leaving water control.
The unit will go in THERMO ON only if the return water temperature
[A‑04] Glycol concentration setting
(RWT) goes above the setpoint plus the differential temperature:
This setting is only applicable for units with a low temperature
Thermo ON: RWT<Setpoint+(([F‑00]/2)+1)
cooling option.
The setting [F‑00] has a variability range from 0 to 15 and the step is
When changing this setting, the freeze prevention parameters will be
1 degree. The default value is 5, meaning that the differential
changed in relation with the glycol concentration.
temperature default value is 3.5.
[A‑04] Description
0 30% glycol, minimum leaving water=0°C 6.3 Switching between cooling and
1 40% glycol, minimum leaving water=–10°C heating
CAUTION Switching the unit between cooling and heating can be done in 2
different ways. This will depend on how the temperature is
Glycol concentrations lower than the set parameter will
controlled, i.e. based on room temperature or based on leaving
cause the fluid to freeze.
water temperature.
[b] Settings are not applicable If the unit control is based on room temperature (external room
[C] Leaving water temperature limits thermostat or remote controller room thermostat), switching between
cooling and heating is done through the remote controller by pushing
This setting is used to limit the selectable leaving water temperature
the cooling/heating button.
on the remote controller.
If the unit control is based on leaving water temperature, we suggest
using the ABC terminals on the outdoor unit (heat pump units only).
The location of the terminals is shown in the following figure.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
20 4P489435-1B – 2017.10
7 Commissioning
During test operation, the outdoor unit and the indoor units will start
up. Make sure that the preparations of all indoor units are finished
A1P A1P
(field piping, electrical wiring, air purge, ...). See installation manual
of the indoor units for details.

1 2
A-B-C

3
A-B-C
7.2 Checklist before commissioning
After the installation of the unit, first check the following items. Once
1 Hydrobox all below checks are fulfilled, the unit must be closed, only then can
2 Master unit (left unit)
3 Slave unit (right unit) if multi-system
the unit be powered up.
You read the complete installation and operation
ON instructions, as described in the installer and user
reference guide.
OFF
Installation
1 2 3 4 1 2 3 4
DS1 DS2 Check that the unit is properly installed, to avoid abnormal
noises and vibrations when starting up the unit.
1 Set DS1 on the outdoor master unit A1P PCB to the ON
Field wiring
position.
Be sure that the field wiring has been carried out
2 Press BS5 for 5 seconds to re-initialise communication of the
according to the instructions described in the chapter
module.
"5.4 Connecting the electrical wiring" on page 11,
▪ Cooling: voltage free contact between terminals A and C is according to the wiring diagrams and according to the
open applicable legislation.
▪ Heating: voltage free contact between terminals A and C is Power supply voltage
closed
X1A Check the power supply voltage on the local supply panel.
The voltage must correspond to the voltage on the
1
identification label of the unit.
EB0568(A)

Earth wiring
PHC1

PHC2

Be sure that the earth wires have been connected


properly and that the earth terminals are tightened.
R1 C1 R3 R4 C2 R2 Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation
X1M resistance of 2 MΩ or more is attained by applying a
A B C
voltage of 500 V DC between power terminals and earth.
Never use the megatester for the transmission wiring.
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally
INFORMATION
installed protection devices are of the size and type
Thermostat input has priority over leaving water specified in the chapter "4.3.1 Safety device
temperature setpoint. requirements" on page 8. Be sure that neither a fuse nor a
It is possible that the leaving water temperature becomes protection device has been bypassed.
lower than the setpoint if the unit is controlled by room Internal wiring
temperature.
Visually check the electrical component box and the
inside of the unit on loose connections or damaged
electrical components.
7 Commissioning Pipe size and pipe insulation

After installation and once the field settings are defined, the installer Be sure that correct pipe sizes are installed and that the
is obliged to verify correct operation. Therefore a test run must be insulation work is properly executed.
performed according to the procedures described below. The air purge valve is open (at least 2 turns).

Shut-off valves
7.1 Precautions when commissioning
Be sure that the shut-off valves are correctly installed and
CAUTION fully open.
Do not perform the test operation while working on the Filter
indoor units. Make sure that the filter is installed correctly.
When performing the test operation, not only the outdoor Damaged equipment
unit, but the connected indoor unit will operate as well.
Working on an indoor unit while performing a test operation Check the inside of the unit on damaged components or
is dangerous. squeezed pipes.
Water leak
NOTICE
Check the inside of the unit for water leakage. If there is a
Be sure to turn on the power 6 hours before operation in water leak, try to repair the leak. If the repair is
order to have power running to the crankcase heater and unsuccessful, close the water inlet and outlet shut-off
to protect the compressor. valves and call your local dealer.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 21
8 Troubleshooting
Installation date and field setting 7.3 Final check
Be sure to keep record of the installation date on the
Before switching on the unit, read the following recommendations:
sticker on the rear of the upper front panel according to
EN60335‑2‑40 and keep record of the contents of the field ▪ When the complete installation and all necessary settings have
setting(s). been carried out, be sure that all panels of the unit are closed. If
Schedule timer form this is not the case, inserting your hand through the remaining
openings can cause serious injury due to electrical and hot parts
Fill out the form at the very end of this document. When inside the unit.
programming the schedule timer, this form can help you
define the required actions for each day. ▪ The service panel of the electrical component box may only be
opened by a licensed electrician for maintenance purposes.
NOTICE
DANGER: RISK OF ELECTROCUTION
Operating the system with closed valves will damage the
Do NOT leave the unit unattended when the service cover
pump.
is removed.
Once all checks are fulfilled, the unit must be closed, only then can
the unit be powered up. When the power supply to the unit is turned INFORMATION
on, " " is displayed on the remote controller during its initialization, During the first running period of the unit, the required
which may take up to 30 seconds. During this process, the remote power may be higher than stated on the nameplate of the
controller cannot be operated. unit. This phenomenon is caused by the compressor, that
needs a continuous run time of 48 hours before reaching
smooth operation and stable power consumption.

8 Troubleshooting

8.1 Error codes: Overview


Main code Cause Solution
Failure writing memory (EEPROM error) Contact your local dealer.
Water circuit malfunction ▪ Check that water flow is possible (open all valves in the
circuit).
▪ Force clean water through the unit.
R410A expansion valve error (K11E/K12E) ▪ Check wiring connections.
▪ Contact your local dealer.
Water system warning ▪ Check filter.
▪ Make sure all valves are open.
▪ Contact your local dealer.
Capacity error Contact your local dealer.
Bad ACS communication Contact your local dealer.
R410A liquid thermistor error (R13T/R23T) ▪ Check wiring connections.
▪ Contact your local dealer.
Returning water thermistor error (R12T/R22T) ▪ Check wiring connections.
▪ Contact your local dealer.
Heating leaving water thermistor error (R11T/R12T) ▪ Check wiring connections.
▪ Contact your local dealer.
Remote controller thermostat thermistor error Contact your local dealer.
High pressure error (SENPH/S1PH) ▪ Check that the circuit does not contain any air.
▪ Check that water flow is possible (open all valves in the
circuit).
▪ Check that the water filter is not blocked.
▪ Check that all refrigerant stop valves are open.
▪ Contact your local dealer.
Low pressure error (SENPL) Contact your local dealer.
R410A suction thermistor error (R14T/R24T) ▪ Check wiring connections.
▪ Contact your local dealer.
Reversed power supply phase malfunction Correct phase order.
Insufficient supply voltage ▪ Check wiring connections.
▪ Contact your local dealer.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
22 4P489435-1B – 2017.10
9 Technical data
Main code Cause Solution
Two main remote controllers are connected (when using two Check that SS1 of one controller is set to MAIN, and the
remote controllers) other one to SUB. Turn the power supply off, and then back
on.
Type connection problem ▪ Wait until initialization between the outdoor module and
the hydro module is completed (wait at least 12 minutes
after power ON).
▪ Contact your local dealer.
Address error Contact your local dealer.

9 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin extranet (authentication required).

h2
9.1 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and F h1
1500
the minimum space for air inlet and air outlet is available (refer to the

500
figure below and choose one of the possibilities).
(mm)
a ABCD Sides along the installation site with obstacles
c b F Front side
Suction side

▪ If the location of the installation is in a cold climate, then


d
dimensions a and b above should be >500 mm to avoid
accumulation of ice in between the outdoor units.

A+B+C+D INFORMATION
Possibility 1 Possibility 2 Further specifications can be found in the technical
a≥300 mm a≥500 mm engineering data.

b≥100 mm b≥500 mm
c≥500 mm c≥500 mm
d≥500 mm d≥500 mm

9.2 Piping diagram: Outdoor module


Piping diagram: Outdoor module a Electronic expansion valve, subcooling (Y2E)
b Electronic expansion valve, main (Y1E)
a b c i d f e g h c Check valve
d Filter
e Fan
M f Fan motor (M1F, M2F)
g Heat exchanger
h Distributor
i Pressure regulating valve
j Accumulator
k 4-way valve, heat exchanger (Y3S)
l Solenoid valve, main (Y1S)
j k m High pressure sensor (SENPH)
n Solenoid valve (Y2S)
o Oil separator
d SV l SENPH m p High pressure switch
q Capillary tube
r Compressor (INV)
s Compressor (STD1)
c c c t Compressor (STD2)
d d d d u Low pressure sensor (SENPL)
o o o v Service port, refrigerant charge
n p d p d d p w Stop valve, liquid pipe
q x Stop valve, gas pipe
HPS HPS HPS
SV

d
r q s t
v INV STD1 STD2
q
q
w
u SENPL
4TW27245-1
x
4TW27255-1
4TW27275-1

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 23
9 Technical data
Piping diagram: Hydro module

A d+f m j a
b B b
R11T R14T

l C o
d+e c i b b p n
h R12T R13T

EWAQ*P*, EWYQ*P*, EWAQ*N*,


EWAQ*H*, EWYQ*H* EWYQ*N*, D
E
k g g
a Air purge valve
b Temperature sensors (R11T, R12T, R13T, R14T)
c Expansion vessel (12 l)
d Shut-off valve (field installed)
e Water inlet connection
f Water outlet connection
g Drain port
h Water filter
i Pressure gauge
j Flow switch
k Pump
l Safety valve
m Check valve
n Electronic expansion valve
o Heat exchanger
p Filter
A Water side
B Refrigerant side
C Only for models with a pump
D Refrigerant flow in cooling mode
E Refrigerant flow in heating mode

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
24 4P489435-1B – 2017.10
9 Technical data

9.3 Wiring diagram: Outdoor unit


Refer to the wiring diagram sticker on the outdoor module. The SD1 Safety devices input
abbreviations used are listed below:
T1A Current sensor
INFORMATION V1R Diode bridge
The wiring diagram on the outdoor module is only for the V1R, V1R Power module
outdoor module. For the hydro module or optional electrical X1A~X9A Connector
components, refer to the wiring diagram of the hydro
module. X1M Terminal strip (power supply)
X1M Terminal strip (control)
A1P~A8P Printed circuit board (main, sub 1, sub 2,
Y1E~Y5E Electronic expansion valve (main 1, sub cool
noise filter, inverter, fan, current sensor)
1, main 2, charge, sub cool 2)
BS1~BS5 Pushbutton switch (mode, set, return, test,
Y1S~Y10S Solenoid valve (RMTG, 4 way valve–H/E
reset)
gas 1, RMTL, hot gas, EV bypass 1, RMTT,
C1, C63, C66 Capacitor RMTO, 4 way valve–H/E gas 2,
E1HC, E2HC Crankcase heater EV bypass 2)
F1U Fuse (DC 650 V, 8 A) Z1C~Z10C Noise filter (ferrite core)
F1U Fuse (250 V, 3.15 A, T) Z1F Noise filter (with surge absorber)
F1U,F2U Fuse (250 V, 3.15 A, T) L1,L2,L3 Live
F5U Field fuse N Neutral
F400U Fuse (250 V, 6.3 A, T) Field wiring
H1P~H8P Pilot lamp Terminal strip
H2P Under preparation or in test operation when Connector
blinking Terminal
H2P Malfunction detection when light up Protective earth (screw)
HAP Pilot lamp (service monitor - green)
BLK Black
K1, K3 Magnetic relay
BLU Blue
K1R Magnetic relay (K2M, Y4S)
BRN Brown
K2, K4 Magnetic contactor (M1C)
GRN Green
K2R Magnetic relay (Y5S)
GRY Grey
K3R Magnetic relay (Y1S)
ORG Orange
K4R Magnetic relay (Y8S)
PNK Pink
K5R Magnetic relay (Y2S)
RED Red
K5R Magnetic relay (for option)
WHT White
K6R Magnetic relay (Y8S)
YLW Yellow
K7R, K8R Magnetic relay (E1HC, E2HC)
K11R Magnetic relay (Y3S)
L1R Reactor Hydro module
M1C, M2C Motor (compressor) A1P Main printed circuit board (master)
M1F, M2F Motor (fan) A2P Remote controller printed circuit board
PS Switching power supply A3P Control printed circuit board
Q1DI Earth leakage protector (field supply) A4P Demand printed circuit board (optional)
Q1RP Phase reversal detection circuit A5P Main printed circuit board (slave)
R10 Resistor A6P Demand printed circuit board (optional)
R50, R59 Resistor A7P Remote controller printed circuit board
R90 Resistor (current sensor) (optional)
R95 Resistor (current limiting) C1~C3 Filter capacitor
R1T Thermistor (air, fin) E1H Electrical component box heater
R2T~R15T Thermistor (H/E gas 1, H/E de-icer 1, sub E2H Plate heat exchanger heater (PHE1)
cool H/E gas 1, sub cool H/E liquid, H/E E3H Plate heat exchanger heater (PHE2)
liquid 1, suction 1, liquid 1, suction 2, H/E
E4H Water piping heater
gas 2, H/E de-icer 2, sub cool H/E gas 2,
liquid 2, H/E liquid 2) E5H Expansion vessel heater
R31T, R32T Thermistor (discharge) (M1C, M2C) F1, F2 Fuse (250 V, 5 A, F)
S1NPH Pressure sensor (high) F1U (A*P) Fuse (250 V, 3.15 A, T)
S1NPL Pressure sensor (low) HAP Printed circuit board LED
S1PH~S3PH Pressure switch (high) K11E Electronic expansion valve (PHE1)
K21E Electronic expansion valve (PHE2)

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 25
10 About the system
K1P Pump contactor S1F Flow switch (PHE1)
K1S Pump overcurrent relay S2F Flow switch (PHE2)
K*R (A3P) Printed circuit board relay S1M Main switch
M1P Pump S1S Thermostat ON/OFF input (field supply)
PS (A*P) Switching power supply S2S Thermostat cooling/heating selection (field
Q1DI Earth leakage circuit breaker (field supply) supply)

Q1T Thermostat for expansion vessel heater S3S Operation ON input (field supply)

R11T Leaving water thermistor (PHE1) S4S Operation OFF input (field supply)

R12T Returning water thermistor (PHE1) SS1 (A1P, A5P) Selector switch (emergency)

R13T Refrigerant liquid thermistor (PHE1) SS1 (A2P) Selector switch (master/slave)

R14T Refrigerant gas thermistor (PHE1) SS1 (A7P) Selector switch (master/slave) (optional)

R21T Leaving water thermistor (PHE2) V1C, V2C Ferrite core noise filter

R22T Returning water thermistor (PHE2) X1M~X4M Terminal strip

R23T Refrigerant liquid thermistor (PHE2) X801M (A*P) Printed circuit board terminal strip (control)

R24T Refrigerant gas thermistor (PHE2) Z1F, Z2F (A*P) Noise filter

For the user

a
10 About the system
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future
system extensions) is available in technical engineering
data and should be consulted. Contact your installer to
receive more information and professional advice.
This small inverter chiller can be combined with fan coil units for air
conditioning purposes, or it can be used for supplying water for b g
process cooling applications. c

d h
e i
10.1 System layout
j
f
Your small inverter chiller can be one of following models: k

Model Description a ON/OFF button


b Quiet mode button
EWAQ Air-to-water cooling only model. c Programming button
EWYQ Air-to-water heat pump model. d Weather dependent setpoint button (heat pump units
only)
e Schedule timer button
f Inspection/test operation button
g The / button is used to select the operation mode:
11 User interface space heating ( ) or space cooling ( ).
h button
i Room temperature adjust buttons and
CAUTION
j Leaving water temperature adjust buttons and
NEVER touch the internal parts of the controller.
k Time adjust buttons and
Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen. Icon Description
For checking and adjusting the internal parts, contact your Operation LED
dealer.
Lit during space heating operation. Blinks if a
malfunction occurs. When the LED is off, space
heating is inactive while the other operation modes
can still be active.
Heating mode
Cooling mode
Quiet mode

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
26 4P489435-1B – 2017.10
12 Operation
Icon Description Icon Description
External control Programming actions for each day of the schedule
timer.
The unit is working in a forced operation. As long as
this icon is displayed, the remote controller cannot be The OFF action is selected when programming the
operated. schedule timer.
The compressor in the unit of the installation is active. Field setting mode
The circulation pump is active. Inspection required. Consult your dealer.
Defrost/start up mode (heat pump units only) Inspection required. Consult your dealer.
Flashes to display the outdoor ambient temperature. Test mode.
Weather dependent setpoint (heat pump units only) This is an error code; for service purposes only. Refer
to the error code list in "8.1 Error codes: Overview" on
The controller will adapt the leaving water
page 22.
temperature setpoint automatically, based on the
outdoor ambient temperature. Code from the field settings list. Refer to "6.2.9 Field
settings on the remote controller" on page 16.
The actual room temperature or room temperature
setpoint are shown. Also displayed when the
temperature setpoint is set in schedule timer
programming mode. See "12.3.5 Other operation
modes" on page 30 for more information.
12 Operation
Current temperature of the installation, either leaving
water temperature or actual room temperature. When 12.1 Operation range
changing the room temperature setpoint, the setpoint
will flash for 5 seconds and then return to the actual Use the system in the following temperature ranges for safe and
room temperature. effective operation.

A non-installed option is addressed or a function is not Cooling Heating


available. An unavailable function can mean Outdoor –15~43°C DB –15~35°C DB
insufficient permission level or can mean that a slave temperature
remote controller is used (see "6.2.9 Field settings on
the remote controller" on page 16).
Current day of the week. When reading or 12.2 Quick start-up
programming the schedule timer, the indicator shows
The flow chart shows the steps required for starting up space
the set day.
cooling/heating and allows the user to start up the system before
Current time. When reading or programming the reading the entire manual.
schedule timer, the clock display shows the action
time. See "12.3 Operating the system" on page 28 for more detailed
information.
The schedule timer is enabled.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 27
12 Operation

Select mode (heating h or cooling c)

Push bi or bj

Display: - starts to blink Display: "n"


Set desired room temperature The remote controller room
(e.g. 22°C) thermostat function is not installed

Push ébi or ébj

You have "room temperature You have "leaving water temperature


based" control of your system based" control of your system
(remote controller room (default)
thermostat is installed)

Set desired leaving water temperature (e.g. 45°C for


heating or 18°C cooling)

If the display is blank, automatic leaving water


temperature is enabled in heating operation

Push y

The 0 LED will light up and the unit will start

For further details and advised settings, see the


chapters about programming, space cooling
operation, and space heating operation.

12.3 Operating the system To set the clock


1 Hold down the button for 5 seconds.
12.3.1 About the clock Result: The clock read-out and the day of week indicator start
flashing.
INFORMATION
2 Press the or button to increase/decrease the time
▪ The clock must be set manually. Adjust the setting by 1 minute. Keep the button pressed to increase/decrease the
when switching from summertime to wintertime and time by 10 minutes.
vice versa.
3 Press the or button to display the previous or
▪ The clock cannot be adjusted if the controller is set to next day of the week.
permission level 2 or 3 (see field setting [0‑00] in
"6.2.9 Field settings on the remote controller" on 4 Press the button to confirm the current set time and day of
page 16). the week.

▪ A power failure of more than 2 hours will reset the clock 5 Press the button to cancel this procedure without saving.
and the day of the week. The schedule timer will Result: If no button is pressed for 5 minutes, the clock and day
continue operation, but with a disordered clock. Correct of the week will return to their previous setting.
the clock and the day of the week.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
28 4P489435-1B – 2017.10
12 Operation

12.3.2 About operating the system INFORMATION

If the main power supply is turned off during operation, operation will ▪ When an external room thermostat is installed, the
restart automatically after the power turns back on again. thermo ON/OFF is determined by the external room
thermostat. The remote controller is then operated in
the leaving water control mode and is not functioning
12.3.3 Space cooling operation as a room thermostat.
Space cooling can be controlled in 2 different ways: ▪ The remote controller ON/OFF status always has
▪ based on room temperature priority over the external room thermostat!

▪ based on leaving water temperature (default) INFORMATION


Setback operation and weather dependent setpoint are not
To switch space cooling on/off using room
available in the cooling mode.
temperature control
In this mode, cooling will be activated as required by the room 12.3.4 Space heating operation
temperature setpoint. The setpoint can be set manually or through
the schedule timer. Space heating is available for heat pump units only.

INFORMATION Space heating can be controlled in 2 different ways:

▪ When using room temperature control, space cooling ▪ based on room temperature
operation based on room temperature will have priority ▪ based on leaving water temperature (default)
over leaving water control.
▪ It is possible that the leaving water temperature To switch space heating on/off using room
becomes higher than the setpoint if the unit is temperature control
controlled by room temperature.
Room temperature control
1 Press to switch space cooling ( ) on/off. In this mode, heating will be activated as required by the room
Result: and the corresponding actual room temperature temperature setpoint. The setpoint can be set manually or through
setpoint appear on the display. The operation LED lights up. the schedule timer.
2 Set the desired room temperature using and . For INFORMATION
setup of the schedule timer function, see "12.3.6 Schedule
timer" on page 30. ▪ When using room temperature control, space heating
operation based on room temperature will have priority
INFORMATION over leaving water control.
Temperature range for cooling: 16°C~32°C (room ▪ It is possible that the leaving water temperature
temperature) becomes higher than the setpoint if the unit is
controlled by room temperature.
3 Select the leaving water temperature which you want to be
used to cool down your system using and . For 1 Press to switch space heating ( ) on/off.
detailed information, see "To switch space cooling on/off using
Result: and the corresponding actual room temperature
leaving water temperature control" on page 29. setpoint appear on the display. The operation LED lights up.

To switch space cooling on/off using leaving water 2 Set the desired room temperature using and . In
temperature control order to avoid overheating, space heating cannot be used when
the outdoor ambient temperature rises above a certain
In this mode, cooling will be activated as required by the water temperature (see "12.1 Operation range" on page 27). For
temperature setpoint. The setpoint can be set manually or through setup of the schedule timer function, see "12.3.6 Schedule
the schedule timer. timer" on page 30.
1 Press to switch space cooling ( ) on/off. INFORMATION
Result: and the corresponding actual room temperature Temperature range for heating: 16°C~32°C (room
setpoint appear on the display. The operation LED lights up.
temperature)
2 Set the desired leaving water temperature using and
. In case the unit has the low temperature cooling 3 Select the leaving water temperature which you want to be
option, lower leaving water temperatures (<5°C) are possible, used to heat up your system using and . For
depending on the glycol concentration setting. For more detailed information, see "To switch space heating on/off using
information, see field setting [9] in "6.2.9 Field settings on the leaving water temperature control" on page 30.
remote controller" on page 16. Automatic setback function
INFORMATION For the automatic setback function settings, see field setting [2] in
"6.2.9 Field settings on the remote controller" on page 16.
Temperature range for cooling: 5°C~20°C (leaving water
temperature) (–10°C~20°C when glycol is used).
For setup of the schedule timer function, see "To program space
cooling" on page 32, "To program space heating" on page 33, and
"To program quiet mode" on page 33.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 29
12 Operation
INFORMATION Automatic setback function

▪ flashes during setback operation. For the automatic setback function settings, see field setting [2] in
"6.2.9 Field settings on the remote controller" on page 16.
▪ While room temperature setback function is active,
leaving water setback operation is also performed (see
"To switch space cooling on/off using leaving water 12.3.5 Other operation modes
temperature control" on page 29). Start up operation
▪ Do not to set the setback value too low, especially During start up, on the display means that the heat pump is
during colder periods (e.g. winter time). It is possible still starting up.
that the room temperature cannot be reached (or it will
take much longer) because of the big temperature Defrost operation ( )
difference.
INFORMATION
The setback function provides the possibility to lower the room This function is available for heat pump units ONLY.
temperature. It can be activated e.g. during the night, because
temperature demands during night and day are not the same. In space heating operation, freezing of the outdoor heat exchanger
may occur due to low outdoor temperature. If this risk occurs, the
To switch space heating on/off using leaving water system goes into defrost operation. It reverses the cycle and takes
temperature control heat from the water system to prevent freezing of the outdoor
system. After a maximum of 15 minutes of defrost operation, the
In this mode, heating will be activated as required by the water system returns to space heating operation. Space heating operation
temperature setpoint. The setpoint can be set manually or through is not possible during defrost operation.
the schedule timer.
Quiet mode operation ( )
1 Press to switch space heating ( ) on/off.
Quiet mode operation means that the unit works at reduced
Result: and the corresponding actual room temperature compressor speed so that the noise produced by the unit drops. This
setpoint appear on the display. The operation LED lights up.
implies that it will take longer until the required temperature setpoint
2 Set the desired leaving water temperature using and is reached. Beware of this when a certain level of heating is required
. In order to avoid overheating, space heating cannot indoors.
be used when the outdoor ambient temperature rises above a
There are 3 different levels of quiet mode operation. The desired
certain temperature (see "12.1 Operation range" on page 27).
quiet mode is set through a field setting.
INFORMATION 1 Press to activate quiet mode operation.
Temperature range for heating: 25°C~50°C (leaving water Result: appears on the display. If the controller is set to
temperature) permission level 2 or 3 (see "6.2 Making field settings" on
page 13), the button cannot be used.
For setup of the schedule timer function, see "12.3.6 Schedule
timer" on page 30. 2 Press again to deactivate quiet mode operation.
Result: disappears from the display.
INFORMATION
The actual temperatures can be displayed on the remote controller.
▪ When an external room thermostat is installed, the
thermo ON/OFF is determined by the external room 3 Press for 5 seconds.
thermostat. The remote controller is then operated in Result: The leaving water temperature is displayed ( , / ,
the leaving water control mode and is not functioning and blink).
as a room thermostat.
4 Press and to display:
▪ The remote controller ON/OFF status always has
▪ The entering water temperature ( and / blink, and
priority over the external room thermostat!
flashes slowly).
Weather dependent setpoint operation ▪ The indoor temperature ( and / blink).
▪ The outdoor temperature ( and blink).
For the automatic setback function settings, see field setting [2] in
"6.2.9 Field settings on the remote controller" on page 16. 5 Press again to leave this mode. If no button is pressed, the
3 Press 1 time to select weather dependent setpoint remote controller leaves the display mode after 10 seconds.
operation (or 2 times when the remote controller room
thermostat function is used). 12.3.6 Schedule timer
Result: appears on the display as well as the shift value. The Press to enable or disable the schedule timer ( ).
shift value is not shown if it is 0.
Four actions per day can be programmed, making a total of 28
4 Set the shift value using and . actions per week.
Result: will be displayed as long as the weather dependent The schedule timer can be programmed in 2 different ways:
setpoint operation is enabled.
▪ based on the temperature setpoint (leaving water temperature and
INFORMATION room temperature)
Range for shift value: –5°C~+5°C ▪ based on the ON/OFF instruction.
5 Press to deactivate weather dependent setpoint operation. The programming method is set in the field settings. See
"6.2 Making field settings" on page 13. Before programming, fill out
6 Set the leaving water temperature using and .
the form at the very end of this document. This form can help you
INFORMATION define the required actions for each day.
During this operation, instead of showing the water
temperature setpoint, the controller shows the shift value
which can be set by the user.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
30 4P489435-1B – 2017.10
12 Operation
INFORMATION B ON OFF ON
▪ When power is restored after a power failure, the auto 22°C
restart function reapplies the remote controller settings
45°C 21°C
at the time of the power failure (if the power was 1 44°C
19°C 19°C
interrupted for less than 2 hours). It is therefore
42°C 42°C
recommended to leave the auto restart function
enabled. t
▪ As the programmed schedule is time driven, it is 16:00 0:30 6:30 9:00
essential to set the clock and the day of the week
correctly. See "12.3.1 About the clock" on page 28.
▪ Schedule timer actions will only be executed when the
schedule timer is enabled ( visible on the display)!
2 18°C
▪ The programmed actions are not stored according to
40°C
their time of execution, but according to the time of t
programming, i.e. action number 1 is the action that
23:00 5:00
was programmed first, even though it may be executed A
after other programmed action numbers. ON OFF ON
B
▪ If 2 or more actions are programmed for the same day
and at the same time, only the action with the lowest 22°C
45°C 21°C
action number will be executed.
19°C 44°C 19°C
Space heating 18°C
3 42°C 42°C
40°C
[0‑03] Status t
Defines whether the ON/OFF instruction can be used in the 16:00 23:00 6:30 9:00
schedule timer for space heating. 1 Schedule timer
2 Setback function
Space heating based on ON/OFF instruction 3 Both setback function and schedule timer are enabled
A Setback function
During operation When the schedule timer switches space
B ON/OFF instruction
heating OFF, the controller will be switched off t Time
(operation LED will stop working). T Temperature setpoint
Room temperature
Press The schedule timer for space heating will stop Leaving water temperature
(when active at that moment) and will start
again at the next scheduled ON function. Space heating based on temperature setpoint(a)
The "last" programmed command overrules the During operation During schedule timer operation the operation
"preceding" programmed command and will LED is lit continuously.
remain active until the "next" programmed Press The schedule timer for space heating stops
command occurs. and will not start again.
Example: imagine the actual time is 17:30 and The controller is switched off (operation LED
actions are programmed at 13:00, 16:00 and off).
19:00. The "last" programmed command
Press The schedule timer for space heating and the
(16:00) overruled the "previous" programmed
quiet mode stops and will not start again.
command (13:00) and will remain active until
the "next" programmed command (19:00) The schedule timer icon is not displayed any
occurs. more.
So in order to know the actual setting, you (a) For leaving water temperature and/or room temperature
should consult the last programmed command ▪ Operation example: Schedule timer based on temperature
(this may date from the day before). setpoint
The controller is switched off (operation LED When the setback function (see field setting [2]) is enabled, the
off), but the schedule timer icon remains on. setback operation will have priority over the scheduled action in the
Press The schedule timer for space heating and the schedule timer.
quiet mode stops and will not start again.
The schedule timer icon is not displayed any
more.

▪ Operation example: Schedule timer based on ON/OFF instruction.


When the setback function (see field setting [2]) is enabled, the
setback operation will have priority over the scheduled action in
the schedule timer if ON instruction is active. If OFF instruction is
active this will have priority over the setback function. At any time
the OFF instruction will have the highest priority.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 31
12 Operation
T To program space cooling
22°C
45°C 21°C
1 44°C 19°C
19°C 19°C
42°C 42°C 42°C

t
16:00 0:30 6:30 9:00
T

2
18°C
40°C

37°C t 5 sec
23:00 5:00
A
T
22°C
45°C 21°C
3 19°C 19°C 44°C 19°C
42°C 18°C 42°C 42°C
40°C

37°C t
16:00 23:00 0:30 5:00 6:30 9:00
1 Schedule timer
2 Setback function
3 Both setback function and schedule timer are enabled
A Setback function
t Time 5 sec
T Temperature setpoint
Room temperature
Leaving water temperature
INFORMATION
INFORMATION
Press to return to previous steps in the programming
Space heating based on temperature setpoint is enabled procedure without saving modified settings.
by default, so only temperature shifts are possible (no ON/
OFF instruction). 1 Press to enter the programming/consulting mode.
2 Select the operation mode you would like to program using
Space cooling
and .
[0‑04] Status
Result: The actual mode is blinking.
Defines whether the ON/OFF instruction can be used in the
3 Press to confirm the selected mode.
schedule timer for cooling.
Result: The time is blinking.
This is the same as for space heating [0‑03], but the setback
function is not available. 4 Consult the action(s) using and .
5 Hold down for 5 seconds to program the detailed actions.
INFORMATION
Result: The first programmed action appears.
Space cooling based on temperature setpoint is enabled
by default, so only temperature shifts are possible (no ON/ 6 Select the action number you would like to program or to modify
OFF instruction). using .
7 Set the correct action time using and .
Quiet mode
8 Set the leaving water temperature using and .
See "To program quiet mode" on page 33.
9 Set the room temperature using and .
Switch the mode on or off at a scheduled time. Four actions can be
programmed per day. These actions are repeated daily. 10 Select using to switch cooling and the remote
controller off.
11 Repeat this procedure to program the other actions.
Result: When all actions have been programmed, make sure
that the display shows the highest action number you would like
to save.
12 Press for 5 seconds to store the programmed actions.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
32 4P489435-1B – 2017.10
12 Operation
Result: If is pressed when action number 3 is displayed, Result: The actual day is blinking.
actions 1, 2 and 3 are stored, but action 4 is deleted. You
4 Select the day you would like to consult or to program using
automatically return to step 6. Press several times to return
to previous steps in this procedure and finally return to normal and .
operation. Result: The selected day is blinking.
13 You automatically return to step 6; start again to program the 5 Press to confirm the selected day.
following day.
6 Hold down for 5 seconds to program the detailed actions.
To program space heating Result: The first programmed action of the selected day
appears.
7 Select the action number you would like to program or to modify
using .
8 Set the correct action time using and .
9 Set the leaving water temperature using and .
10 Set the room temperature using and .
11 Press to select:
▪ : to switch heating and the remote controller off.
▪ : to select automatic temperature calculation for leaving
water temperature
12 Set the appropriate shift value using and . For
more information about weather dependent setpoint, see
"12.3.6 Schedule timer" on page 30.
13 Repeat this procedure to program the other actions of the
selected day.
Result: When all actions have been programmed, make sure
that the display shows the highest action number you would like
to save.
14 Press for 5 seconds to store the programmed actions.
Result: If is pressed when action number 3 is displayed,
actions 1, 2 and 3 are stored, but action 4 is deleted. You
5 sec automatically return to step 6. Press several times to return
to previous steps in this procedure and finally return to normal
operation.
15 You automatically return to step 6; start again to program the
following day.

To program quiet mode

5 sec

INFORMATION
Press to return to previous steps in the programming
procedure without saving modified settings.
1 Press to enter the programming/consulting mode.
2 Select the operation mode you would like to program using
and .
Result: The actual mode is blinking.
3 Press to confirm the selected mode.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 33
12 Operation
INFORMATION To copy programmed actions to next day

Press to return to previous steps in the programming In space heating program it is possible to copy all programmed
procedure without saving modified settings. actions of a specific day to the next day (e.g. copy all programmed
actions from " " to " ").
1 Press to enter the programming/consulting mode.
2 Press .
2 Select the operation mode you would like to program using
Result: The actual mode is blinking.
and .
3 Select the mode you want to program using and .
Result: The actual mode is blinking.
Result: The selected mode is blinking. You can leave
3 Press to confirm the selected mode.
programming by pressing .
4 Consult the action(s) using and .
4 Press to confirm the selected mode.
5 Hold down for 5 seconds to program the detailed actions.
Result: The actual day is blinking.
Result: The first programmed action appears.
5 Select the day you would like to copy to the next day using
6 Select the action number you would like to program or to modify and .
using .
Result: The selected day is blinking. Press to return to
7 Set the correct action time using and . step 2.
8 Select or deselect as an action using . 6 Press and simultaneously for 5 seconds.
9 Repeat this procedure to program the other actions of the 7 After 5 seconds the display will show the next day (e.g. " " if
selected mode. " " was selected first). This indicates that the day has been
copied.
Result: When all actions have been programmed, make sure
that the display shows the highest action number you would like 8 Press to return to step 2.
to save.
To delete one or more programmed actions
10 Press for 5 seconds to store the programmed actions.
Deleting one or more programmed actions is done at the same time
Result: If is pressed when action number 3 is displayed, as storing the programmed actions.
actions 1, 2 and 3 are stored, but action 4 is deleted. You
automatically return to step 6. Press several times to return When all actions for one day have been programmed, make sure
to previous steps in this procedure and finally return to normal that the display shows the highest action number you would like to
operation. save. Pressing for 5 seconds stores all actions except those with a
11 You automatically return to step 6; start again to program the higher action number than the one that is displayed.
following day. Example: Pressing when action number 3 is displayed, stores
actions 1, 2 and 3, but deletes action 4.
To consult programmed actions
12.3.7 Operating the optional demand PCB
INFORMATION
Press to return to previous steps in the consulting An optional PCB EKRP1AHTA can be connected to the unit and be
procedure. used to remotely control the unit.
The 3 inputs allow:
1 Press to enter the programming/consulting mode.
▪ remote switching between cooling and heating
2 Select the operation mode you would like to consult using
and . ▪ remote thermo on/off
Result: The actual mode is blinking. ▪ remote unit on/off
3 Press to confirm the selected mode. For more details about this option kit, refer to the wiring diagram of
Result: The actual day is blinking. the unit.

4 Select the day you would like to consult using and INFORMATION
.
The signal (voltage free) must take at least 50 ms.
Result: The selected day is blinking.
See also field setting [6‑01] in "6.2.9 Field settings on the remote
5 Press to confirm the selected day. controller" on page 16 for setting the function of your preference.
Result: The first programmed action of the selected day
appears. 12.3.8 Operating the optional external control
6 Consult the other programmed actions of that day using adapter
and .
An optional control adapter PCB DTA104A62 can be connected to
Result: This is called the readout mode. Empty program the unit and be used to remotely control 1 or more units.
actions (e.g. 4) are not displayed. Press several times to
return to previous steps in this procedure and finally return to By short-circuiting contacts on the option kit PCB, you can:
normal operation. ▪ reduce capacity to about 70%,

Schedule timer tips and tricks ▪ reduce capacity to about 40%,


▪ force thermo off,
To program the next day(s)
▪ capacity save (fan low speed turn, compressor frequency control).
1 After confirming the programmed actions of a specific day,
press once. For more details about this option kit, refer to a separate instruction
that is delivered with the unit.
Result: You can now select another day using and
and restart consulting and programming.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
34 4P489435-1B – 2017.10
13 Maintenance and service

12.3.9 Operating the optional remote controller ▪ If repairs to the product are necessary within the warranty period,
contact your dealer and keep the warranty card at hand.
If besides the main remote controller the optional remote controller is
installed as well, the main remote controller (master) can access all 13.2.2 Recommended maintenance and
settings while the second remote controller (slave) can not access
schedule settings and parameter settings.
inspection
Refer to the installation manual for more details. Since dust collects when using the unit for several years,
performance of the unit will deteriorate to some extent. As taking
apart and cleaning interiors of units requires technical expertise and
in order to ensure the best possible maintenance of your units, we
13 Maintenance and service recommend to enter into a maintenance and inspection contract on
top of normal maintenance activities. Our network of dealers has
WARNING access to a permanent stock of essential components in order to
keep your unit in operation as long as possible. Contact your dealer
Never replace a fuse with a fuse of a wrong ampere ratings
for more information.
or other wires when a fuse blows out. Use of wire or
copper wire may cause the unit to break down or cause a When asking your dealer for an intervention, always state:
fire.
▪ The complete model name of the unit.
CAUTION ▪ The manufacturing number (stated on the nameplate of the unit).
Do not insert fingers, rods or other objects into the air inlet ▪ The installation date.
or outlet. Do not remove the fan guard. When the fan is
▪ The symptoms or malfunction, and details of the defect.
rotating at high speed, it will cause injury.

CAUTION
After a long use, check the unit stand and fitting for 14 Troubleshooting
damage. If damaged, the unit may fall and result in injury.
If one of the following malfunctions occur, take the measures shown
Water pressure below and contact your dealer.
Check whether the water pressure is above 1 bar. If it is lower, add WARNING
water.
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
13.1 About the refrigerant Leaving the unit running under such circumstances may
This product contains fluorinated greenhouse gases. Do NOT vent cause breakage, electric shock or fire. Contact your dealer.
gases into the atmosphere. The system must be repaired by a qualified service person:
Refrigerant type: R410A
Malfunction Measure
Global warming potential (GWP) value: 2087.5
If a safety device such as a fuse, a Turn off the main power
NOTICE breaker or an earth leakage breaker switch.
frequently actuates or the ON/OFF
In Europe, the greenhouse gas emissions of the total switch does not properly work.
refrigerant charge in the system (expressed as tonnes
CO2-equivalent) is used to determine the maintenance If water leaks from the unit. Stop the operation.
intervals. Follow the applicable legislation. The operation switch does not work Turn off the power.
well.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in If the user interface display indicates the Notify your installer and
kg] / 1000 unit number, the operation lamp flashes report the malfunction
and the malfunction code appears. code.
Please contact your installer for more information.
If the system does not properly operate except for the above
WARNING mentioned cases and none of the above mentioned malfunctions is
The refrigerant in the system is safe and normally does not evident, investigate the system according to the following
leak. If the refrigerant leaks in the room, contact with a fire procedures.
of a burner, a heater or a cooker may result in a harmful
Malfunction Measure
gas.
The remote controller ▪ Check if there is no power failure. Wait
Turn off any combustible heating devices, ventilate the
display is blank. until power is restored. If power failure
room and contact the dealer where you purchased the unit.
occurs during operation, the system
Do not use the system until a service person confirms that automatically restarts immediately after
the portion where the refrigerant leaks is repaired. power is restored.
▪ Check if no fuse has blown or breaker is
13.2 After-sales service and warranty activated. Change the fuse or reset the
breaker if necessary.
▪ Check if the benefit kWh rate power
13.2.1 Warranty period
supply is active.
▪ This product includes a warranty card that was filled in by the An error code is Consult your local dealer. Refer to
dealer at the time of installation. The completed card has to be displayed on the "8.1 Error codes: Overview" on page 22 for
checked by the customer and stored carefully. remote controller. a detailed list of error codes.

EWAQ016~064CAW + EWYQ016~064CAW Installation and operation manual


Packaged air-cooled water chiller
4P489435-1B – 2017.10 35
15 Relocation
Malfunction Measure
The schedule timer Check if the clock and the day of the week
works, but the are set correctly, and correct if necessary.
programmed actions
are executed at the
wrong time.
The schedule timer is In case is not displayed, push to
programmed, but does enable the schedule timer.
not work.
Capacity shortage. Consult your local dealer.
Temperature values on To switch the display between °C and °F,
the remote controller push and simultaneously for
are displayed in °F 5 seconds. The default temperature display
instead of in °C. is in °C.

If after checking all above items, it is impossible to fix the problem


yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

14.1 Error codes: Overview


In case a malfunction code appears on the indoor unit user interface
display, contact your installer and inform the malfunction code, the
unit type, and serial number (you can find this information on the
nameplate of the unit).
For your reference, a list with malfunction codes is provided. You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

15 Relocation
Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.

16 Disposal
This unit uses hydrofluorocarbon. Contact your dealer when
discarding this unit.

NOTICE
Do not try to dismantle the system yourself: the dismantling
of the system, treatment of the refrigerant, oil and other
parts must comply with applicable legislation. Units must
be treated at a specialised treatment facility for reuse,
recycling and recovery.

Installation and operation manual EWAQ016~064CAW + EWYQ016~064CAW


Packaged air-cooled water chiller
36 4P489435-1B – 2017.10
4P489435-1 B 00000004

Copyright 2017 Daikin

4P489435-1B 2017.10

You might also like